Remote Transmission
i | Remote transmission provided: | No p | Yes p | Alarm to: |
|
| ||
Fault transmission provided: | No p | Yes p | Alarm to: | |||||
|
|
|
|
|
|
|
|
|
What is “remote transmission”?
The remote transmission facility establishes a transmission path to the fire department in the event of a fire alarm issued by the fire detection system. Depending on the alarm concept, the alarm is transmitted immediately to the fire department, or after a certain delay, giving time for investigation by operating personnel.
In single cases a separate transmission path for fault messages is established.
When has the remote transmission to be disabled?
Under normal conditions the remote alarm transmission facility is enabled to ensure minimal alarming times. The remote transmission facility is disabled only in special cases to prevent un- necessary turn out of the fire brigade. The transmission facility should be disabled for:
nTest of the fire detection system
nMaintenance and conversion works on the fire detection system
WARNING
When the remote alarm transmission is disabled, no automatic alarm is transmitted to the fire department! Operating personnel must be on the premises to investigate immediately the location in case of an alarm and to alarm the fire department in case of fire!
Disabling the remote alarm transmission facility
1. Press St . |
|
Ü Display shows | * |
2.Select option 2. ä 2. ä 3.
Ü Display shows | * |
3.Enter the desired disabling time or 99 for permanent disabling.
Ü Display shows | * |
for a few seconds |
|
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
DISABLE RT−alarm:
> hours DISABLED? (99=permanent)
hm: back to menu | Stop: end operating |
| |
RT−alarm permanent DISABLED | |
timeout /hm: menu | Stop: end operating |
|
|
ÜThe remote fire alarm transmission is disabled.
ÜThe yellow LEDs of the display fields Isolation and Remote alarm/fault off are on.
ÜThe text display indicates that no alarm message is pending.
Enabling the remote alarm transmission facility
1. Press St . |
|
Ü Display shows | * |
2.Select option 1. ä 2. ä 3.
Ü Display shows | * |
for a few seconds |
|
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
RT−alarm ENABLED
timeout /hm: menu | Stop: end operating |
ÜThe remote fire alarm transmission is enabled.
ÜThe yellow LEDs of the display fields Isolation and Remote alarm/fault off are off, if no other parts of the system are isolated.
28