Siemens FC330A manual Set time and date, Purpuse and Principle

Page 56
Set time and date

Set time and date

i

Changeover summertime to wintertime: manually p

automatically p

 

Purpuse and Principle

Time and date are set by the service engineer when the system is put into service. Under normal conditions there is no need to correct time and date.

The changeover from summertime to wintertime and vice versa is performed automatically for Central European Time. Central European Time is valid for Western Europe, most of Eastern Europe an parts of Russia. The switchover from summertime to wintertime is performed at the last sunday in March, vise versa at the last sunday in October. Differing automatic switching ti- mes are not possible.

Only due to an electronical distortion or a complete power failure (mains and battery interrupted) the system sets time and date to “default”.

Set time and date

Log in with at least ”access level 2”.

 

1. Press St .

 

Ü Display shows

*

START system operating > enter password?

hm /Stop: end operating

2.Enter the password and press Ü Display shows

ok .

*

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

3.

Select option 4. ä 1. ä 2.

 

 

 

 

set TIME:

##:##:##

 

Ü Display shows

*

> new time: hour.min.sec.?

 

 

 

hm: back to menu

Stop: end operating

4.

Enter the current time and press ok .

 

 

 

 

 

 

 

set DATE:

##.##.##

 

Ü Display shows

*

> new date: day.mon.year?

5.

Enter the current date and press ok .

 

hm: back to menu

Stop: end operating

 

 

 

 

 

 

 

Ü Time and date are set to the current va-

 

 

 

lues.

*

FUNCTIONS:

1. switching alarm org.

 

Ü Display shows

(4.1)

2. set time / date

 

 

 

 

 

 

 

 

6. Use St to terminate the time and date setting.

52

Fire & Security Products

e1973c-16

Siemens Building Technologies Group

02.2004

Image 56
Contents Fire & Security Products PhaseSynova FC330A Fire detection system Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Siemens Building Technologies Group Fire & Security Products06.2003 Introduction Fire & Security Productse1973c-1 Siemens Building Technologies GroupPage Fundamentals Fire & Security Productse1973c-2 Siemens Building Technologies GroupControl console FC330A Control console layout1 ALARM B3Q590/595 Floor panelB3Q580 Overview operating menu page 4.other functionsonly for service engineer 4.other functionsFundamental operation How to operate the control consoleNormal operation ALARMWhat is “normal operation”? Mains interruptionHow do I get operating access? Operating accessPossible access levels Log out Operating access via passwordLog in Operating “manned” and “unmanned” Basic rulesAutomatic switchover Extra timeAlarm Fire & Security Productse1973c-3 Siemens Building Technologies GroupSPECIAL Alarm Concept Purpose and principleV2 = Alarm investigation timeV1 = Principle AlarmALARM How are alarm messages shown on the text display? How to respond in case of alarmWhat to do after an alarm Scrolling alarm messagesFire & Security Products e1973c-3Siemens Building Technologies Group 02.2004Disable/Enable System Parts Fire & Security Productse1973c-4 Siemens Building Technologies GroupWhen has a detector zone to be isolated? Temporary isolation of a detector zoneWhat is a detector zone? Zone isolation procedure Viewing disabled zones Zone reactivation procedureDisable all zones Several zones disabledEnable all disabled zones Enable single zonesEnable a range of zones Single detector isolation procedure Temporary isolation of a single detectorWhen has a single detector to be isolated? Detector reactivation procedure Remote Transmission What is “remote transmission”?When has the remote transmission to be disabled? Disabling the remote alarm transmission facilityDisabling the remote fault transmission facility Enabling the remote fault transmission facilityAlarm devices When have alarm devices to be disabled?Disabling the alarm devices Enabling alarm devicesFaults Fire & Security Productse1973c-7 Siemens Building Technologies GroupFaults How do I respond to fault messages?Reset What remedies are available to the user?Maintenance Fire & Security Productse1973c-8 Siemens Building Technologies GroupRecommendations for function tests Detector testPurpose and Principle 4.After entering the last number press ok twice Functional testing of automatic AlgoRex-detectors Test procedure for detector tester RE6Test procedure for detector tester RE6T Required equipementTest procedure for type KAC Test procedure for type DIN indirect activationFunctional test of manual call points Control consolePurpose of the lamp test Lamp testLamp test procedure Purpose and principle Battery load testBattery load test procedure Purpose and principle Test of acoustic alarm devicesHorn test procedure Test of Remote Transmission RT Test procedure for remote alarm transmissionTest procedure for remote fault transmission Purpose and principleFire & Security Products e1973c-12Siemens Building Technologies Group 02.2004Other Functions Fire & Security Productse1973c-13 Siemens Building Technologies GroupPrinter disabling/enabling When has the printer to be disabled?Disabling the printer Enabling the printerPaper replacement with logging printer B2Q191 Switch off the printerEnable the printer Change of printer paperPolling the alarm counter Poll alarm counterPurpose of polling the alarm counter Polling the event memory Poll event memoryPurpose of polling the event memory Polling user text of zones or elements Poll user text of zones or elementsPurpose Polling the system status Poll system statusPurpose Poll configuration data Polling configuration data of detector zonesPolling configuration data of address lines PurposePrintout Print event memory/alarm counterPrint configuration/user text Print configuration zone/line/LONSet time and date Set time and datePurpuse and Principle Page Siemens Building Technologies AG Alte Landstrasse CH-8708Männedorf Tel. +41 1 −Document no. e1973c Edition