Siemens FC330A Alarm devices, When have alarm devices to be disabled?, Enabling alarm devices

Page 34
Alarm devices

Alarm devices

When have alarm devices to be disabled?

Under normal conditions the alarm devices (e. g. horns or sirens) operate in active stand−by.

They are only disabled for:

nTest of the fire detection system.

nMaintenance and conversion works on the fire detection system.

WARNING

When the alarm devices are disabled, no acoustic alarm (except the buzzer) is issued in case of fire!

Normally all acoustic devices are disabled together. Single devices or lines are only disa- i bled in exceptional cases. For the alarm devices there are always 2 lines, in some cases 4

lines, but max. 6 lines possible.

Disabling the alarm devices

1. Press St .

 

Ü Display shows

*

2.Select option 2. ä 2. ä 1.

Ü Display shows

*

3.Enter the desired horn number or 555 for disabling all horns.

Ü Display shows

*

for a few seconds

 

4.Enter the number of a further device to disable.

or

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

DISABLE horn:

> enter horn no.? (all=555)

hm: back to menu

Stop: end operating

 

 

DISABLE horn:

 

> all horns DISABLED

 

timeout /hm: menu

Stop: end operating

 

 

"Press St to finish the procedure.

ÜThe desired alarm devices are disabled.

ÜThe yellow LEDs of the display fields Isolation and Alarm horn fault/off are on.

ÜThe text display indicates that no alarm message is pending.

Enabling alarm devices

1. Press St .

 

Ü Display shows

*

2.Select option 1. ä 2. ä 1.

Ü Display shows

*

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

ENABLE horn outputs:

> enter horn no.? (all=555)

hm: back to menu

Stop: end operating

3.Enter the desired horn number or 555 to enable all horns.

Ü Display shows

*

for a few seconds

 

4.Enter the number of a further device to disable.

ENABLE horn outputs:

> all horn outputs ENABLED

timeout /hm: menu

Stop: end operating

or

"Press St to finish the procedure.

ÜThe desired alarm devices are enabled.

ÜThe yellow LEDs of the display fields Isolation and Alarm horn fault/off are off, if no other parts of the system are isolated.

30

Fire & Security Products

e1973c-6

Siemens Building Technologies Group

02.2004

Image 34
Contents Synova FC330A Fire detection system Fire & Security ProductsPhase Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu 06.2003 Fire & Security ProductsSiemens Building Technologies Group e1973c-1 IntroductionFire & Security Products Siemens Building Technologies GroupPage e1973c-2 FundamentalsFire & Security Products Siemens Building Technologies Group1 ALARM Control console layoutControl console FC330A B3Q580 Floor panelB3Q590/595 Overview operating menu page 4.other functionsonly for service engineer 4.other functionsFundamental operation How to operate the control consoleWhat is “normal operation”? Normal operationALARM Mains interruptionPossible access levels Operating accessHow do I get operating access? Log in Operating access via passwordLog out Operating “manned” and “unmanned” Basic rulesAutomatic switchover Extra timee1973c-3 AlarmFire & Security Products Siemens Building Technologies GroupSPECIAL Alarm Concept Purpose and principleV1 = Alarm investigation timeV2 = ALARM AlarmPrinciple What to do after an alarm How are alarm messages shown on the text display?How to respond in case of alarm Scrolling alarm messagesSiemens Building Technologies Group Fire & Security Productse1973c-3 02.2004e1973c-4 Disable/Enable System PartsFire & Security Products Siemens Building Technologies GroupWhat is a detector zone? Temporary isolation of a detector zoneWhen has a detector zone to be isolated? Zone isolation procedure Disable all zones Viewing disabled zonesZone reactivation procedure Several zones disabledEnable a range of zones Enable single zonesEnable all disabled zones When has a single detector to be isolated? Temporary isolation of a single detectorSingle detector isolation procedure Detector reactivation procedure When has the remote transmission to be disabled? Remote TransmissionWhat is “remote transmission”? Disabling the remote alarm transmission facilityDisabling the remote fault transmission facility Enabling the remote fault transmission facilityDisabling the alarm devices Alarm devicesWhen have alarm devices to be disabled? Enabling alarm devicese1973c-7 FaultsFire & Security Products Siemens Building Technologies GroupReset FaultsHow do I respond to fault messages? What remedies are available to the user?e1973c-8 MaintenanceFire & Security Products Siemens Building Technologies GroupPurpose and Principle Detector testRecommendations for function tests 4.After entering the last number press ok twice Test procedure for detector tester RE6T Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6 Required equipementFunctional test of manual call points Test procedure for type KACTest procedure for type DIN indirect activation Control consoleLamp test procedure Lamp testPurpose of the lamp test Battery load test procedure Battery load testPurpose and principle Horn test procedure Test of acoustic alarm devicesPurpose and principle Test procedure for remote fault transmission Test of Remote Transmission RTTest procedure for remote alarm transmission Purpose and principleSiemens Building Technologies Group Fire & Security Productse1973c-12 02.2004e1973c-13 Other FunctionsFire & Security Products Siemens Building Technologies GroupDisabling the printer Printer disabling/enablingWhen has the printer to be disabled? Enabling the printerEnable the printer Paper replacement with logging printer B2Q191Switch off the printer Change of printer paperPurpose of polling the alarm counter Poll alarm counterPolling the alarm counter Purpose of polling the event memory Poll event memoryPolling the event memory Purpose Poll user text of zones or elementsPolling user text of zones or elements Purpose Poll system statusPolling the system status Polling configuration data of address lines Poll configuration dataPolling configuration data of detector zones PurposePrint configuration/user text PrintoutPrint event memory/alarm counter Print configuration zone/line/LONPurpuse and Principle Set time and dateSet time and date Page Document no. e1973c Siemens Building Technologies AG Alte LandstrasseCH-8708Männedorf Tel. +41 1 − Edition