Honeywell W7750A specifications Data Share Points

Page 108

74-2958— 1

108

Table 28. Data Share Points.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Stateor Value ofState

 

E-Vision (M, P,S)

 

 

DirectAccess

ManualConfig.

FailureDetect

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

User Address

NvName

Field Name

(Metric) or States plus Range

Default

Share

Map

Comments

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

DestOaEnth

nviOdEnthS7

 

mA

 

SI_INVALID

 

X

 

 

X

X

nviOdEnth allows one outdoor enthalpy sensor at a node to be shared by many

 

 

 

4 to 20

 

 

 

 

 

 

 

 

other nodes. When nviOdEnth is not SI_INVALID then any local sensor is

 

 

 

 

 

 

 

 

 

 

 

 

ignored by the local control algorithm and OdEnth is used instead. If the value is

 

 

 

 

 

 

 

 

 

 

 

 

outside the allowed range (4 to 20 mA), then the node uses the value of the

 

 

 

 

 

 

 

 

 

 

 

 

nearest range limit.

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcOaEnth

nvoOdEnthS7

 

mA

 

SI_INVALID

M

X

 

X

 

 

nvoOdEnth allows the local outdoor enthalpy sensor to be shared with other

 

 

 

4 to 20

 

 

 

 

 

 

 

 

nodes and is typically bound to OdEnth on other nodes. If the local sensor is

 

 

 

 

 

 

 

 

 

 

 

 

configured by Select, nviOdEnth is periodically sent on the network. If the local

 

 

 

 

 

 

 

 

 

 

 

 

sensor is not configured or currently showing an error, the value is SI_INVALID.

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcMonSwCt

nvoMonSw

value

0 to 100

 

0

 

X

 

 

 

 

MonSw value allows the monitor switch to be shared with another node. MonSw

 

 

 

 

 

 

 

 

 

 

 

 

is typically bound to an SBC to indicate a user defined alarm condition. The

 

 

 

 

 

 

 

 

 

 

 

 

output values have the following meanings: If the state is SW_OFF and the

 

 

 

 

 

 

 

 

 

 

 

 

value is 0, then the monitor switch is open. If the state is SW_ON and the value

 

 

 

 

 

 

 

 

 

 

 

 

is 100 percent, then the monitor switch is closed. If the state is SW_NUL and

 

 

 

 

 

 

 

 

 

 

 

 

the value is 0, then the monitor switch is not configured by Select.

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcMonSw

nvoMonSw

state

SW_OFF

0

SW_NUL

M

 

 

X

 

 

For MonSw.state, refer to MonSw.value.

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviIaqOvr

value

0 to 100

 

0

 

 

 

 

 

 

IaqOvr allows an indoor air quality sensor to be shared by many other nodes.

 

 

 

 

 

 

 

 

 

 

 

 

The states are follows: If the state is SW_OFF and the value is don’t care, then

 

 

 

 

 

 

 

 

 

 

 

 

the indoor air quality is acceptable. If the state is SW_ON and the value is 0,

 

 

 

 

 

 

 

 

 

 

 

 

then the indoor air quality is acceptable. If the node receives this combination of

 

 

 

 

 

 

 

 

 

 

 

 

state and value, then state is set to SW_OFF. If the state is SW_ON and the

 

 

 

 

 

 

 

 

 

 

 

 

value is not zero, then the indoor air quality is not acceptable and additional

 

 

 

 

 

 

 

 

 

 

 

 

outdoor air is needed to bring it back to acceptable. If the state is SW_NUL and

 

 

 

 

 

 

 

 

 

 

 

 

the value is don’t care, then the indoor air quality is acceptable. If the state is

 

 

 

 

 

 

 

 

 

 

 

 

other, then the network variable is not bound, the communications path from the

 

 

 

 

 

 

 

 

 

 

 

 

sending node has failed, or the sending node has failed. The indoor air quality is

 

 

 

 

 

 

 

 

 

 

 

 

acceptable.

 

 

 

 

 

 

 

 

 

 

 

 

 

DestIaqOvrd

nviIaqOvr

state

SW_OFF

0

SW_NUL

M

X

 

X

X

X

For IaqOvr.state, refer to IaqOvr.value.

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcIaqOvrCt

nvoIaqOvr

value

0 to 100

 

0

X

X

 

 

 

 

IaqOvr allows an indoor air quality sensor to be shared with other nodes and is

 

 

 

 

 

 

 

 

 

 

 

 

typically bound to IaqOvr on other nodes. If Data2.siSpaceCo2 is not

 

 

 

 

 

 

 

 

 

 

 

 

SI_INVALID, and exceeds Aux1SetPt.CO2IaqLimit, then poor air quality is

 

 

 

 

 

 

 

 

 

 

 

 

detected. In addition, if a local digital input is configured for IAQ_OVERRIDE_IN

 

 

 

 

 

 

 

 

 

 

 

 

and IO.IaqOverRide is 1 (TRUE) then poor air quality is also detected. The state

 

 

 

 

 

 

 

 

 

 

 

 

has the following meanings: If the state is SW_OFF and the value is 0, then the

 

 

 

 

 

 

 

 

 

 

 

 

indoor air quality is acceptable. If the state is SW_ON and the value is 100

 

 

 

 

 

 

 

 

 

 

 

 

percent, then the indoor air quality is not acceptable and additional outdoor air is

 

 

 

 

 

 

 

 

 

 

 

 

needed to bring it back to an acceptable state. If the state is SW_NUL and the

 

 

 

 

 

 

 

 

 

 

 

 

value is 0, then the economizer for this node has not been configured or there is

 

 

 

 

 

 

 

 

 

 

 

 

no sensor (via IO.SpaceDo2 or IO.IaqOverRide) configured or the only

 

 

 

 

 

 

 

 

 

 

 

 

configured sensor (via IO.SpaceCo2) has failed.

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcIaqOvr

nvoIaqOvr

state

SW_OFF

0

SW_NUL

M

X

 

X

 

 

For IaqOvr.State, refer to IaqOvr.value.

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Image 108
Contents Excel General Considerations W7750 Controllers Appendices72-2958 List of Figures 74-2958Setpoint ramping parameters with ramp rate calculation 74-2958List of Tables Description of Devices Typical system overviewControl Application Control ProvidedProducts Covered Organization of ManualApplicable Literature Form No TitleProduct Names Agency ListingsAbbreviations and Definitions Construction ControllersW7750A DI-1Performance Specifications PowerSpecial Note for the W7750B,C Unit Specified Space Temperature Sensing Range CPUMemory Capacity Excel 10 W7750C Constant Volume AHU Controller Jack DIN rail adapters Lonmark Functional ProfileInputs/Outputs Analog InputsDigital Inputs Triac Outputs on the W7750B,C Models onlyDigital Outputs Wall Modules Duct SensorT7770A1006 T7770CT7560A,B construction in in. mm Configurations GeneralConfiguration Options Summary For W7750A,B,C Controllers Allowable Heating and Cooling Equipment Configurations Staged HEATING/COOLING ControlHeat Pump Control Modulating HEATING/COOLING ControlEconomizer Control Pneumatic Actuator ControlOccupancy Sensor Window Open/Closed Digital InputWall Module Options MIXED-OUTPUT-TYPE ControlModes of Operation Dirty Filter MonitorIndoor Air Quality IAQ Override Smoke ControlOFF Mode DisabledNot AssignedOverview Plan the SystemDetermine Other Bus Devices Required Step No DescriptionLay Out Communications and Power Wiring Lonworks Bus LayoutExcel VAV Cvahu Power Wiring Power Budget Calculation ExampleDeviceVA Information Obtained from VA Ratings For Transformer Sizing Device Description ML6161A/B Damper Actuator, 35 lb-in R8242A ContactorML7984B PWM Valve Actuator Line LossPower wiring details for one Excel 10 per Transformer Nema class 2 transformer voltage output limitsPrepare Wiring Diagrams General ConsiderationsW7750 Controllers Factory Default Digital Outputs Terminal Terminal Number DescriptionConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Lonworks Bus Termination Module Pneumatic transducer to W7750B,C Shown, see triangle noteBrown Orange Lonworks Bus termination wiring options Order EquipmentT7770 and T7560 Wall Modules Honeywell Logo T7770D1018Sensor with Bypass/LED and Lonworks Jack Accessories Sensors AccessoriesEchelon Based Components and Parts Configure Controllers TroubleshootingTroubleshooting Excel 10 Controllers and Wall Modules CablingAlarms Excel 10 AlarmsResistance Value ohms Broadcasting the Service Message W7750 Controller Status LEDAppendix A. Using E-Vision to Commission a W7750 Controller Setting the Pid ParametersT7770C,D Wall Module Bypass Pushbutton and Override LED Sensor CalibrationAppendix B. Sequences of Operation Common Operations Room Temperature Sensor RmTemp HeatingEconomizer IAQ OptionBypass Mode StatusOvrd and StatusLed Remote Setpoint RmtStptPotSetpoint Limits LoSetptLim and HiSetptLim BypassTimeContinuous Unoccupied Mode Occupancy Mode and Manual Override ArbitrationNot Assigned Bypass OccupiedRecovery Ramping for Heat Pump Systems Time Clock OccTimeClockSchedule Master SchedMaster Setpoint RampingWindow Sensor StatusWndw Smoke ControlFAN Operation Demand Limit Control DLCTemperature Control Operations See for a diagram of a typical W7750 UnitDirty Filter Monitor Staged Cooling Control ONE StageTWO Stages Three StagesCascade Control of Modulating COOLING/HEATING Series 60 Modulating ControlPulse Width Modulating PWM Control Outdoor AIR Lockout of HEATING/COOLINGEconomizer ENABLE/DISABLE Control Indoor AIR Quality IAQ OverrideFreeze Stat Discharge AIR LOW Limit ControlInput Output Points Address Control Parameters AddressEnergy Management Points Address Status Points AddressMappable User Addresses and Table Number Relative Temperature Air FlowCO2 Concentration EnthalpyApplication reset therefore, these points can Placed in manual mode through a menuValid states and the corresponding Enumerated values are shownDefault Input/Output PointsNvName Field Name CommentsNciIoSelect DigitalIn1 Occsensor Shcedmasterin255 NciIoSelect DigitalIn2 Occsensor UnuseddiCOOLSTAGE1 COOLSTAGE2COOLSTAGE3 COOLSTAGE4Sixtyfifty SiinvalidPPM Siinvalid FalseTrue EconEnSw NvoIO EconEnableIn Position when poor indoor air quality is detectedStatusDI3 NvoIO UbDigitalIn OccSensr NvoIODefault Comments NvNameControl Parameters OdEnthalpyEnable MaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/HrMinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr MaxClRamp, OdTempMaxClRamp,PPM Discharge air temperature cascade control loop GainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees CGain for the cooling control loop GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees CEnergy Management Points Refer to WSHPEnable.value NviFree1 ValueAuxiliary functions. nviFree1 controls the FREE1OUT Network variable input failsNviTimeClk Value DestTimeClk NviTimeClk StateRefer to nviTimeClk.value 255 SrcTimeClkCt NvoTimeClk ValueStatus Points Alarmbit1 Bit Offset = SensorFailAlrmBit Offset = FrostProtectAlrm Bit Offset = InvalidSetPtAlrmNoalarm NodedisabledSmokealarm UpdateallfieldsDisabledmode StartupwaitHeat CoolStatusEconEn NvoData1 EconEnable Air flow switch is configuredNciAux1SetPts.ubOdEnthalpyEnableS2 StatusManOcc NvoData1 NetManOccHeatStgsOn NvoData1 HeatStagesOn Auxiliary heating stages are turned onCoolStgsOn NvoData1 CoolStagesOn For both heating or coolingIs 1, the algorithm controls as per the settings found NciConfig.SmokeControlController mode is switched to Freezeprotect MonitorSw NvoData1 MonSwitchBypasstimerfield TempcontrolptfieldSpacetempfield DischargetempfieldUbinvalid StatusError NvoError Errorbit0 SpaceTempErrorNvoError Errorbit0 Bit Offset = Temperature SetPtError NvoError Errorbit0NvoError Errorbit1 Bit Offset = RtnEnthalpyError NvoError Errorbit1Are disabled as if the sensor was not configured Bit Offset = SpaceCO2Error NvoError Errorbit1Bit Offset = NvWindowError NvoError Errorbit2 Bit Offset = NvDlcShedError NvoError Errorbit2Bit Offset = NvTodEventError NvoError Errorbit3 Bit Offset = NvByPassError NvoError Errorbit3Cfglocal CfgexternalCfgnul Calibration PointsConfiguration Parameters False True DisMinHtTime NciConfig DisableHeatMinTime DisMinClTime NciConfig DisableCoolMinTimeCascCntrl NciConfig CascadeControl UseRaTempCtl NciConfigLast NET Offset AbsolutemiddleNone Normal BypassonlyLonmark /Open System Points Hvacauto HvacheatHvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge Hvacnul Hvacoff74-2958 100 DestRmTemp NviSpaceTemp Degrees FSNVTtempp 14 to SrcRmTemp NvoSpaceTemp Degrees FHvacauto Hvacnul HvacmrngwrmupHvactest Alarmnotifydisabled NvoStatus Electricalfault 103 NvoStatus Inalarm255 Not configured 74-2958 NvoStatus UnabletomeasureSwon On other nodes. If the economizer function is configured by Corresponding economizer function is not enabled becauseSrcEconEnable NvoEcon State SrcEconEnCt NvoEcon ValueDirect Access And Special Points OFF Data Share Points Approximate Memory Size Estimating Procedure =using One-to-Many and not using points= including mapped points and others for Mapped points = number of mapped points per ExcelSensor Resistance Versus Temperature Resistance Ohms Resistance SensorsSensor Type Sensor UseOffset Setpoint Temperature Direct Setpoint TemperatureT7770B,C 10K ohm setpoint potentiometer Relative Above and Below Setpoint Resistance OhmsVoltage/Current Sensors Sensor Voltage Versus Humidity Humidity PercentageSensor Voltage Versus Humidity Relative Humidity Percentage Sensor Current Versus Enthalpy volts Enthalpy mA 113 74-2958T7242 or equivalent 74-2958 114MAmAmAmA AmA mA mA Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Sensor Voltage Vdc Versus Pressure Inw Pressure Inw kPa Sensor Voltage VdcInw 50.0.13