Siemens FC330A manual V1 =, V2 =, Alarm investigation time

Page 21
V1 =

V1 =

 

min.

Alarm acknowledgement time V1

nThe alarm acknowledgement time is active for automatic detectors when the system opera- tes in “manned” mode.

nThe system checks whether someone acknowledges the alarm message within this prepro- grammed time.

nAn alarm must be acknowledged before V1 expires, otherwise the alarm is transmitted to the fire department.

nThe remaining time is indicated on the text dis-

play in minutes and seconds.

 

 

ALARM zone ###/## / ######

1:27 min

 

 

1 ( 1)

 

 

 

V2 =

 

min.

Alarm investigation time V2

nThe alarm investigation time is active for automatic detectors when the system operates in “manned” mode.

nIt limits the time for investigating the fire location to an preprogrammed length.

nOn expiration of this time the alarm is transmitted to the fire department.

nIn case of minor incidents, an alarm must be reset before V2 expires.

nThe remaining time is indicated on the text dis-

play in minutes and seconds.

 

 

ALARM zone ###/## / ######

2:27 min

 

 

1 ( 1)

 

 

 

17

Fire & Security Products

e1973c-3

Siemens Building Technologies Group

02.2004

Image 21
Contents Phase Fire & Security ProductsSynova FC330A Fire detection system Operating manual System operation for userECopyright by Siemens Building Technologies AG Overview operating menu Fire & Security Products 06.2003Siemens Building Technologies Group Fire & Security Products Introductione1973c-1 Siemens Building Technologies GroupPage Fire & Security Products Fundamentalse1973c-2 Siemens Building Technologies GroupControl console layout 1 ALARMControl console FC330A Floor panel B3Q580B3Q590/595 Overview operating menu 4.other functions page4.other functions only for service engineerHow to operate the control console Fundamental operationALARM Normal operationWhat is “normal operation”? Mains interruptionOperating access Possible access levelsHow do I get operating access? Operating access via password Log inLog out Basic rules Operating “manned” and “unmanned”Extra time Automatic switchoverFire & Security Products Alarme1973c-3 Siemens Building Technologies GroupPurpose and principle SPECIAL Alarm ConceptAlarm investigation time V1 =V2 = Alarm ALARMPrinciple How to respond in case of alarm How are alarm messages shown on the text display?What to do after an alarm Scrolling alarm messagese1973c-3 Fire & Security ProductsSiemens Building Technologies Group 02.2004Fire & Security Products Disable/Enable System Partse1973c-4 Siemens Building Technologies GroupTemporary isolation of a detector zone What is a detector zone?When has a detector zone to be isolated? Zone isolation procedure Zone reactivation procedure Viewing disabled zonesDisable all zones Several zones disabledEnable single zones Enable a range of zonesEnable all disabled zones Temporary isolation of a single detector When has a single detector to be isolated?Single detector isolation procedure Detector reactivation procedure What is “remote transmission”? Remote TransmissionWhen has the remote transmission to be disabled? Disabling the remote alarm transmission facilityEnabling the remote fault transmission facility Disabling the remote fault transmission facilityWhen have alarm devices to be disabled? Alarm devicesDisabling the alarm devices Enabling alarm devicesFire & Security Products Faultse1973c-7 Siemens Building Technologies GroupHow do I respond to fault messages? FaultsReset What remedies are available to the user?Fire & Security Products Maintenancee1973c-8 Siemens Building Technologies GroupDetector test Purpose and PrincipleRecommendations for function tests 4.After entering the last number press ok twice Test procedure for detector tester RE6 Functional testing of automatic AlgoRex-detectorsTest procedure for detector tester RE6T Required equipementTest procedure for type DIN indirect activation Test procedure for type KACFunctional test of manual call points Control consoleLamp test Lamp test procedurePurpose of the lamp test Battery load test Battery load test procedurePurpose and principle Test of acoustic alarm devices Horn test procedurePurpose and principle Test procedure for remote alarm transmission Test of Remote Transmission RTTest procedure for remote fault transmission Purpose and principlee1973c-12 Fire & Security ProductsSiemens Building Technologies Group 02.2004Fire & Security Products Other Functionse1973c-13 Siemens Building Technologies GroupWhen has the printer to be disabled? Printer disabling/enablingDisabling the printer Enabling the printerSwitch off the printer Paper replacement with logging printer B2Q191Enable the printer Change of printer paperPoll alarm counter Purpose of polling the alarm counterPolling the alarm counter Poll event memory Purpose of polling the event memoryPolling the event memory Poll user text of zones or elements PurposePolling user text of zones or elements Poll system status PurposePolling the system status Polling configuration data of detector zones Poll configuration dataPolling configuration data of address lines PurposePrint event memory/alarm counter PrintoutPrint configuration/user text Print configuration zone/line/LONSet time and date Purpuse and PrincipleSet time and date Page CH-8708Männedorf Tel. +41 1 − Siemens Building Technologies AG Alte LandstrasseDocument no. e1973c Edition