Carrier 17EX Load Surge Prevention Occurs TOO Soon Occurs TOO Late, Increase P1 by Decrease P1 by

Page 56

If surge prevention occurs too soon or too late, make the following adjustments:

LOAD

SURGE PREVENTION

SURGE PREVENTION

OCCURS TOO SOON

OCCURS TOO LATE

 

At low loads

Increase P1 by

Decrease P1 by

PERFORM AN AUTOMATED CONTROL TEST Ð Check the safety controls status by performing an automated con- trols test. Access the CONTROL TEST table from the SERV- ICE menu. This table has the following screens:

(,50%)

10 psid (70 kPad)

10 psid (70 kPad)

At high loads

Increase P2 by

Decrease P2 by

(.50%)

10 psid (70 kPad)

10 psid (70 kPad)

MODIFY EQUIPMENT CONFIGURATION IF NECES- SARY Ð The EQUIPMENT CONFIGURATION table has a number of screens to select, view, and/or modify. See Fig. 16 for the menu structure of this table. Carrier provides certi®ed drawings that have the con®guration values re- quired for speci®c jobsites. Modify these values only if requested.

CONFIG Screen Modi®cations Ð Change the values on this screen according to your job data. See certi®ed drawings for the correct values. Modi®cations can include:

·chilled water reset

·entering chilled water control (Enable/Disable)

·4 to 20 mA demand limit

·auto. restart option (Enable/Disable)

·remote contact option (Enable/Disable)

LEAD/LAG Screen Modi®cations Ð Change the values on this screen according to your job data. See certi®ed draw-

Automated Test

PSIO Thermistors

Options Thermistors

Transducers

Guide Vane Actuator

Pumps

Discrete Outputs

Pumpdown/Lockout

Terminate Lockout

FX Gear Oil Pump I/O

As described above, a complete control test.

Checks all PSIO thermistors only. Checks all options board thermistors. Checks all transducers.

Checks the guide vane operation.

Checks operation of pump output; either all pumps can be activated or individual pumps. Also tests the associated input such as ¯ow or pressure.

Activates all on/off outputs, all at once or individually.

Pumpdown prevents the low refrigerant alarm during evacuation so refrigerant can be removed from the unit, locks the compressor off. and starts the water pumps.

Charges refrigerant and enables the chiller to run after pumpdown lockout.

Activates external gear main oil pump and auxiliary oil pump (if supplied).

ings for speci®c values. Modi®cations can include:

·lead/lag selection

·load balance option

·common sensor option

·lag start/stop timers

·standby chiller option

Owner-Modi®ed CCN TablesÐ The following tables are de- scribed for reference only. For detailed information on CCN operations, consult the CCN supplement for your chiller.

·OCCDEFCS Screen Modi®cations Ð This table contains the local and CCN time schedules, which can be modi®ed here, or on the SCHEDULE screen as described previously.

·HOLIDEF Screen Modi®cations Ð This table con®gures the days of the year that holidays are in effect. See the holiday paragraphs in the Controls section for more details.

·BRODEF Screen Modi®cations Ð This table de®nes the outside-air temperature sensor and humidity sensor if one is to be installed. It also de®nes the start and end of day- light savings time. Enter the dates for the start and end of daylight savings, if required for your location. BRODEF also activates the Broadcast function, which enables the holiday periods de®ned on the LID to take effect.

·Other Tables Ð The ALARMDEF, CONS-DEF, RUNT- DEF, and WSMALMDF screens contain information for use with a CCN system. See the applicable CCN manual for more information on these screens. These screens can only be changed from a CCN Building Supervisor terminal.

CHECK VOLTAGE SUPPLY Ð Access the STATUS 01 screen and read the LINE VOLTAGE: ACTUAL value. This reading should be equal to the incoming power to the starter. Use a voltmeter to check incoming power at the starter power leads. If the readings are not equal, an adjustment can be made by selecting the LINE VOLTAGE: ACTUAL parameter and then increasing or decreasing the value so that the value appear- ing on the LID is calibrated to match the incoming power voltage reading. Voltage can be calibrated only between 90 and 100% of the rated line voltage.

Automated Test Ð Before running this test, be sure that the compressor is in the OFF mode and the 24-v input to the SMM is in range (per line voltage percent on STATUS01 screen). Put the compressor in OFF mode by pressing the STOP pushbutton on the LID.

The automated test starts with a check of the PSIO ther- mistors and proceeds through the rest of the tests listed in the table below. The test not only checks readings, such as temperature and pressure readings, but also lets the operator know if certain devices, such as pumps or relays, are on or off and if all outputs and inputs are functioning. It also sets the refrigerant type.

As each test is executed, the LID display shows which test is running as well as other pertinent data. At the end of each test, the LID displays, OK TO CONTINUE? If a test indicates a problem, error, or device malfunction, the op- erator can choose to address the problem as the test is being done or note the problem and proceed to the next test.

NOTE: If during the control test the guide vanes do not open, check to see that the low pressure alarm is not active. (This causes the guide vanes to close.)

NOTE: The oil pump test will not energize the oil pump if cooler pressure is below ±5 psig (±35 kPa).

When the test is ®nished, or the EXIT softkey is pressed,

the test stops and the CONTROL TEST menu is displayed. If a speci®c automated test procedure is not completed, ac- cess that test by scrolling to it and selecting it to test the function when ready. The CONTROL TEST menu is de- scribed in more detail in Table 8.

Check Pumpout System Controls and Optional Pumpout Compressor Ð The pumpout system con- trols include an on/off switch, a 3-amp fuse, the compressor overloads, an internal thermostat, a compressor contactor, and a refrigerant high pressure cutout. The high pressure cutout is factory set to open at 161 psig (1110 kPa) and reset at 130 psig (896 kPa). Check that the water-cooled condenser has been connected. Loosen the compressor holddown bolts to allow free spring travel. Open the compressor suction and discharge service valves. Check that oil is visible in the com- pressor sight glass. Add oil if necessary.

56

Image 56
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Piping Check Relief Devices Inspect Wiring OCCPC01S Input Service CongurationsCoupling Maintenance Motor Maintenance Inspect Water PipingContents 17EX Chiller Familiarization IntroductionAbbreviations Performance CertifiedTypical 17EX Chiller Components OIL Cooling Cycle Lubrication CycleStarters Refrigeration, Cycle17EX Compressor Lubrication Cycle Controls DenitionsTemperature Sensors See Fig Pressure Transducers Major PIC Components Panel LocationsPIC Component Panel Location Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations Psio LIDPIC Tewac Equip GND ÐGRD General LID Operation and Menus FigPROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Service Screen YES or no , on or OFF , etc. to select the desired state Override OperationsDefault Screen 17EX LID Menu StructureService Table Alarm HistoryEquipment Configuration Control TestCCN Carrier Comfort NetworkHgbp Ð Hot Gas Bypass LIDSetpoint ChwrChws HgbpDescription Range Units Reference Point Name Alarm History LID Display DataExample 1 Ð STATUS01 Display Screen Menu Status SelectMenu Status Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen Menu Example 4 Ð STATUS04 Display ScreenExample 5 Ð Setpoint Display Screen ICE Build Termination Example 6 Ð Configuration Config Display ScreenECW Control Option Example 7 Ð LEAD/LAG Configuration Display Screen LAG =2, Standby =3Example 8 Ð SERVICE1 Display Screen Example 9 Ð SERVICE2 Display Screen Spare Alert EnableExample 10 Ð SERVICE3 Display Screen Menu ServiceExample 11 Ð Maintenance MAINT01 Display Screen Example 12 Ð Maintenance MAINT02 Display ScreenDischarge Temperature Bearing TemperatureDescription RANGE/STATUS Units Reference Point Name Example 13 Ð Maintenance MAINT03 Display ScreenExample 14 Ð Maintenance MAINT04 Display Screen PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen To Access the Service Screens Example of Holiday Period ScreenSTART-UP/SHUTDOWN Recycle Sequence FigPage Before Initial START-UP Job Data RequiredEquipment Required MotorPage 17EX Leak Test Procedures Ð HFC-134a Pressure Ð Temperature F Ð HFC-134a Pressure Ð Temperature CTemperature F Temperature CDehydration Cold Trap 900 500 901 7000 1000 7001-14500 2500 Inspect WiringCheck Optional Pumpout Compressor Water Pip External Gear Pre-Start Checks Recommended Motor Fastener Tightening TorquesExternal Gear Lubrication System SOLID-STATE Starters Check StarterMechanical Starters Input the Local Occupied Schedule OCCPC01S Set Up Chiller Control CongurationInput the Design Set Points Ð To modify the set T1/P1 Full Load Points T2/P2 Change the LID Configuration if NecessarySurge Limiting or 50% Load Surge Prevention Occurs TOO Soon Occurs TOO LateIncrease P1 by Decrease P1 by Charge Refrigerant into Chiller Initial START-UPControl Test Menu Functions Tests to be Devices Tested PerformedInitial Motor START-UP Dry Run to Test Start-Up SequenceCheck Motor Rotation Page Flange Nut Tightening Torques Low Speed Couplings Only Calibrate Motor Current Demand Setting Check Oil Pressure and Compressor StopTo Prevent Accidental Start-Up Ð The PIC can be General RecommendationsOperating Instructions Operator DutiesStarting the Chiller Stopping the ChillerPumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View RLA Valve ConditionGeneral Maintenance Return Chiller to Normal Operating ConditionsContact Seal Maintenance Refer to Ð Checking Guide Vane Linkage Ð Refer to FigContact Seal Page Chiller Alignment Checking Preliminary AlignmentMeasuring Angular Misalignment Elevation Alignment Formula Adjusting Angular Misalignment in Plan HOT Alignment CheckCorrecting Parallel Misalignment DowelingWeekly Maintenance Scheduled MaintenanceCheck Safety and Operating Controls Monthly Changing the Oil FiltersPumpout Compressor OIL17EX Chiller Oil Specications Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Troubleshooting Guide Controls for Optional Pumpout CompressorPage MAINT01 MAINT02MAINT03 MAINT041CR AUX OilpdOilt PICStarts Limit Exceeded Autorestart in ProgressFault OperationPotential FREEZE-UP Failure to StopRunning Ð Temp Control Running Ð Demand LimitedChiller Protect Limit Faults Sensor Fault Alert LOW OIL PressureAlert Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY External Gear Troubleshooting Guide ProblemPossible Cause Ð Item NO.s Possible Cause ActionÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Temperature Voltage Resistance DropModule Switch Control ModulesModule Address Input Options ModuleGRD Processor/Sensor Input/Output Module Psio FigStarter Management Module SMM Fig Installation of NEW Psio Module Switch Setting Options ModuleFour-In/Two-Out Module Fig Options ModulePhysical Data and Wiring Schematics 4-In/2-Out ModuleAdditional Cooler Weights Weight Vessel SIZE²Condenser Total Weight Condenser Charge 100Additional Condenser Weights Compressor Weight and Elbow WeightDrive Component Weights 101102 Ð Total Motor Weight, English lbÐ Total Motor Weight, SI kg Marine Waterbox Cover Weights NIH Waterbox Cover WeightsApproximate Refrigerant HCFC-134a Charge 103104 Auxiliary Systems, Electrical DataRelief Valve Locations and Data Compressor Fits and Clearances 105Measure 106Clearance Type Description 17FX Tabulation Ð Impeller Clearances Open-Drive Compressors107 108 109 TempPress Tewac110 111 112 113 General114 GND Ð GroundT1-T4 Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.