Siemens FC330A manual Automatic switchover, Extra time

Page 18
Automatic switchover

Toggle via menu

 

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 1. ä 1.

Ü Display shows

*

3.If the operating state has to be changed to

“manned”: select option 1.

“unmanned”: select option 2.

ÜIf mode ”manned” is selected

Ü Display shows

*

for a few seconds

 

Automatic switchover

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

mode ’manned’ until ##:##, 1.> unmanned

sel. #,

2.> manned

3.extra time

hm: back to menu

Stop: end operating

mode ’manned’ TERMINATED

> system is set to NORMAL OPERATION

timeout /hm: menu

Stop: end operating

The automatic switchover is used for example, to prevent the system status “manned” during nighttime when no operating personnel is present: The system switches automatically to status “unmanned” at a defined time (e. g. after the office hours). The same scheme can be used for unattended times during weekends or holidays. The automatic switchover scheme is defined by the service engineer. No user action is required.

n

Automatic switchover from “manned” to “unmanned”: at

 

p.m.

n

Automatic switchover from “unmanned” to “manned”: at

 

a.m.

Extra time

Function extra time The function “extra time” allows to set the system to manned operation for a preset time, after the activated p automatic switchover to unmanned has taken place.

not activated p

1.

Press St .

 

SELECT:

1.

ENabling

 

(main menu)

2.

DISabling

 

Ü Display shows

 

 

*

 

3.

INFO polling

 

 

 

 

4.

other functions

 

 

 

 

 

 

2.

Select option 4. ä 1. ä 1.

 

mode ’unmanned’

2.

> ’manned’

 

(hm = INTERRUPT)

3.

extra time

 

Ü Display shows

*

hm: back to menu

Stop: end operating

 

 

 

ÜThe actual display depends on the initial mode, here e. g. mode unmanned (i. e. after 17:00).

 

3.

Select option 3.

 

 

 

 

Ü Display shows

*

Extra time max.

 

4.

Enter the extra time.

 

EXTRA TIME h/min? (max. ##:##)

hm: back to menu

Stop: end operating

ÜThe time until the system is set to manned mode is displayed.

14

Fire & Security Products

e1973c-2

Siemens Building Technologies Group

02.2004

Image 18
Contents Synova FC330A Fire detection system Fire & Security ProductsPhase Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Fire & Security Products 06.2003Siemens Building Technologies Group e1973c-1 IntroductionFire & Security Products Siemens Building Technologies GroupPage e1973c-2 FundamentalsFire & Security Products Siemens Building Technologies GroupControl console layout 1 ALARMControl console FC330A Floor panel B3Q580B3Q590/595 Overview operating menu page 4.other functionsonly for service engineer 4.other functionsFundamental operation How to operate the control consoleWhat is “normal operation”? Normal operationALARM Mains interruptionOperating access Possible access levelsHow do I get operating access? Operating access via password Log inLog out Operating “manned” and “unmanned” Basic rulesAutomatic switchover Extra timee1973c-3 AlarmFire & Security Products Siemens Building Technologies GroupSPECIAL Alarm Concept Purpose and principleAlarm investigation time V1 =V2 = Alarm ALARMPrinciple What to do after an alarm How are alarm messages shown on the text display?How to respond in case of alarm Scrolling alarm messagesSiemens Building Technologies Group Fire & Security Productse1973c-3 02.2004e1973c-4 Disable/Enable System PartsFire & Security Products Siemens Building Technologies GroupTemporary isolation of a detector zone What is a detector zone?When has a detector zone to be isolated? Zone isolation procedure Disable all zones Viewing disabled zonesZone reactivation procedure Several zones disabledEnable single zones Enable a range of zonesEnable all disabled zones Temporary isolation of a single detector When has a single detector to be isolated?Single detector isolation procedure Detector reactivation procedure When has the remote transmission to be disabled? Remote TransmissionWhat is “remote transmission”? Disabling the remote alarm transmission facilityDisabling the remote fault transmission facility Enabling the remote fault transmission facilityDisabling the alarm devices Alarm devicesWhen have alarm devices to be disabled? Enabling alarm devicese1973c-7 FaultsFire & Security Products Siemens Building Technologies GroupReset FaultsHow do I respond to fault messages? What remedies are available to the user?e1973c-8 MaintenanceFire & Security Products Siemens Building Technologies GroupDetector test Purpose and PrincipleRecommendations for function tests 4.After entering the last number press ok twice Test procedure for detector tester RE6T Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6 Required equipementFunctional test of manual call points Test procedure for type KACTest procedure for type DIN indirect activation Control consoleLamp test Lamp test procedurePurpose of the lamp test Battery load test Battery load test procedurePurpose and principle Test of acoustic alarm devices Horn test procedurePurpose and principle Test procedure for remote fault transmission Test of Remote Transmission RTTest procedure for remote alarm transmission Purpose and principleSiemens Building Technologies Group Fire & Security Productse1973c-12 02.2004e1973c-13 Other FunctionsFire & Security Products Siemens Building Technologies GroupDisabling the printer Printer disabling/enablingWhen has the printer to be disabled? Enabling the printerEnable the printer Paper replacement with logging printer B2Q191Switch off the printer Change of printer paperPoll alarm counter Purpose of polling the alarm counterPolling the alarm counter Poll event memory Purpose of polling the event memoryPolling the event memory Poll user text of zones or elements PurposePolling user text of zones or elements Poll system status PurposePolling the system status Polling configuration data of address lines Poll configuration dataPolling configuration data of detector zones PurposePrint configuration/user text PrintoutPrint event memory/alarm counter Print configuration zone/line/LONSet time and date Purpuse and PrincipleSet time and date Page Document no. e1973c Siemens Building Technologies AG Alte LandstrasseCH-8708Männedorf Tel. +41 1 − Edition