Siemens FC330A Functional test of manual call points, Test procedure for type KAC

Page 41
Functional test of manual call points

Functional test of manual call points

Response indicator

Test−Test procedure for type KAC key

Response Test procedure for type DIN (indirect activation)indicator

Control console Button

Test procedure for type KAC

1.Set the desired zone into detector test mode (+ page 34).

2.Insert the test key into the opening at the lower left side of the housing.

ÜA test alarm is simulated.

3.Observe, whether the response indicator near the upper right corner of the housing flashes.

4.Remove the test key.

ÜThe functional testing is completed.

"If the tested manual call point did not respond, call the SIEMENS service organization.

Test procedure for type DIN (indirect activation)

1.Set the desired zone into detector test mode (+ page 34).

2.Open the housing of the manual call point with the key.

3.Press down the button completely.

ÜA test alarm is simulated.

4.Observe, whether the response indicator, a red LED to the right of the button, flashes.

5.Close the housing.

ÜThe functional testing is completed.

"If the tested manual call point did not respond, call the SIEMENS service organization.

Control console

 

Ü Display shows

*

mode ’detector TEST’ ACTIVE

>test−ALARM zone ###/##

WED 21.7.99 15:00

"Each test alarm is indicated in the display for a few seconds and also registered in the event memory.

37

Fire & Security Products

e1973c-8

Siemens Building Technologies Group

02.2004

Image 41
Contents Phase Fire & Security ProductsSynova FC330A Fire detection system Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Siemens Building Technologies Group Fire & Security Products06.2003 Fire & Security Products Introductione1973c-1 Siemens Building Technologies GroupPage Fire & Security Products Fundamentalse1973c-2 Siemens Building Technologies GroupControl console FC330A Control console layout1 ALARM B3Q590/595 Floor panelB3Q580 Overview operating menu 4.other functions page4.other functions only for service engineerHow to operate the control console Fundamental operationALARM Normal operationWhat is “normal operation”? Mains interruptionHow do I get operating access? Operating accessPossible access levels Log out Operating access via passwordLog in Basic rules Operating “manned” and “unmanned”Extra time Automatic switchoverFire & Security Products Alarme1973c-3 Siemens Building Technologies GroupPurpose and principle SPECIAL Alarm ConceptV2 = Alarm investigation timeV1 = Principle AlarmALARM How to respond in case of alarm How are alarm messages shown on the text display?What to do after an alarm Scrolling alarm messagese1973c-3 Fire & Security ProductsSiemens Building Technologies Group 02.2004Fire & Security Products Disable/Enable System Partse1973c-4 Siemens Building Technologies GroupWhen has a detector zone to be isolated? Temporary isolation of a detector zoneWhat is a detector zone? Zone isolation procedure Zone reactivation procedure Viewing disabled zonesDisable all zones Several zones disabledEnable all disabled zones Enable single zonesEnable a range of zones Single detector isolation procedure Temporary isolation of a single detectorWhen has a single detector to be isolated? Detector reactivation procedure What is “remote transmission”? Remote TransmissionWhen has the remote transmission to be disabled? Disabling the remote alarm transmission facilityEnabling the remote fault transmission facility Disabling the remote fault transmission facilityWhen have alarm devices to be disabled? Alarm devicesDisabling the alarm devices Enabling alarm devicesFire & Security Products Faultse1973c-7 Siemens Building Technologies GroupHow do I respond to fault messages? FaultsReset What remedies are available to the user?Fire & Security Products Maintenancee1973c-8 Siemens Building Technologies GroupRecommendations for function tests Detector testPurpose and Principle 4.After entering the last number press ok twice Test procedure for detector tester RE6 Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6T Required equipementTest procedure for type DIN indirect activation Test procedure for type KACFunctional test of manual call points Control consolePurpose of the lamp test Lamp testLamp test procedure Purpose and principle Battery load testBattery load test procedure Purpose and principle Test of acoustic alarm devicesHorn test procedure Test procedure for remote alarm transmission Test of Remote Transmission RTTest procedure for remote fault transmission Purpose and principlee1973c-12 Fire & Security ProductsSiemens Building Technologies Group 02.2004Fire & Security Products Other Functionse1973c-13 Siemens Building Technologies GroupWhen has the printer to be disabled? Printer disabling/enablingDisabling the printer Enabling the printerSwitch off the printer Paper replacement with logging printer B2Q191Enable the printer Change of printer paperPolling the alarm counter Poll alarm counterPurpose of polling the alarm counter Polling the event memory Poll event memoryPurpose of polling the event memory Polling user text of zones or elements Poll user text of zones or elementsPurpose Polling the system status Poll system statusPurpose Polling configuration data of detector zones Poll configuration dataPolling configuration data of address lines PurposePrint event memory/alarm counter PrintoutPrint configuration/user text Print configuration zone/line/LONSet time and date Set time and datePurpuse and Principle Page CH-8708Männedorf Tel. +41 1 − Siemens Building Technologies AG Alte LandstrasseDocument no. e1973c Edition