Faults

Faults

How do I respond to fault messages?

Fault messages are issued on the text display if a malfunction in the system, the cabling or the attached devices is detected. Additionally the LED in the fault display field is blinking.

1.Confirm the message by pressing the Acknowledge key.

Ü The yellow LED in the fault display field changes from blinking to constant on.

2.Read the fault message on the display and decide, whether the fault can be remedied by the user (see next paragraph: What remedies are available to the user).

3.To cancel the fault message after the fault is remedied, press the Reset key.

WARNING

If the fault cannot remedied by the user, immediately call the SIEMENS service organiza- tion!

What remedies are available to the user?

Only a few faults can be remedied by the user. These are listed below. For all other faults call the

SIEMENS service organization.

Defective or missing detector

 

Ü Display shows

*

or

 

Ü Display shows

*

Broken glass on manual call point

 

Ü Display shows

*

ÜManual call point with broken glass is flashing

"If a detector is missing, insert a detector of the same type into the detector base.

FAULT message(s):

total:###

zone ### elem. ##: dev. DEFECTIVE

TUE 27.7.99

10:35

 

 

 

 

 

FAULT message(s):

total:###

zone ### elem. ##: NO RESPONSE

TUE 27.7.99

10:35

 

 

 

 

 

FAULT message(s):

total:###

zone ### elem ##: Broken glass

TUE 27.7.99

10:35

 

 

 

 

"If a detector is damaged, replace it with a detector of the same type and order a new reserve detector from the SIEMENS service organization.

"If a manual call point has been operated and the glass is broken, replace it, then press the key

Reset.

Mains POWER OFF

 

Ü Display shows

*

FAULT message(s):

total:###

EARTH FAULT to 24V

 

TUE 27.7.99 10:35

 

 

 

Emergency power

n

If the public power supply is down, no action is required. The emergency battery supplies the

supply:

h

 

system for several hours (according to local requirements at least 12 h, max. 72 h), depen-

 

 

 

 

ding on the size of the emergency battery.

 

 

 

n

If the outage is not in the public power supply:

1.Check the power fuse at the main distribution panel of the building.

2.If the fuse is blown, replace the fuse.

Printer out of paper

"Insert a new paper roll (+ page 45, Printer: Paper replenishing).

32

Fire & Security Products

e1973c-7

Siemens Building Technologies Group

02.2004

Image 36
Contents Fire & Security Products PhaseSynova FC330A Fire detection system Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Fire & Security Products 06.2003Siemens Building Technologies Group Introduction Fire & Security Productse1973c-1 Siemens Building Technologies GroupPage Fundamentals Fire & Security Productse1973c-2 Siemens Building Technologies GroupControl console layout 1 ALARMControl console FC330A Floor panel B3Q580B3Q590/595 Overview operating menu page 4.other functionsonly for service engineer 4.other functionsFundamental operation How to operate the control consoleNormal operation ALARMWhat is “normal operation”? Mains interruptionOperating access Possible access levelsHow do I get operating access? Operating access via password Log inLog out Operating “manned” and “unmanned” Basic rulesAutomatic switchover Extra timeAlarm Fire & Security Productse1973c-3 Siemens Building Technologies GroupSPECIAL Alarm Concept Purpose and principleAlarm investigation time V1 =V2 = Alarm ALARMPrinciple How are alarm messages shown on the text display? How to respond in case of alarmWhat to do after an alarm Scrolling alarm messagesFire & Security Products e1973c-3Siemens Building Technologies Group 02.2004Disable/Enable System Parts Fire & Security Productse1973c-4 Siemens Building Technologies GroupTemporary isolation of a detector zone What is a detector zone?When has a detector zone to be isolated? Zone isolation procedure Viewing disabled zones Zone reactivation procedureDisable all zones Several zones disabledEnable single zones Enable a range of zonesEnable all disabled zones Temporary isolation of a single detector When has a single detector to be isolated?Single detector isolation procedure Detector reactivation procedure Remote Transmission What is “remote transmission”?When has the remote transmission to be disabled? Disabling the remote alarm transmission facilityDisabling the remote fault transmission facility Enabling the remote fault transmission facilityAlarm devices When have alarm devices to be disabled?Disabling the alarm devices Enabling alarm devicesFaults Fire & Security Productse1973c-7 Siemens Building Technologies GroupFaults How do I respond to fault messages?Reset What remedies are available to the user?Maintenance Fire & Security Productse1973c-8 Siemens Building Technologies GroupDetector test Purpose and PrincipleRecommendations for function tests 4.After entering the last number press ok twice Functional testing of automatic AlgoRex-detectors Test procedure for detector tester RE6Test procedure for detector tester RE6T Required equipementTest procedure for type KAC Test procedure for type DIN indirect activationFunctional test of manual call points Control consoleLamp test Lamp test procedurePurpose of the lamp test Battery load test Battery load test procedurePurpose and principle Test of acoustic alarm devices Horn test procedurePurpose and principle Test of Remote Transmission RT Test procedure for remote alarm transmissionTest procedure for remote fault transmission Purpose and principleFire & Security Products e1973c-12Siemens Building Technologies Group 02.2004Other Functions Fire & Security Productse1973c-13 Siemens Building Technologies GroupPrinter disabling/enabling When has the printer to be disabled?Disabling the printer Enabling the printerPaper replacement with logging printer B2Q191 Switch off the printerEnable the printer Change of printer paperPoll alarm counter Purpose of polling the alarm counterPolling the alarm counter Poll event memory Purpose of polling the event memoryPolling the event memory Poll user text of zones or elements PurposePolling user text of zones or elements Poll system status PurposePolling the system status Poll configuration data Polling configuration data of detector zonesPolling configuration data of address lines PurposePrintout Print event memory/alarm counterPrint configuration/user text Print configuration zone/line/LONSet time and date Purpuse and PrincipleSet time and date Page Siemens Building Technologies AG Alte Landstrasse CH-8708Männedorf Tel. +41 1 −Document no. e1973c Edition