Honeywell W7750A Bit Offset = RtnEnthalpyError NvoError Errorbit1, NvoError Errorbit2

Page 91

Table 23. Status Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[1]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

RtnEnthalpyError: All control functions associated with the failed sensor are

 

 

 

Byte Offset = 1

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

 

Bit Offset = 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(RtnEnthalpyError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[1]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

MonitorSensorError: All control functions associated with the failed sensor

 

 

 

Byte Offset = 1

TRUE

1

 

 

 

 

 

 

 

 

 

are disabled as if the sensor was not configured.

 

 

 

Bit Offset = 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(MonitorSensorError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[1]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

SpaceCO2Error: All control functions associated with the failed sensor are

 

 

 

Byte Offset = 1

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

 

Bit Offset = 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SpaceCO2Error)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[1]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

FilterStaticPresError: All control functions associated with the failed sensor

 

 

 

Byte Offset = 1

TRUE

1

 

 

 

 

 

 

 

 

 

are disabled as if the sensor was not configured.

 

 

 

Bit Offset = 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(FilterStaticPresError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

91

 

nvoError

error_bit[1]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

ADCalError: All control functions associated with the failed sensor are

 

 

Byte Offset = 1

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

 

Bit Offset = 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(ADCalError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[1]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

ApplModeError: All control functions associated with the failed NV are

 

 

 

Byte Offset = 1

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the NV was not configured.

 

 

 

Bit Offset = 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(nvApplModeError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[2]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

SetPtOffsetError: All control functions associated with the failed NV are

 

 

 

Byte Offset = 2

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the NV was not configured.

 

 

 

Bit Offset = 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(nvSetPtOffsetError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[2]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

SpaceTempError: All control functions associated with the failed NV are

 

 

 

Byte Offset = 2

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the NV was not configured.

 

 

 

Bit Offset = 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(nvSpaceTempError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[2]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

OdTempError: All control functions associated with the failed NV are

 

 

 

Byte Offset = 2

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the NV was not configured.

 

 

 

Bit Offset = 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(nvOdTempError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[2]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

OdHumError: All control functions associated with the failed NV are

 

 

 

Byte Offset = 2

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the NV was not configured.

 

 

 

Bit Offset = 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(nvOdHumError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[2]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

SensorOccError: All control functions associated with the failed NV are

 

 

 

Byte Offset = 2

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the NV was not configured.

74-

 

 

Bit Offset = 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(nvSensorOccError)

 

 

 

 

 

 

 

 

 

 

 

 

2958— 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Image 91
Contents Excel Appendices General Considerations W7750 Controllers72-2958 74-2958 List of Figures74-2958 Setpoint ramping parameters with ramp rate calculationList of Tables Typical system overview Description of DevicesControl Provided Control ApplicationForm No Title Products CoveredOrganization of Manual Applicable LiteratureAgency Listings Product NamesAbbreviations and Definitions Controllers ConstructionDI-1 W7750APower Performance SpecificationsSpecial Note for the W7750B,C Unit CPU Specified Space Temperature Sensing RangeMemory Capacity Excel 10 W7750C Constant Volume AHU Controller Jack Lonmark Functional Profile DIN rail adaptersAnalog Inputs Inputs/OutputsTriac Outputs on the W7750B,C Models only Digital InputsDigital Outputs T7770C Wall ModulesDuct Sensor T7770A1006T7560A,B construction in in. mm General ConfigurationsConfiguration Options Summary For W7750A,B,C Controllers Modulating HEATING/COOLING Control Allowable Heating and Cooling Equipment ConfigurationsStaged HEATING/COOLING Control Heat Pump ControlPneumatic Actuator Control Economizer ControlMIXED-OUTPUT-TYPE Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsSmoke Control Modes of OperationDirty Filter Monitor Indoor Air Quality IAQ OverrideAssigned OFF ModeDisabled NotStep No Description OverviewPlan the System Determine Other Bus Devices RequiredLonworks Bus Layout Lay Out Communications and Power WiringExcel VAV Cvahu Power Budget Calculation Example Power WiringDeviceVA Information Obtained from Line Loss VA Ratings For Transformer Sizing Device DescriptionML6161A/B Damper Actuator, 35 lb-in R8242A Contactor ML7984B PWM Valve ActuatorNema class 2 transformer voltage output limits Power wiring details for one Excel 10 per TransformerGeneral Considerations Prepare Wiring DiagramsW7750 Controllers Terminal Terminal Number Description Factory Default Digital OutputsConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Pneumatic transducer to W7750B,C Shown, see triangle note Lonworks Bus Termination ModuleBrown Orange Order Equipment Lonworks Bus termination wiring optionsHoneywell Logo T7770D1018 T7770 and T7560 Wall ModulesSensor with Bypass/LED and Lonworks Jack Accessories Accessories SensorsEchelon Based Components and Parts Cabling Configure ControllersTroubleshooting Troubleshooting Excel 10 Controllers and Wall ModulesExcel 10 Alarms AlarmsResistance Value ohms W7750 Controller Status LED Broadcasting the Service MessageSensor Calibration Appendix A. Using E-Vision to Commission a W7750 ControllerSetting the Pid Parameters T7770C,D Wall Module Bypass Pushbutton and Override LEDAppendix B. Sequences of Operation Common Operations IAQ Option Room Temperature Sensor RmTempHeating EconomizerBypassTime Bypass Mode StatusOvrd and StatusLedRemote Setpoint RmtStptPot Setpoint Limits LoSetptLim and HiSetptLimBypass Occupied Continuous Unoccupied ModeOccupancy Mode and Manual Override Arbitration Not AssignedSetpoint Ramping Recovery Ramping for Heat Pump SystemsTime Clock OccTimeClock Schedule Master SchedMasterDemand Limit Control DLC Window Sensor StatusWndwSmoke Control FAN OperationSee for a diagram of a typical W7750 Unit Temperature Control OperationsDirty Filter Monitor Three Stages Staged Cooling ControlONE Stage TWO StagesOutdoor AIR Lockout of HEATING/COOLING Cascade Control of Modulating COOLING/HEATINGSeries 60 Modulating Control Pulse Width Modulating PWM ControlDischarge AIR LOW Limit Control Economizer ENABLE/DISABLE ControlIndoor AIR Quality IAQ Override Freeze StatStatus Points Address Input Output Points AddressControl Parameters Address Energy Management Points AddressMappable User Addresses and Table Number Enthalpy Relative TemperatureAir Flow CO2 ConcentrationEnumerated values are shown Application reset therefore, these points canPlaced in manual mode through a menu Valid states and the correspondingComments DefaultInput/Output Points NvName Field NameOccsensor Unuseddi NciIoSelect DigitalIn1Occsensor Shcedmasterin 255 NciIoSelect DigitalIn2COOLSTAGE4 COOLSTAGE1COOLSTAGE2 COOLSTAGE3Siinvalid SixtyfiftyFalse PPM SiinvalidTrue OccSensr NvoIO EconEnSw NvoIO EconEnableInPosition when poor indoor air quality is detected StatusDI3 NvoIO UbDigitalInNvName Default CommentsControl Parameters MaxClRamp, OdTempMaxClRamp, OdEnthalpyEnableMaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/HrPPM GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees C Discharge air temperature cascade control loopGainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C Gain for the cooling control loopEnergy Management Points Network variable input fails Refer to WSHPEnable.valueNviFree1 Value Auxiliary functions. nviFree1 controls the FREE1OUT255 SrcTimeClkCt NvoTimeClk Value NviTimeClk ValueDestTimeClk NviTimeClk State Refer to nviTimeClk.valueStatus Points Bit Offset = InvalidSetPtAlrm Alarmbit1Bit Offset = SensorFailAlrm Bit Offset = FrostProtectAlrmUpdateallfields NoalarmNodedisabled SmokealarmCool DisabledmodeStartupwait HeatStatusManOcc NvoData1 NetManOcc StatusEconEn NvoData1 EconEnableAir flow switch is configured NciAux1SetPts.ubOdEnthalpyEnableS2For both heating or cooling HeatStgsOn NvoData1 HeatStagesOnAuxiliary heating stages are turned on CoolStgsOn NvoData1 CoolStagesOnMonitorSw NvoData1 MonSwitch Is 1, the algorithm controls as per the settings foundNciConfig.SmokeControl Controller mode is switched to FreezeprotectDischargetempfield BypasstimerfieldTempcontrolptfield SpacetempfieldUbinvalid Bit Offset = Temperature SetPtError NvoError Errorbit0 StatusError NvoError Errorbit0SpaceTempError NvoError Errorbit0Bit Offset = SpaceCO2Error NvoError Errorbit1 NvoError Errorbit1Bit Offset = RtnEnthalpyError NvoError Errorbit1 Are disabled as if the sensor was not configuredBit Offset = NvByPassError NvoError Errorbit3 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvTodEventError NvoError Errorbit3Calibration Points CfglocalCfgexternal CfgnulConfiguration Parameters False True UseRaTempCtl NciConfig DisMinHtTime NciConfig DisableHeatMinTimeDisMinClTime NciConfig DisableCoolMinTime CascCntrl NciConfig CascadeControlBypassonly Last NETOffset Absolutemiddle None NormalLonmark /Open System Points Hvacoff HvacautoHvacheat Hvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge HvacnulSrcRmTemp NvoSpaceTemp Degrees F 74-2958 100DestRmTemp NviSpaceTemp Degrees F SNVTtempp 14 toHvacmrngwrmup Hvacauto HvacnulHvactest Alarmnotifydisabled NvoStatus Unabletomeasure NvoStatus Electricalfault103 NvoStatus Inalarm 255 Not configured 74-2958Swon SrcEconEnCt NvoEcon Value On other nodes. If the economizer function is configured byCorresponding economizer function is not enabled because SrcEconEnable NvoEcon StateDirect Access And Special Points OFF Data Share Points Mapped points = number of mapped points per Excel Approximate Memory Size Estimating Procedure=using One-to-Many and not using points = including mapped points and others forSensor Use Sensor Resistance Versus Temperature Resistance OhmsResistance Sensors Sensor TypeAbove and Below Setpoint Resistance Ohms Offset Setpoint TemperatureDirect Setpoint Temperature T7770B,C 10K ohm setpoint potentiometer RelativeSensor Voltage Versus Humidity Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Relative Humidity Percentage 113 74-2958 Sensor Current Versus Enthalpy volts Enthalpy mA74-2958 114 T7242 or equivalentMAmAmAmA AmA mA mA Sensor Voltage Versus Input Voltage To A/D Voltage to A/D 50.0.13 Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc Inw