Functional test of manual call points
Response indicator
Test− key
Response indicator
Button
Test procedure for type KAC
1.Set the desired zone into detector test mode (+ page 34).
2.Insert the test key into the opening at the lower left side of the housing.
ÜA test alarm is simulated.
3.Observe, whether the response indicator near the upper right corner of the housing flashes.
4.Remove the test key.
ÜThe functional testing is completed.
"If the tested manual call point did not respond, call the SIEMENS service organization.
Test procedure for type DIN (indirect activation)
1.Set the desired zone into detector test mode (+ page 34).
2.Open the housing of the manual call point with the key.
3.Press down the button completely.
ÜA test alarm is simulated.
4.Observe, whether the response indicator, a red LED to the right of the button, flashes.
5.Close the housing.
ÜThe functional testing is completed.
"If the tested manual call point did not respond, call the SIEMENS service organization.
Control console |
|
Ü Display shows | * |
mode ’detector TEST’ ACTIVE
>test−ALARM zone ###/##
WED 21.7.99 15:00
"Each test alarm is indicated in the display for a few seconds and also registered in the event memory.