| Table 25. Configuration Parameters. (Continued) |
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Value | Digital |
|
|
|
| Direct | Hardware | Manual |
| NOTE: Physical I/O points that are configurable are in Table 20. | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| User Address |
| NvName |
| Field Name | (Metric) or States plus Range | ofState | Stateor |
| Default | (M, P,S) | Share | Map | Access | Config. | Config. | Test | Comments | |
|
|
|
|
|
| Engineering Units: English |
|
|
|
|
|
|
|
|
|
|
|
| |
| OvrdPriority | nciConfig | OverridePriority | LAST | 0 |
| NET | P |
| X | X |
|
|
| OverridePriority configures the override arbitration between ManOcc, | ||||
|
|
|
|
|
| NET | 1 |
|
|
|
|
|
|
|
|
|
| Bypass.state, and the wall module override button. If OverridePriority is 0 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (LAST), then the last command received from either the wall module or |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| iManOcc determines the effective override state. If OverridePriority is 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (NET), this specifies that when ManOcc is not OC_NUL, that the effective |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| occupancy is ManOcc regardless of the wall module override state. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| UseWallModStpt | nciConfig | UseWallModStPt | FALSE | 0 |
| TRUE | P |
| X | X |
|
|
| UseWallModStpt specifies the OC_OCCUPIED temperature setpoint | ||||
|
|
|
|
|
| TRUE | 1 |
|
|
|
|
|
|
|
|
|
| source. If UseWallModStpt is 0 (FALSE), then the occupied TempSetPts | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| are used when the effective occupancy is OC_OCCUPIED. If |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| UseWallModStpt is 1 (TRUE), then the wall modules setpoint knob is used |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| when the effective occupancy is OC_OCCUPIED. SetPt overrides all. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SetPtKnob | nciConfig | SetPntKnob | OFFSET | 0 |
| ABSOLUTE_MIDDLE | P |
| X | X |
|
|
| SetPntKnob specifies the usage of the setpoint knob when | ||||
|
|
|
|
|
| ABSOLUTE_MIDDLE | 1 |
|
|
|
|
|
|
|
|
|
| UseWallModStPt is TRUE. When SetPntKnob is 0 (ABSOLUTE_MIDDLE), | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| the setpoint knob directly determines the center point of between the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OC_OCCUPIED cooling and heating setpoints. When SetPntKnob is 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (OFFSET), the effective setpoint is calculated by adding the remote |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| setpoint potentiometer value (center scale = 0) to the appropriate value of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TempSetPts. |
97 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OvrdType | nciConfig | OverrideType | NONE | 0 |
| NORMAL | P |
| X | X |
|
|
| OverrideType specifies the behavior of the override button. If the | |||||
|
|
|
|
|
| NORMAL | 1 |
|
|
|
|
|
|
|
|
|
| OverrideType is 0 (NONE) then the override button is disabled. An | |
|
|
|
|
|
| BYPASS_ONLY | 2 |
|
|
|
|
|
|
|
|
|
| OverrideType of 1 (NORMAL), causes the override button to set the | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OverRide state to OC_BYPASS for Aux2SetPt.BypassTime seconds when |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| the override button has been pressed for approximately 1 to 4 seconds, or |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| to set the OverRide state to UNOCC when the button has been pressed for |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| approximately 4 to 7 seconds. When the button is pressed longer than |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| approximately 7 seconds, then the OverRide state is set to OC_NUL. If the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OverrideType is 2 (BYPASS_ONLY), the override button sets the OverRide |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| state to OC_BYPASS for Aux2SetPt.BypassTime seconds on the first |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| press. On the next press, the OverRide state is set to OC_NUL. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Table 26. LONMARK® /Open System Points. |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ValueofState | DigitalStateor |
| Share | Map | DirectAccess | HardwareConfig. | ManualConfig. | FailureDetect | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| Engineering Units: English |
|
|
|
|
|
|
|
|
|
|
| |
| User Address |
| NvName |
| Field Name |
| (Metric) or States plus Range |
|
| Default |
|
|
|
|
|
|
| Comments | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| nciNodeSendT |
|
|
| Seconds |
|
|
| 0 |
|
|
|
|
|
|
| The maximum time between updates of network variable outputs from the |
|
|
| (SNVT_time_sec) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| node object. | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| nciRtuSendT |
|
|
| Seconds |
|
|
| 0 |
|
|
|
|
|
|
| The SGPUC and SGPU time (heart beat time) between updates of network |
|
|
| (SNVT_time_sec) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| variable outputs.NOTE: RtuSendT should be set to 55 seconds by a | |
74- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| management node to be compatible with a Honeywell system. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| nciRtuRcvT |
|
|
| Seconds |
|
|
| 0 |
|
|
|
|
|
|
| This is the failure detection time for network SGPUC and SGPU variables | |
2958 |
|
| (SNVT_time_sec) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| outputs.NOTE: RtuRcvT should be set to 300 seconds by a management | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| node to be compatible with a Honeywell system. | |
— 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER