Detector test

Detector test

Purpose and Principle

For function tests of the automatic fire detectors and the manual call points, zones of the fire detection system are set into the “detector test mode”. In the detector test mode a responding detector or manual call point triggers only a test alarm.

This allows individual on−site function tests, where automatic fire detectors deliberately are trig- gered by means of special detector test equipement.

Manual call points are triggered either with a special test key or by opening the cover and actua- ting the button.

Test alarm

A test alarm generates no danger message on the control console. Acoustic alarm devices, the remote alarm transmission or any other control functions are not activated.

A test alarm is indicated on the text display of the control console as test−ALARM ZONE #. It is recorded in the event memory and automatically logged, if a printer is connected.

Frequency

Visual control of detectors and manual call points: Once a year.

Testing of all detectors and manual call points: Once every two years.

i

Differing national or local regulations always have priority!

 

Recommendations for function tests

nPerform the function tests periodically. The frequency of function tests is determined by the service engineer.

nSwitch only the fire detectors of a few zones at a time to detector test mode, never the entire building.

nFor manual call points the function test needs to be performed only according to a sampling plan, designed by the service engineer.

nTest automatic fire detectors and manual call points separately. Never switch them to detec- tor test mode simultaneously.

WARNING

A zone in detector test mode cannot trigger any danger or fault messages!

After completion of the test work immediatly set the fire detection system back to normal operation!

Set only a few zones at a time to detector test mode, never all zones at the same time!

Setting single detector zones into detector test mode

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 2. ä 3. ä 1.

Ü Display shows

*

3.Enter the desired zone numbers (e. g. 1 and 2; max. 4 zones). Use the ok key to separate the numbers and the del key to cancel keying errors.

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

No ’DET. TEST’ mode, set single zone(s): > zone no.? (max. 4)

hm: back to menu

Stop: end operating

34

Fire & Security Products

e1973c-8

Siemens Building Technologies Group

02.2004

Image 38
Contents Synova FC330A Fire detection system Fire & Security ProductsPhase Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Siemens Building Technologies Group Fire & Security Products06.2003 e1973c-1 IntroductionFire & Security Products Siemens Building Technologies GroupPage e1973c-2 FundamentalsFire & Security Products Siemens Building Technologies GroupControl console FC330A Control console layout1 ALARM B3Q590/595 Floor panelB3Q580 Overview operating menu page 4.other functionsonly for service engineer 4.other functionsFundamental operation How to operate the control consoleWhat is “normal operation”? Normal operationALARM Mains interruptionHow do I get operating access? Operating accessPossible access levels Log out Operating access via passwordLog in Operating “manned” and “unmanned” Basic rulesAutomatic switchover Extra timee1973c-3 AlarmFire & Security Products Siemens Building Technologies GroupSPECIAL Alarm Concept Purpose and principleV2 = Alarm investigation timeV1 = Principle AlarmALARM What to do after an alarm How are alarm messages shown on the text display?How to respond in case of alarm Scrolling alarm messagesSiemens Building Technologies Group Fire & Security Productse1973c-3 02.2004e1973c-4 Disable/Enable System PartsFire & Security Products Siemens Building Technologies GroupWhen has a detector zone to be isolated? Temporary isolation of a detector zoneWhat is a detector zone? Zone isolation procedure Disable all zones Viewing disabled zonesZone reactivation procedure Several zones disabledEnable all disabled zones Enable single zonesEnable a range of zones Single detector isolation procedure Temporary isolation of a single detectorWhen has a single detector to be isolated? Detector reactivation procedure When has the remote transmission to be disabled? Remote TransmissionWhat is “remote transmission”? Disabling the remote alarm transmission facilityDisabling the remote fault transmission facility Enabling the remote fault transmission facilityDisabling the alarm devices Alarm devicesWhen have alarm devices to be disabled? Enabling alarm devicese1973c-7 FaultsFire & Security Products Siemens Building Technologies GroupReset FaultsHow do I respond to fault messages? What remedies are available to the user?e1973c-8 MaintenanceFire & Security Products Siemens Building Technologies GroupRecommendations for function tests Detector testPurpose and Principle 4.After entering the last number press ok twice Test procedure for detector tester RE6T Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6 Required equipementFunctional test of manual call points Test procedure for type KACTest procedure for type DIN indirect activation Control consolePurpose of the lamp test Lamp testLamp test procedure Purpose and principle Battery load testBattery load test procedure Purpose and principle Test of acoustic alarm devicesHorn test procedure Test procedure for remote fault transmission Test of Remote Transmission RTTest procedure for remote alarm transmission Purpose and principleSiemens Building Technologies Group Fire & Security Productse1973c-12 02.2004e1973c-13 Other FunctionsFire & Security Products Siemens Building Technologies GroupDisabling the printer Printer disabling/enablingWhen has the printer to be disabled? Enabling the printerEnable the printer Paper replacement with logging printer B2Q191Switch off the printer Change of printer paperPolling the alarm counter Poll alarm counterPurpose of polling the alarm counter Polling the event memory Poll event memoryPurpose of polling the event memory Polling user text of zones or elements Poll user text of zones or elementsPurpose Polling the system status Poll system statusPurpose Polling configuration data of address lines Poll configuration dataPolling configuration data of detector zones PurposePrint configuration/user text PrintoutPrint event memory/alarm counter Print configuration zone/line/LONSet time and date Set time and datePurpuse and Principle Page Document no. e1973c Siemens Building Technologies AG Alte LandstrasseCH-8708Männedorf Tel. +41 1 − Edition