Siemens FC330A manual After entering the last number press ok twice

Page 39
4.After entering the last number press ok twice.

4.After entering the last number press ok twice.

Ü Display shows

*

for a few seconds

 

ÜThe selected detector zones are set into detector test mode.

Ü Display shows

*

ÜThe yellow LED of the display field de- tector test mode are on.

Mode ’DET. TEST’ zones: ###,###,###,###

Outputs NOT activated

timeout /hm: menu

Stop: end operating

Mode ’DET. TEST’ zones: ###,###,###,###

Mode ’DET. TEST’ range: ### − ###

TUE 27.7.99 10:35

Setting a zone range or all detectors into detector test mode

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 2. ä 3. ä 2.

Ü Display shows

*

3.Enter the first number of the desired zone range (e. g. 2) or 555 for testing all zones.

Ü Display shows

*

for a few seconds

 

4.Enter the last number of the desired zone range (e. g. 5).

Ü Display shows

*

ÜThe selected zone range is set into de- tector test mode.

Ü Display shows

*

Terminating the detector test mode for single zones

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 2. ä 3. ä 1.

Ü Display shows

*

3.Press del to delete all displayed zone numbers and enter “0” (zero) instead.

4.Press ok twice.

Ü Display shows

*

for a few seconds

 

ÜThe detector test mode is terminated for all detector zones.

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

No ’DET.TEST’ mode, set range ### − ###:

> zone no.? (555=all, 0=end)

zone range ### − ### in ’DET. TEST’ mode Outputs NOT activated

timeout /hm: menu

Stop: end operating

zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###)

Mode ’DET. TEST’ zones: ###,###,###,###

Mode ’DET. TEST’ range: ### − ###

TUE 27.7.99 10:35

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

No ’DET. TEST’ mode, set single zone(s): > zone no.? (max. 4)

hm: back to menu

Stop: end operating

 

’DET. TEST’ mode TERMINATED

timeout /hm: menu

Stop: end operating

 

 

Terminating the detector test mode for a zone range

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 2. ä 3. ä 2.

Ü Display shows

*

3.Enter “0” (zero) and press ok .

Ü Display shows

*

for a few seconds

 

ÜThe detector test mode is terminated for all detector zones.

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

No ’DET.TEST’ mode, set range ### − ###:

> zone no.? (555=all, 0=end)

hm: back to menu

Stop: end operating

 

’DET. TEST’ mode TERMINATED

timeout /hm: menu

Stop: end operating

 

 

35

Fire & Security Products

e1973c-8

Siemens Building Technologies Group

02.2004

Image 39
Contents Operating manual System operation for user Fire & Security ProductsPhase Synova FC330A Fire detection systemECopyright by Siemens Building Technologies AG Overview operating menu Fire & Security Products 06.2003Siemens Building Technologies Group Siemens Building Technologies Group IntroductionFire & Security Products e1973c-1Page Siemens Building Technologies Group FundamentalsFire & Security Products e1973c-2Control console layout 1 ALARMControl console FC330A Floor panel B3Q580B3Q590/595 Overview operating menu 4.other functions page4.other functions only for service engineerHow to operate the control console Fundamental operationMains interruption Normal operationALARM What is “normal operation”?Operating access Possible access levelsHow do I get operating access? Operating access via password Log inLog out Basic rules Operating “manned” and “unmanned”Extra time Automatic switchoverSiemens Building Technologies Group AlarmFire & Security Products e1973c-3Purpose and principle SPECIAL Alarm ConceptAlarm investigation time V1 =V2 = Alarm ALARMPrinciple Scrolling alarm messages How are alarm messages shown on the text display?How to respond in case of alarm What to do after an alarm02.2004 Fire & Security Productse1973c-3 Siemens Building Technologies GroupSiemens Building Technologies Group Disable/Enable System PartsFire & Security Products e1973c-4Temporary isolation of a detector zone What is a detector zone?When has a detector zone to be isolated? Zone isolation procedure Several zones disabled Viewing disabled zonesZone reactivation procedure Disable all zonesEnable single zones Enable a range of zonesEnable all disabled zones Temporary isolation of a single detector When has a single detector to be isolated?Single detector isolation procedure Detector reactivation procedure Disabling the remote alarm transmission facility Remote TransmissionWhat is “remote transmission”? When has the remote transmission to be disabled?Enabling the remote fault transmission facility Disabling the remote fault transmission facilityEnabling alarm devices Alarm devicesWhen have alarm devices to be disabled? Disabling the alarm devicesSiemens Building Technologies Group FaultsFire & Security Products e1973c-7What remedies are available to the user? FaultsHow do I respond to fault messages? ResetSiemens Building Technologies Group MaintenanceFire & Security Products e1973c-8Detector test Purpose and PrincipleRecommendations for function tests 4.After entering the last number press ok twice Required equipement Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6 Test procedure for detector tester RE6TControl console Test procedure for type KACTest procedure for type DIN indirect activation Functional test of manual call pointsLamp test Lamp test procedurePurpose of the lamp test Battery load test Battery load test procedurePurpose and principle Test of acoustic alarm devices Horn test procedurePurpose and principle Purpose and principle Test of Remote Transmission RTTest procedure for remote alarm transmission Test procedure for remote fault transmission02.2004 Fire & Security Productse1973c-12 Siemens Building Technologies GroupSiemens Building Technologies Group Other FunctionsFire & Security Products e1973c-13Enabling the printer Printer disabling/enablingWhen has the printer to be disabled? Disabling the printerChange of printer paper Paper replacement with logging printer B2Q191Switch off the printer Enable the printerPoll alarm counter Purpose of polling the alarm counterPolling the alarm counter Poll event memory Purpose of polling the event memoryPolling the event memory Poll user text of zones or elements PurposePolling user text of zones or elements Poll system status PurposePolling the system status Purpose Poll configuration dataPolling configuration data of detector zones Polling configuration data of address linesPrint configuration zone/line/LON PrintoutPrint event memory/alarm counter Print configuration/user textSet time and date Purpuse and PrincipleSet time and date Page Edition Siemens Building Technologies AG Alte LandstrasseCH-8708Männedorf Tel. +41 1 − Document no. e1973c