Lamp test

Lamp test

Purpose of the lamp test

Alarms, faults and operating state of the fire detection system are indicated by LEDs in the dis- play fields, the text display and the alarm buzzer of the control console.

To check the correct function of these parts the lamp test can be initiated: All visual and audible devices of the control console are activated for a few seconds.

Frequency

The lamps have to be tested at least once a year.

Lamp test procedure

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 2. ä 2. ä 1.

ÜTo initiate the lamp test.

Ü Display shows

*

3.Check:

all LEDs on?

buzzer audible?

missing segments in text display?

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

TESTING lamps and display:

(→← ↓↑)

> remaining time

.........................................

.........................................

i

38

If one or more devices are malfunctional, call the SIEMENS service organization.

Lamp test on local indication and control panels + page 5.

Fire & Security Products

e1973c-9

Siemens Building Technologies Group

02.2004

Image 42
Contents Synova FC330A Fire detection system Fire & Security ProductsPhase Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Fire & Security Products 06.2003Siemens Building Technologies Group e1973c-1 IntroductionFire & Security Products Siemens Building Technologies GroupPage e1973c-2 FundamentalsFire & Security Products Siemens Building Technologies GroupControl console layout 1 ALARMControl console FC330A Floor panel B3Q580B3Q590/595 Overview operating menu page 4.other functionsonly for service engineer 4.other functionsFundamental operation How to operate the control consoleWhat is “normal operation”? Normal operationALARM Mains interruptionOperating access Possible access levelsHow do I get operating access? Operating access via password Log inLog out Operating “manned” and “unmanned” Basic rulesAutomatic switchover Extra timee1973c-3 AlarmFire & Security Products Siemens Building Technologies GroupSPECIAL Alarm Concept Purpose and principleAlarm investigation time V1 =V2 = Alarm ALARMPrinciple What to do after an alarm How are alarm messages shown on the text display?How to respond in case of alarm Scrolling alarm messagesSiemens Building Technologies Group Fire & Security Productse1973c-3 02.2004e1973c-4 Disable/Enable System PartsFire & Security Products Siemens Building Technologies GroupTemporary isolation of a detector zone What is a detector zone?When has a detector zone to be isolated? Zone isolation procedure Disable all zones Viewing disabled zonesZone reactivation procedure Several zones disabledEnable single zones Enable a range of zonesEnable all disabled zones Temporary isolation of a single detector When has a single detector to be isolated?Single detector isolation procedure Detector reactivation procedure When has the remote transmission to be disabled? Remote TransmissionWhat is “remote transmission”? Disabling the remote alarm transmission facilityDisabling the remote fault transmission facility Enabling the remote fault transmission facilityDisabling the alarm devices Alarm devicesWhen have alarm devices to be disabled? Enabling alarm devicese1973c-7 FaultsFire & Security Products Siemens Building Technologies GroupReset FaultsHow do I respond to fault messages? What remedies are available to the user?e1973c-8 MaintenanceFire & Security Products Siemens Building Technologies GroupDetector test Purpose and PrincipleRecommendations for function tests 4.After entering the last number press ok twice Test procedure for detector tester RE6T Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6 Required equipementFunctional test of manual call points Test procedure for type KACTest procedure for type DIN indirect activation Control consoleLamp test Lamp test procedurePurpose of the lamp test Battery load test Battery load test procedurePurpose and principle Test of acoustic alarm devices Horn test procedurePurpose and principle Test procedure for remote fault transmission Test of Remote Transmission RTTest procedure for remote alarm transmission Purpose and principleSiemens Building Technologies Group Fire & Security Productse1973c-12 02.2004e1973c-13 Other FunctionsFire & Security Products Siemens Building Technologies GroupDisabling the printer Printer disabling/enablingWhen has the printer to be disabled? Enabling the printerEnable the printer Paper replacement with logging printer B2Q191Switch off the printer Change of printer paperPoll alarm counter Purpose of polling the alarm counterPolling the alarm counter Poll event memory Purpose of polling the event memoryPolling the event memory Poll user text of zones or elements PurposePolling user text of zones or elements Poll system status PurposePolling the system status Polling configuration data of address lines Poll configuration dataPolling configuration data of detector zones PurposePrint configuration/user text PrintoutPrint event memory/alarm counter Print configuration zone/line/LONSet time and date Purpuse and PrincipleSet time and date Page Document no. e1973c Siemens Building Technologies AG Alte LandstrasseCH-8708Männedorf Tel. +41 1 − Edition