Carrier 17EX specifications MAINT01, MAINT02, MAINT03, MAINT04, Occdefm, Wsmdefme

Page 85

4.A high pressure point can also be calibrated between 240 and 260 psig (1655 and 1793 kPa) by attaching a regu- lated 250 psig (1724 kPa) pressure (usually from a ni- trogen cylinder). The high pressure point can be calibrated by accessing the appropriate transducer on the

STATUS01 screen, highlighting the transducer, pressing

the SELECT softkey, and then increasing or decreasing the value to the exact pressure on the refrigerant gage.

Press ENTER to ®nish. High altitude locations must com- pensate the pressure so that the temperature/pressure re- lationship is correct.

If the transducer reading returns to the previous value and the pressure is within the allowed range, check the volt- age ratio of the transducer. Refer to Step 3 above. The voltage ratio for this high pressure calibration must be between 0.585 and 0.634 vdc to allow calibration. Change the pressure at the transducer until the ratio is within the acceptable range. Then attempt to calibrate to the new pressure input.

The PIC will not allow calibration if the transducer is too far out of calibration. A new transducer must be installed and re-calibrated.

OIL DIFFERENTIAL PRESSURE/POWER SUPPLY MOD- ULE CALIBRATION Ð (See Fig. 48.) The oil reservoir in the 17EX chiller is not common to cooler pressure. There- fore, a comparison of pump output to cooler pressure can not be used to provide differential oil pressure information. A different method has been developed.

Oil transmission sump pressure and oil supply pressure are fed to a comparator circuit on a 5V power supply board. The output of this circuit, which represents differential oil pressure, is fed to the PSIO. The oil differential pressure is calibrated to 0 psid (0 kPad) by selecting the oil pressure input on the STATUS01 screen. Then, with the oil pump turned

OFF and the transducers connected, press the ENTER soft-

key to zero the point. No high end calibration is needed or possible.

17EX OIL PRESSURE INPUT

Fig. 48 Ð Oil Differential Pressure/Power

Supply Module

TROUBLESHOOTING TRANSDUCERS Ð When trouble- shooting transducers, keep the negative lead of your volt- ohmmeter on terminal U4 of the power supply (or terminal 4 on power supplies without the comparator circuit).

Voltage VO1 = (VH1-VL1) + .467 ± .1 V

For all PIC transducers:

Measured pressure = (507.97 × (V out/Vin) ) − 47.33

Vout = transducer output ref. to neg. terminal (4 or U4) i.e., VH1 to U4 or VL1 to U4

Vin = power supply output, i.e., U3 to U4

TRANSDUCER REPLACEMENT Ð Since the transduc- ers are mounted on Schrader-type ®ttings, there is no need to remove refrigerant from the vessel. Disconnect the trans- ducer wiring by pulling up on the locking tab while pulling up on the weather-tight connecting plug from the end of the transducer. Do not pull on the transducer wires. Unscrew the transducer from the Schrader ®tting. When installing a new transducer, do not use pipe sealer, which can plug the sensor. Put the plug connector back on the sensor and snap into place. Check for refrigerant leaks.

Make sure to use a backup wrench on the Schrader ®t- ting whenever removing a transducer.

Control Algorithms Checkout Procedure Ð One of the tables in the SERVICE menu is the CONTROL AL- GORITHM STATUS table. This table has 6 screens that may be viewed to see how a particular control algorithm is operating, that is, to see what parameters and values the PIC is using to control the chiller.

MAINT01

Capacity

The values used to calculate the chilled

 

Control

water/brine control point.

MAINT02

Override

Details of all chilled water control over-

 

Status

ride values

MAINT03

Surge/

The surge and hot gas bypass control

 

HGBP

algorithm status as well as the values

 

Status

dealing with this control.

MAINT04

LEAD/LAG

LEAD/LAG operation status.

 

Status

 

OCCDEFM

Time

The Local and CCN occupied sched-

 

Schedules

ules, displayed in a way that allows the

 

Status

operator to quickly determine whether

 

 

the schedule is in an occupied period

 

 

or not.

WSMDEFME

Water

The status of the WSM (water system

 

System

manager), a CCN module that can turn

 

Manager

on the chiller and change the chilled

 

Status

water control point.

These maintenance tables are very useful in determining guide vane position, reaction from load changes, control point overrides, hot gas bypass reaction, surge prevention, etc.

Control Test Ð The control test feature can check all the thermistor temperature sensors, including those on the Options modules, pressure transducers, pumps and their as- sociated ¯ow switches, the guide vane actuator, and other control outputs, such as hot gas bypass. The tests can help to determine whether a switch is defective, or a pump relay is not operating, among other useful troubleshooting tests.

During pumpdown operations, the pumps are energized to prevent freeze-up, and the vessel pressures and tempera- tures are displayed. The pumpdown/lockout feature pre- vents the compressor from starting up when there is no re- frigerant in the chiller or when the vessels are isolated. The operator then uses the terminate lockout screen to end the pumpdown lockout after the pumpdown procedure is re- versed and refrigerant is added.

85

Image 85
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents OCCPC01S Input Service Congurations Piping Check Relief Devices Inspect WiringCoupling Maintenance Motor Maintenance Inspect Water PipingContents Abbreviations Introduction17EX Chiller Familiarization Certified PerformanceTypical 17EX Chiller Components Lubrication Cycle OIL Cooling CycleRefrigeration, Cycle Starters17EX Compressor Lubrication Cycle Denitions ControlsMajor PIC Components Panel Locations Temperature Sensors See Fig Pressure TransducersPIC Component Panel Location Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations PIC LIDPsio GRD Equip GND ÐTewac PROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Operation and Menus FigGeneral LID Service Screen Override Operations YES or no , on or OFF , etc. to select the desired state17EX LID Menu Structure Default ScreenAlarm History Service TableEquipment Configuration Control TestCarrier Comfort Network CCNHgbp Ð Hot Gas Bypass LIDChwr SetpointChws HgbpLID Display Data Description Range Units Reference Point Name Alarm HistoryExample 1 Ð STATUS01 Display Screen Menu Status SelectExample 3 Ð STATUS03 Display Screen Example 2 Ð STATUS02 Display ScreenMenu Status Example 5 Ð Setpoint Display Screen Example 4 Ð STATUS04 Display ScreenMenu ECW Control Option Example 6 Ð Configuration Config Display ScreenICE Build Termination LAG =2, Standby =3 Example 7 Ð LEAD/LAG Configuration Display ScreenExample 8 Ð SERVICE1 Display Screen Spare Alert Enable Example 9 Ð SERVICE2 Display ScreenExample 10 Ð SERVICE3 Display Screen Menu ServiceExample 12 Ð Maintenance MAINT02 Display Screen Example 11 Ð Maintenance MAINT01 Display ScreenDischarge Temperature Bearing TemperatureExample 14 Ð Maintenance MAINT04 Display Screen Example 13 Ð Maintenance MAINT03 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen Example of Holiday Period Screen To Access the Service ScreensRecycle Sequence Fig START-UP/SHUTDOWNPage Job Data Required Before Initial START-UPEquipment Required MotorPage 17EX Leak Test Procedures Ð HFC-134a Pressure Ð Temperature C Ð HFC-134a Pressure Ð Temperature FTemperature F Temperature CDehydration Cold Trap Check Optional Pumpout Compressor Water Pip Inspect Wiring900 500 901 7000 1000 7001-14500 2500 Recommended Motor Fastener Tightening Torques External Gear Pre-Start ChecksExternal Gear Lubrication System Mechanical Starters Check StarterSOLID-STATE Starters Input the Design Set Points Ð To modify the set Set Up Chiller Control CongurationInput the Local Occupied Schedule OCCPC01S Surge Limiting or Change the LID Configuration if NecessaryT1/P1 Full Load Points T2/P2 Increase P1 by Decrease P1 by Load Surge Prevention Occurs TOO Soon Occurs TOO Late50% Initial START-UP Charge Refrigerant into ChillerControl Test Menu Functions Tests to be Devices Tested PerformedCheck Motor Rotation Dry Run to Test Start-Up SequenceInitial Motor START-UP Page Flange Nut Tightening Torques Low Speed Couplings Only Check Oil Pressure and Compressor Stop Calibrate Motor Current Demand SettingTo Prevent Accidental Start-Up Ð The PIC can be General RecommendationsOperator Duties Operating InstructionsStarting the Chiller Stopping the ChillerOperating the Optional Pumpout Compressor Pumpout and Refrigerant Transfer ProceduresPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View Valve Condition RLAReturn Chiller to Normal Operating Conditions General MaintenanceChecking Guide Vane Linkage Ð Refer to Fig Contact Seal Maintenance Refer to ÐContact Seal Page Checking Preliminary Alignment Chiller AlignmentMeasuring Angular Misalignment Elevation Alignment Formula HOT Alignment Check Adjusting Angular Misalignment in PlanDoweling Correcting Parallel MisalignmentScheduled Maintenance Weekly MaintenanceCheck Safety and Operating Controls Monthly Changing the Oil Filters17EX Chiller Oil Specications Compressor OILPumpout Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Controls for Optional Pumpout Compressor Troubleshooting GuidePage MAINT02 MAINT01MAINT03 MAINT04Oilpd 1CR AUXOilt PICAutorestart in Progress Starts Limit ExceededOperation FaultPotential FREEZE-UP Failure to StopRunning Ð Demand Limited Running Ð Temp ControlChiller Protect Limit Faults LOW OIL Pressure Sensor Fault AlertAlert Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Problem External Gear Troubleshooting GuidePossible Cause Ð Item NO.s Possible Cause ActionTemperature Voltage Resistance Drop Ð Thermistor Temperature F vs Resistance/Voltage DropTemperature Voltage Resistance Drop Ð Thermistor Temperature C vs Resistance/Voltage DropControl Modules Module SwitchModule Address Input Options ModuleStarter Management Module SMM Fig Processor/Sensor Input/Output Module Psio FigGRD Switch Setting Options Module Installation of NEW Psio ModuleFour-In/Two-Out Module Fig Options Module4-In/2-Out Module Physical Data and Wiring SchematicsWeight Vessel SIZE² Additional Cooler WeightsCondenser Total Weight Condenser Charge 100Compressor Weight and Elbow Weight Additional Condenser WeightsDrive Component Weights 101Ð Total Motor Weight, SI kg Ð Total Motor Weight, English lb102 NIH Waterbox Cover Weights Marine Waterbox Cover WeightsApproximate Refrigerant HCFC-134a Charge 103Relief Valve Locations and Data Auxiliary Systems, Electrical Data104 105 Compressor Fits and ClearancesClearance Type Description 106Measure 107 Tabulation Ð Impeller Clearances Open-Drive Compressors17FX 108 Temp 109Press Tewac110 111 112 General 113GND Ð Ground 114T1-T4 Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.