Honeywell W7750A specifications Control Application, Control Provided

Page 7

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Control Application

W7750 systems in commercial buildings typically incorporate a packaged air handler system that delivers a constant volume of air at preconditioned temperatures to the zone being served. Each zone is usually serviced by a separate AHU; however, sometimes two or more AHUs service the same zone. Note that the W7750 is not designed to control Variable Air Volume (VAV) air handlers or Multi-Zone air handlers, where one air handler simultaneously controls the space temperature in many zones.

OA TEMP

The W7750 can control staged or modulating heating and cooling coils, mixed air economizer dampers, and the system fan. Control of heat pump units, where the compressor(s) is used for both cooling and heating, is also provided. The zone the W7750 services can use a T7770 or T7650 for space temperature sensing and an LONWORKS Bus network access for users. Fig. 2 shows a typical W7750 control application.

OUTDOOR AIR

 

COOL

HEAT

FILTER

COIL

COIL

 

FAN

 

 

-

+

M

 

 

EXCEL 10

W7750

CVAHU

DA TEMP

RA TEMP

OCCUPANCY

SENSOR

RETURN

T7770 OR T7560A,B

AIR

 

 

WINDOW CONTACT

 

Fig. 2. Typical W7750 control application.

ROOF

CEILING

DISCHARGE

AIR

M17488

Control Provided

The W7750 Controller is designed to control a single air handler to maintain the units space temperature at the current setpoint. Heating and cooling control is provided for either staged or modulating equipment. Up to four stages of mechanical cooling and up to four stages of heating are allowed. Modulating outputs can be either floating type such as a Series 60 control, or Pulse Width Modulated (PWM W7750B,C only) control.

The economizer dampers can be controlled directly with floating or PWM outputs, or indirectly using a digital output as an enable/disable signal to a packaged economizer controller. The economizer enable function, which decides when to allow outdoor air to be used for free cooling, can be configured to

one of ten strategies based on the inputs. For more details, see Appendix B— Sequences of Operation. When the economizer position is controlled from the W7750, the minimum position setting (for ventilation requirements) can be adjusted based on indoor air quality (IAQ) needs in the space. IAQ monitoring is provided through either a CO2 sensor or a digital input from a space-mounted IAQ limit switch.

For heat pump configurations, up to four compressors can be controlled, along with up to four stages of auxiliary heat, and a heat/cool change over valve. Including the supply fan, the combination of these items may not exceed eight outputs if a W7750B,C is used, or six outputs for a W7750A. (The eight outputs on the W7750C consist of five digital and three analog outputs.)

7

74-2958— 1

Image 7
Contents Excel Appendices General Considerations W7750 Controllers72-2958 74-2958 List of Figures74-2958 Setpoint ramping parameters with ramp rate calculationList of Tables Typical system overview Description of DevicesControl Provided Control ApplicationForm No Title Products CoveredOrganization of Manual Applicable LiteratureAgency Listings Product NamesAbbreviations and Definitions Controllers ConstructionDI-1 W7750APower Performance SpecificationsSpecial Note for the W7750B,C Unit CPU Specified Space Temperature Sensing RangeMemory Capacity Excel 10 W7750C Constant Volume AHU Controller Jack Lonmark Functional Profile DIN rail adaptersAnalog Inputs Inputs/OutputsTriac Outputs on the W7750B,C Models only Digital InputsDigital Outputs T7770C Wall ModulesDuct Sensor T7770A1006T7560A,B construction in in. mm General ConfigurationsConfiguration Options Summary For W7750A,B,C Controllers Modulating HEATING/COOLING Control Allowable Heating and Cooling Equipment ConfigurationsStaged HEATING/COOLING Control Heat Pump ControlPneumatic Actuator Control Economizer ControlMIXED-OUTPUT-TYPE Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsSmoke Control Modes of OperationDirty Filter Monitor Indoor Air Quality IAQ OverrideAssigned OFF ModeDisabled NotStep No Description OverviewPlan the System Determine Other Bus Devices RequiredLonworks Bus Layout Lay Out Communications and Power WiringExcel VAV Cvahu Power Budget Calculation Example Power WiringDeviceVA Information Obtained from Line Loss VA Ratings For Transformer Sizing Device DescriptionML6161A/B Damper Actuator, 35 lb-in R8242A Contactor ML7984B PWM Valve ActuatorNema class 2 transformer voltage output limits Power wiring details for one Excel 10 per TransformerGeneral Considerations Prepare Wiring DiagramsW7750 Controllers Terminal Terminal Number Description Factory Default Digital OutputsConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Pneumatic transducer to W7750B,C Shown, see triangle note Lonworks Bus Termination ModuleBrown Orange Order Equipment Lonworks Bus termination wiring optionsHoneywell Logo T7770D1018 T7770 and T7560 Wall ModulesSensor with Bypass/LED and Lonworks Jack Accessories Accessories SensorsEchelon Based Components and Parts Cabling Configure ControllersTroubleshooting Troubleshooting Excel 10 Controllers and Wall ModulesExcel 10 Alarms AlarmsResistance Value ohms W7750 Controller Status LED Broadcasting the Service MessageSensor Calibration Appendix A. Using E-Vision to Commission a W7750 ControllerSetting the Pid Parameters T7770C,D Wall Module Bypass Pushbutton and Override LEDAppendix B. Sequences of Operation Common Operations IAQ Option Room Temperature Sensor RmTempHeating EconomizerBypassTime Bypass Mode StatusOvrd and StatusLedRemote Setpoint RmtStptPot Setpoint Limits LoSetptLim and HiSetptLimBypass Occupied Continuous Unoccupied ModeOccupancy Mode and Manual Override Arbitration Not AssignedSetpoint Ramping Recovery Ramping for Heat Pump SystemsTime Clock OccTimeClock Schedule Master SchedMasterDemand Limit Control DLC Window Sensor StatusWndwSmoke Control FAN OperationSee for a diagram of a typical W7750 Unit Temperature Control OperationsDirty Filter Monitor Three Stages Staged Cooling ControlONE Stage TWO StagesOutdoor AIR Lockout of HEATING/COOLING Cascade Control of Modulating COOLING/HEATINGSeries 60 Modulating Control Pulse Width Modulating PWM ControlDischarge AIR LOW Limit Control Economizer ENABLE/DISABLE ControlIndoor AIR Quality IAQ Override Freeze StatStatus Points Address Input Output Points AddressControl Parameters Address Energy Management Points AddressMappable User Addresses and Table Number Enthalpy Relative TemperatureAir Flow CO2 ConcentrationEnumerated values are shown Application reset therefore, these points canPlaced in manual mode through a menu Valid states and the correspondingComments DefaultInput/Output Points NvName Field NameOccsensor Unuseddi NciIoSelect DigitalIn1Occsensor Shcedmasterin 255 NciIoSelect DigitalIn2COOLSTAGE4 COOLSTAGE1COOLSTAGE2 COOLSTAGE3Siinvalid SixtyfiftyFalse PPM SiinvalidTrue OccSensr NvoIO EconEnSw NvoIO EconEnableInPosition when poor indoor air quality is detected StatusDI3 NvoIO UbDigitalInNvName Default CommentsControl Parameters MaxClRamp, OdTempMaxClRamp, OdEnthalpyEnableMaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/HrPPM GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees C Discharge air temperature cascade control loopGainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C Gain for the cooling control loopEnergy Management Points Network variable input fails Refer to WSHPEnable.valueNviFree1 Value Auxiliary functions. nviFree1 controls the FREE1OUT255 SrcTimeClkCt NvoTimeClk Value NviTimeClk ValueDestTimeClk NviTimeClk State Refer to nviTimeClk.valueStatus Points Bit Offset = InvalidSetPtAlrm Alarmbit1Bit Offset = SensorFailAlrm Bit Offset = FrostProtectAlrmUpdateallfields NoalarmNodedisabled SmokealarmCool DisabledmodeStartupwait HeatStatusManOcc NvoData1 NetManOcc StatusEconEn NvoData1 EconEnableAir flow switch is configured NciAux1SetPts.ubOdEnthalpyEnableS2For both heating or cooling HeatStgsOn NvoData1 HeatStagesOnAuxiliary heating stages are turned on CoolStgsOn NvoData1 CoolStagesOnMonitorSw NvoData1 MonSwitch Is 1, the algorithm controls as per the settings foundNciConfig.SmokeControl Controller mode is switched to FreezeprotectDischargetempfield BypasstimerfieldTempcontrolptfield SpacetempfieldUbinvalid Bit Offset = Temperature SetPtError NvoError Errorbit0 StatusError NvoError Errorbit0SpaceTempError NvoError Errorbit0Bit Offset = SpaceCO2Error NvoError Errorbit1 NvoError Errorbit1Bit Offset = RtnEnthalpyError NvoError Errorbit1 Are disabled as if the sensor was not configuredBit Offset = NvByPassError NvoError Errorbit3 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvTodEventError NvoError Errorbit3Calibration Points CfglocalCfgexternal CfgnulConfiguration Parameters False True UseRaTempCtl NciConfig DisMinHtTime NciConfig DisableHeatMinTimeDisMinClTime NciConfig DisableCoolMinTime CascCntrl NciConfig CascadeControlBypassonly Last NETOffset Absolutemiddle None NormalLonmark /Open System Points Hvacoff HvacautoHvacheat Hvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge HvacnulSrcRmTemp NvoSpaceTemp Degrees F 74-2958 100DestRmTemp NviSpaceTemp Degrees F SNVTtempp 14 toHvacmrngwrmup Hvacauto HvacnulHvactest Alarmnotifydisabled NvoStatus Unabletomeasure NvoStatus Electricalfault103 NvoStatus Inalarm 255 Not configured 74-2958Swon SrcEconEnCt NvoEcon Value On other nodes. If the economizer function is configured byCorresponding economizer function is not enabled because SrcEconEnable NvoEcon StateDirect Access And Special Points OFF Data Share Points Mapped points = number of mapped points per Excel Approximate Memory Size Estimating Procedure=using One-to-Many and not using points = including mapped points and others forSensor Use Sensor Resistance Versus Temperature Resistance OhmsResistance Sensors Sensor TypeAbove and Below Setpoint Resistance Ohms Offset Setpoint TemperatureDirect Setpoint Temperature T7770B,C 10K ohm setpoint potentiometer RelativeSensor Voltage Versus Humidity Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Relative Humidity Percentage 113 74-2958 Sensor Current Versus Enthalpy volts Enthalpy mA74-2958 114 T7242 or equivalentMAmAmAmA AmA mA mA Sensor Voltage Versus Input Voltage To A/D Voltage to A/D 50.0.13 Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc Inw