Lamp test
Purpose of the lamp test
Alarms, faults and operating state of the fire detection system are indicated by LEDs in the dis- play fields, the text display and the alarm buzzer of the control console.
To check the correct function of these parts the lamp test can be initiated: All visual and audible devices of the control console are activated for a few seconds.
Frequency
The lamps have to be tested at least once a year.
Lamp test procedure
1. Press St . |
|
Ü Display shows | * |
2.Select option 4. ä 2. ä 2. ä 1.
ÜTo initiate the lamp test.
Ü Display shows | * |
3.Check:
−all LEDs on?
−buzzer audible?
−missing segments in text display?
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
TESTING lamps and display: | (→← ↓↑) |
> remaining time |
.........................................
.........................................
i
38
If one or more devices are malfunctional, call the SIEMENS service organization.
Lamp test on local indication and control panels + page 5.