Carrier 17EX specifications Running Ð Temp Control, Running Ð Demand Limited

Page 89

Table 12 Ð LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

I. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND

PRIMARY MESSAGE

SECONDARY MESSAGE

PROBABLE CAUSE/REMEDY

RUNNING Ð RESET ACTIVE

4-20MA SIGNAL

 

RUNNING Ð RESET ACTIVE

REMOTE SENSOR CONTROL

Reset program active based on CONFIG screen setup.

RUNNING Ð RESET ACTIVE

CHW TEMP DIFFERENCE

 

RUNNING Ð TEMP CONTROL

LEAVING CHILLED WATER

Default method of temperature control.

RUNNING Ð TEMP CONTROL

ENTERING CHILLED WATER

ECW control activated on CONFIG screen.

RUNNING Ð TEMP CONTROL

TEMPERATURE RAMP LOADING

Ramp loading in effect. Use SERVICE1 screen to modify.

RUNNING Ð DEMAND LIMITED

BY DEMAND RAMP LOADING

Ramp loading in effect. Use SERVICE1 screen to modify.

RUNNING Ð DEMAND LIMITED

BY LOCAL DEMAND SETPOINT

Demand limit set point is , actual demand.

RUNNING Ð DEMAND LIMITED

BY 4-20MA SIGNAL

 

RUNNING Ð DEMAND LIMITED

BY CCN SIGNAL

Demand limit is active based on CONFIG screen setup.

RUNNING Ð DEMAND LIMITED

BY LOADSHED/REDLINE

 

RUNNING Ð TEMP CONTROL

HOT GAS BYPASS

Hot gas bypass option is energized. See surge prevention in the

control section.

 

 

RUNNING Ð DEMAND LIMITED

BY LOCAL SIGNAL

Active demand limit manually overridden on STATUS01 table.

RUNNING Ð TEMP CONTROL

ICE BUILD MODE

Chiller is running under Ice Build temperature control.

 

 

 

J. NORMAL RUN OVERRIDES ACTIVE (ALERTS)

PRIMARY MESSAGE

SECONDARY MESSAGE

 

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

RUN CAPACITY LIMITED

HIGH CONDENSER PRESSURE

CRP [VALUE] exceeded limit of [LIMIT]*.

 

 

 

Condenser pressure override.

 

RUN CAPACITY LIMITED

HIGH MOTOR TEMPERATURE

MTRW [VALUE] exceeded limit of [LIMIT]*.

 

 

 

Motor temperature override.

See Capacity Overrides, Table 4.

RUN CAPACITY LIMITED

LOW EVAP REFRIG TEMP

ERT [VALUE] exceeded limit of [LIMIT]*. Check

Correct operating condition, modify set-

 

 

refrigerant charge level.

 

 

point, or release override.

RUN CAPACITY LIMITED

HIGH COMPRESSOR LIFT

Surge Prevention Override; lift too high for

 

 

 

compressor.

 

RUN CAPACITY LIMITED

MANUAL GUIDE VANE TARGET

GV

 

TRG Run Capacity Limited: Manual guide

 

 

 

vane target.

 

 

 

 

 

 

 

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point prede®ned or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.

K. OUT-OF-RANGE SENSOR FAILURES

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

SENSOR FAULT

LEAVING CHW TEMPERATURE

Sensor Fault: Check leaving CHW

 

 

 

sensor.

 

SENSOR FAULT

ENTERING CHW TEMPERATURE

Sensor Fault: Check entering CHW

 

 

 

sensor.

 

SENSOR FAULT

CONDENSER PRESSURE

Sensor Fault: Check condenser pressure

 

 

 

transducer.

 

SENSOR FAULT

EVAPORATOR PRESSURE

Sensor Fault: Check evaporator pressure

 

 

 

transducer.

See sensor test procedure and check

SENSOR FAULT

BEARING TEMPERATURE

Sensor Fault: Check bearing temperature

sensors for proper operation and

 

 

sensor.

 

 

wiring.

SENSOR FAULT

MOTOR WINDING TEMP

Sensor Fault: Check motor temperature

 

 

 

sensor.

 

SENSOR FAULT

DISCHARGE TEMPERATURE

Sensor Fault: Check discharge temperature

 

 

 

sensor.

 

SENSOR FAULT

OIL SUMP TEMPERATURE

Sensor Fault: Check oil sump temperature

 

 

 

sensor.

 

SENSOR FAULT

OIL PRESSURE TRANSDUCER

Sensor Fault: Check oil pressure

 

 

 

transducer.

 

89

Image 89
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents OCCPC01S Input Service Congurations Piping Check Relief Devices Inspect WiringCoupling Maintenance Motor Maintenance Inspect Water PipingContents 17EX Chiller Familiarization IntroductionAbbreviations Certified PerformanceTypical 17EX Chiller Components Lubrication Cycle OIL Cooling CycleRefrigeration, Cycle Starters17EX Compressor Lubrication Cycle Denitions ControlsMajor PIC Components Panel Locations Temperature Sensors See Fig Pressure TransducersPIC Component Panel Location Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations Psio LIDPIC Tewac Equip GND ÐGRD General LID Operation and Menus FigPROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Service Screen Override Operations YES or no , on or OFF , etc. to select the desired state17EX LID Menu Structure Default ScreenAlarm History Service TableEquipment Configuration Control TestCarrier Comfort Network CCNHgbp Ð Hot Gas Bypass LIDChwr SetpointChws HgbpLID Display Data Description Range Units Reference Point Name Alarm HistoryExample 1 Ð STATUS01 Display Screen Menu Status SelectMenu Status Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen Menu Example 4 Ð STATUS04 Display ScreenExample 5 Ð Setpoint Display Screen ICE Build Termination Example 6 Ð Configuration Config Display ScreenECW Control Option LAG =2, Standby =3 Example 7 Ð LEAD/LAG Configuration Display ScreenExample 8 Ð SERVICE1 Display Screen Spare Alert Enable Example 9 Ð SERVICE2 Display ScreenExample 10 Ð SERVICE3 Display Screen Menu ServiceExample 12 Ð Maintenance MAINT02 Display Screen Example 11 Ð Maintenance MAINT01 Display ScreenDischarge Temperature Bearing TemperatureDescription RANGE/STATUS Units Reference Point Name Example 13 Ð Maintenance MAINT03 Display ScreenExample 14 Ð Maintenance MAINT04 Display Screen PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen Example of Holiday Period Screen To Access the Service ScreensRecycle Sequence Fig START-UP/SHUTDOWNPage Job Data Required Before Initial START-UPEquipment Required MotorPage 17EX Leak Test Procedures Ð HFC-134a Pressure Ð Temperature C Ð HFC-134a Pressure Ð Temperature FTemperature F Temperature CDehydration Cold Trap 900 500 901 7000 1000 7001-14500 2500 Inspect WiringCheck Optional Pumpout Compressor Water Pip Recommended Motor Fastener Tightening Torques External Gear Pre-Start ChecksExternal Gear Lubrication System SOLID-STATE Starters Check StarterMechanical Starters Input the Local Occupied Schedule OCCPC01S Set Up Chiller Control CongurationInput the Design Set Points Ð To modify the set T1/P1 Full Load Points T2/P2 Change the LID Configuration if NecessarySurge Limiting or 50% Load Surge Prevention Occurs TOO Soon Occurs TOO LateIncrease P1 by Decrease P1 by Initial START-UP Charge Refrigerant into ChillerControl Test Menu Functions Tests to be Devices Tested PerformedInitial Motor START-UP Dry Run to Test Start-Up SequenceCheck Motor Rotation Page Flange Nut Tightening Torques Low Speed Couplings Only Check Oil Pressure and Compressor Stop Calibrate Motor Current Demand SettingTo Prevent Accidental Start-Up Ð The PIC can be General RecommendationsOperator Duties Operating InstructionsStarting the Chiller Stopping the ChillerOperating the Optional Pumpout Compressor Pumpout and Refrigerant Transfer ProceduresPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View Valve Condition RLAReturn Chiller to Normal Operating Conditions General MaintenanceChecking Guide Vane Linkage Ð Refer to Fig Contact Seal Maintenance Refer to ÐContact Seal Page Checking Preliminary Alignment Chiller AlignmentMeasuring Angular Misalignment Elevation Alignment Formula HOT Alignment Check Adjusting Angular Misalignment in PlanDoweling Correcting Parallel MisalignmentScheduled Maintenance Weekly MaintenanceCheck Safety and Operating Controls Monthly Changing the Oil FiltersPumpout Compressor OIL17EX Chiller Oil Specications Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Controls for Optional Pumpout Compressor Troubleshooting GuidePage MAINT02 MAINT01MAINT03 MAINT04Oilpd 1CR AUXOilt PICAutorestart in Progress Starts Limit ExceededOperation FaultPotential FREEZE-UP Failure to StopRunning Ð Demand Limited Running Ð Temp ControlChiller Protect Limit Faults LOW OIL Pressure Sensor Fault AlertAlert Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Problem External Gear Troubleshooting GuidePossible Cause Ð Item NO.s Possible Cause ActionTemperature Voltage Resistance Drop Ð Thermistor Temperature F vs Resistance/Voltage DropTemperature Voltage Resistance Drop Ð Thermistor Temperature C vs Resistance/Voltage DropControl Modules Module SwitchModule Address Input Options ModuleGRD Processor/Sensor Input/Output Module Psio FigStarter Management Module SMM Fig Switch Setting Options Module Installation of NEW Psio ModuleFour-In/Two-Out Module Fig Options Module4-In/2-Out Module Physical Data and Wiring SchematicsWeight Vessel SIZE² Additional Cooler WeightsCondenser Total Weight Condenser Charge 100Compressor Weight and Elbow Weight Additional Condenser WeightsDrive Component Weights 101102 Ð Total Motor Weight, English lbÐ Total Motor Weight, SI kg NIH Waterbox Cover Weights Marine Waterbox Cover WeightsApproximate Refrigerant HCFC-134a Charge 103104 Auxiliary Systems, Electrical DataRelief Valve Locations and Data 105 Compressor Fits and ClearancesMeasure 106Clearance Type Description 17FX Tabulation Ð Impeller Clearances Open-Drive Compressors107 108 Temp 109Press Tewac110 111 112 General 113GND Ð Ground 114T1-T4 Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.