Siemens FC330A manual Operating “manned” and “unmanned”, Basic rules

Page 17
Operating “manned” and “unmanned”

Operating “manned” and “unmanned”

i

SPECIAL Alarm Concept used: Yes p

No p

 

Basic rules

The operating states “manned” and “unmanned” are defined in a SPECIAL Alarm Concept, where signals from automatic fire detectors and manual call points are processed differently (for details + page 16).

The switchover from the operating states “manned” to “unmanned” and vice versa is either done manually by the operating personnel or automatically as programmed by the service engineer.

Operating state “manned”

nThe operating person, responsible for the surveillance of the system and the alarm investiga- tion, is present on the premises.

nThe LED in the display field Premises manned Ê is on.

nThe LED in the display field Isolation is on (depends on system configuration).

Operating state “unmanned”

nThe responsible operating person is not present on the premises.

nThe LED in the display field Premises manned Ê is off.

System on

Remote alarm

Alarm delay

Remote alarm

7

8

9

F1

Start/

fault / off

off

 

active

Stop

 

 

 

 

 

 

Fault

Alarm horn

Premises

1

 

4

5

6

F2

 

fault / off

manned

 

 

Isolation

System fault

 

 

 

1

2

3

ok

 

 

 

 

 

 

 

 

Detector

 

 

 

 

del

0

 

 

 

test mode

 

 

 

 

hm

 

 

FC330A

 

 

 

 

 

 

 

 

 

Manual switching between the operating states “manned” and “unmanned”

i

Manual switching between the operating states “manned” and “unmanned” is only possible

during defined working hours (+ page 14, Automatic switchover).

1.Log in with ”access level 2”.

2.Press the Premises manned key on the control panel to toggle between the operating states “manned” (yellow LED is on) and “unmanned” (yellow LED is off).

or

" Toggle between “manned” and “unmanned” via menu which is described next page.

Operating state ”unmanned”

 

Ü Display shows

*

Operating state ”manned”

 

Ü Display shows

*

NORMAL OPERATION

WED 21.7.99 15:00

NORMAL OPERATION mode ’manned’

WED 21.7.99 15:00

13

Fire & Security Products

e1973c-2

Siemens Building Technologies Group

02.2004

Image 17
Contents Phase Fire & Security ProductsSynova FC330A Fire detection system Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Siemens Building Technologies Group Fire & Security Products06.2003 Fire & Security Products Introductione1973c-1 Siemens Building Technologies GroupPage Fire & Security Products Fundamentalse1973c-2 Siemens Building Technologies GroupControl console FC330A Control console layout1 ALARM B3Q590/595 Floor panelB3Q580 Overview operating menu 4.other functions page4.other functions only for service engineerHow to operate the control console Fundamental operationALARM Normal operationWhat is “normal operation”? Mains interruptionHow do I get operating access? Operating accessPossible access levels Log out Operating access via passwordLog in Basic rules Operating “manned” and “unmanned”Extra time Automatic switchoverFire & Security Products Alarme1973c-3 Siemens Building Technologies GroupPurpose and principle SPECIAL Alarm ConceptV2 = Alarm investigation timeV1 = Principle AlarmALARM How to respond in case of alarm How are alarm messages shown on the text display?What to do after an alarm Scrolling alarm messagese1973c-3 Fire & Security ProductsSiemens Building Technologies Group 02.2004Fire & Security Products Disable/Enable System Partse1973c-4 Siemens Building Technologies GroupWhen has a detector zone to be isolated? Temporary isolation of a detector zoneWhat is a detector zone? Zone isolation procedure Zone reactivation procedure Viewing disabled zonesDisable all zones Several zones disabledEnable all disabled zones Enable single zonesEnable a range of zones Single detector isolation procedure Temporary isolation of a single detectorWhen has a single detector to be isolated? Detector reactivation procedure What is “remote transmission”? Remote TransmissionWhen has the remote transmission to be disabled? Disabling the remote alarm transmission facilityEnabling the remote fault transmission facility Disabling the remote fault transmission facilityWhen have alarm devices to be disabled? Alarm devicesDisabling the alarm devices Enabling alarm devicesFire & Security Products Faultse1973c-7 Siemens Building Technologies GroupHow do I respond to fault messages? FaultsReset What remedies are available to the user?Fire & Security Products Maintenancee1973c-8 Siemens Building Technologies GroupRecommendations for function tests Detector testPurpose and Principle 4.After entering the last number press ok twice Test procedure for detector tester RE6 Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6T Required equipementTest procedure for type DIN indirect activation Test procedure for type KACFunctional test of manual call points Control consolePurpose of the lamp test Lamp testLamp test procedure Purpose and principle Battery load testBattery load test procedure Purpose and principle Test of acoustic alarm devicesHorn test procedure Test procedure for remote alarm transmission Test of Remote Transmission RTTest procedure for remote fault transmission Purpose and principlee1973c-12 Fire & Security ProductsSiemens Building Technologies Group 02.2004Fire & Security Products Other Functionse1973c-13 Siemens Building Technologies GroupWhen has the printer to be disabled? Printer disabling/enablingDisabling the printer Enabling the printerSwitch off the printer Paper replacement with logging printer B2Q191Enable the printer Change of printer paperPolling the alarm counter Poll alarm counterPurpose of polling the alarm counter Polling the event memory Poll event memoryPurpose of polling the event memory Polling user text of zones or elements Poll user text of zones or elementsPurpose Polling the system status Poll system statusPurpose Polling configuration data of detector zones Poll configuration dataPolling configuration data of address lines PurposePrint event memory/alarm counter PrintoutPrint configuration/user text Print configuration zone/line/LONSet time and date Set time and datePurpuse and Principle Page CH-8708Männedorf Tel. +41 1 − Siemens Building Technologies AG Alte LandstrasseDocument no. e1973c Edition