Siemens FC330A manual Purpose and principle, Battery load test procedure

Page 43
Battery load test

Battery load test

Purpose and principle

In case of mains interruption the power supply of the fire detection system relies on an internal battery pack. The capacity of the battery pack is sufficent to keep the system for a couple of hours operating (+ page 32, Faults). As the lifetime of batteries is limited, a battery load test has to be performed periodically to ensure a good condition of the battery pack: For 10 seconds the battery is highly loaded and the battery voltage is monitored. If the voltage drop is beyond a cer- tain value, the battery pack has to be replaced.

Frequency

The batterie test is automatically performed by the system every 24 hours. If the battery is dama- ged, or provides only an insufficent capacity, a fault messages is displayed.

Once a year the battery test has to be performed manually.

Battery load test procedure

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 2. ä 2. ä 2.

ÜTo initiate the battery load test.

Ü Display shows

*

ÜIf the battery test is completed, the sy- stem shows the result.

Ü Display shows

*

for a few seconds

 

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

TESTING battery:

> remaining time for load test

hm: stop test

Stop: end operating

 

 

RESULT battery test:

 

> battery OK.

 

timeout /hm: menu

Stop: end operating

 

 

If the battery load test yields insufficent battery capacity, call the SIEMENS service organization to replace the battery.

39

Fire & Security Products

e1973c-10

Siemens Building Technologies Group

02.2004

Image 43
Contents Operating manual System operation for user Fire & Security ProductsPhase Synova FC330A Fire detection systemECopyright by Siemens Building Technologies AG Overview operating menu 06.2003 Fire & Security ProductsSiemens Building Technologies Group Siemens Building Technologies Group IntroductionFire & Security Products e1973c-1Page Siemens Building Technologies Group FundamentalsFire & Security Products e1973c-21 ALARM Control console layoutControl console FC330A B3Q580 Floor panelB3Q590/595 Overview operating menu 4.other functions page4.other functions only for service engineerHow to operate the control console Fundamental operationMains interruption Normal operationALARM What is “normal operation”?Possible access levels Operating accessHow do I get operating access? Log in Operating access via passwordLog out Basic rules Operating “manned” and “unmanned”Extra time Automatic switchoverSiemens Building Technologies Group AlarmFire & Security Products e1973c-3Purpose and principle SPECIAL Alarm ConceptV1 = Alarm investigation timeV2 = ALARM AlarmPrinciple Scrolling alarm messages How are alarm messages shown on the text display?How to respond in case of alarm What to do after an alarm02.2004 Fire & Security Productse1973c-3 Siemens Building Technologies GroupSiemens Building Technologies Group Disable/Enable System PartsFire & Security Products e1973c-4What is a detector zone? Temporary isolation of a detector zoneWhen has a detector zone to be isolated? Zone isolation procedure Several zones disabled Viewing disabled zonesZone reactivation procedure Disable all zonesEnable a range of zones Enable single zonesEnable all disabled zones When has a single detector to be isolated? Temporary isolation of a single detectorSingle detector isolation procedure Detector reactivation procedure Disabling the remote alarm transmission facility Remote TransmissionWhat is “remote transmission”? When has the remote transmission to be disabled?Enabling the remote fault transmission facility Disabling the remote fault transmission facilityEnabling alarm devices Alarm devicesWhen have alarm devices to be disabled? Disabling the alarm devicesSiemens Building Technologies Group FaultsFire & Security Products e1973c-7What remedies are available to the user? FaultsHow do I respond to fault messages? ResetSiemens Building Technologies Group MaintenanceFire & Security Products e1973c-8Purpose and Principle Detector testRecommendations for function tests 4.After entering the last number press ok twice Required equipement Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6 Test procedure for detector tester RE6TControl console Test procedure for type KACTest procedure for type DIN indirect activation Functional test of manual call pointsLamp test procedure Lamp testPurpose of the lamp test Battery load test procedure Battery load testPurpose and principle Horn test procedure Test of acoustic alarm devicesPurpose and principle Purpose and principle Test of Remote Transmission RTTest procedure for remote alarm transmission Test procedure for remote fault transmission02.2004 Fire & Security Productse1973c-12 Siemens Building Technologies GroupSiemens Building Technologies Group Other FunctionsFire & Security Products e1973c-13Enabling the printer Printer disabling/enablingWhen has the printer to be disabled? Disabling the printerChange of printer paper Paper replacement with logging printer B2Q191Switch off the printer Enable the printerPurpose of polling the alarm counter Poll alarm counterPolling the alarm counter Purpose of polling the event memory Poll event memoryPolling the event memory Purpose Poll user text of zones or elementsPolling user text of zones or elements Purpose Poll system statusPolling the system status Purpose Poll configuration dataPolling configuration data of detector zones Polling configuration data of address linesPrint configuration zone/line/LON PrintoutPrint event memory/alarm counter Print configuration/user textPurpuse and Principle Set time and dateSet time and date Page Edition Siemens Building Technologies AG Alte LandstrasseCH-8708Männedorf Tel. +41 1 − Document no. e1973c