Honeywell W7750A specifications List of Tables

Page 5

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

List of Tables

 

Table 1. Agency Listing

9

Table 2. List of Differences in W7750A and W7750B,C Controllers

11

Table 3. Common Configuration Options Summary For W7750A,B,C Controllers

22

Table 4. Configuration Options Summary For W7750A,B,C Controllers

23

Table 5. Modes Of Operation For The Excel 10 W7750 Controller

27

Table 6. Application Steps

29

Table 7. LONWORKS® Bus Configuration Rules And Device Node Numbers

30

Table 8. VA Ratings For Transformer Sizing

33

Table 9. Field Wiring Reference Table (Honeywell listed as AK#### or equivalent)

36

Table 10. W7750A Version I/O Description

37

Table 11. Excel 10 W7750 Controller Ordering Information

46

Table 12. Excel 10 Alarms

49

Table 14. Common Configuration Options Summary For W7750A,B,C Controllers

53

Table 15. Configuration Options Summary For W7750A,B,C Controllers

54

Table 16. Bypass Pushbutton Operation

55

Table 17. Interstage Minimum Times

60

Table 18. Excel 10 W7750 Controller User

 

Address Point Types

62

Table 20. Input/Output Points

67

Table 21. Control Parameters

73

Table 22. Energy Management Points

78

Table 23. Status Points

81

Table 24. Calibration Points

93

Table 25. Configuration Parameters

94

Table 26. LONMARK® /Open System Points

97

Table 27. Direct Access And Special Points

106

Table 28. Data Share Points

108

Table 29. Sensor Resistance Versus Temperature

110

Table 30. Sensor Resistance Versus Temperature

110

Table 31. Sensor Resistance Versus Temperature

111

Table 32. Sensor Resistance Versus Temperature

111

Table 33. Sensor Resistance Versus Temperature

111

Table 34. Sensor Voltage Versus Humidity

112

Table 35. Sensor Voltage Versus Humidity

112

Table 36. Sensor Current Versus Enthalpy (volts)

113

Table 37. Sensor Voltage Versus CO2 Concentration

115

Table 38. Sensor Voltage Versus Input Voltage To A/D

115

Table 39. Sensor Voltage (Vdc) Versus Pressure (Inw)

116

5

74-2958— 1

Image 5
Contents Excel 72-2958 General Considerations W7750 ControllersAppendices 74-2958 List of Figures74-2958 Setpoint ramping parameters with ramp rate calculationList of Tables Typical system overview Description of DevicesControl Provided Control ApplicationOrganization of Manual Products CoveredApplicable Literature Form No TitleAgency Listings Product NamesAbbreviations and Definitions Controllers ConstructionDI-1 W7750ASpecial Note for the W7750B,C Unit Performance SpecificationsPower Memory Capacity Specified Space Temperature Sensing RangeCPU Excel 10 W7750C Constant Volume AHU Controller Jack Lonmark Functional Profile DIN rail adaptersAnalog Inputs Inputs/OutputsDigital Outputs Digital InputsTriac Outputs on the W7750B,C Models only Duct Sensor Wall ModulesT7770A1006 T7770CT7560A,B construction in in. mm General ConfigurationsConfiguration Options Summary For W7750A,B,C Controllers Staged HEATING/COOLING Control Allowable Heating and Cooling Equipment ConfigurationsHeat Pump Control Modulating HEATING/COOLING ControlPneumatic Actuator Control Economizer ControlWindow Open/Closed Digital Input Occupancy SensorWall Module Options MIXED-OUTPUT-TYPE ControlDirty Filter Monitor Modes of OperationIndoor Air Quality IAQ Override Smoke ControlDisabled OFF ModeNot AssignedPlan the System OverviewDetermine Other Bus Devices Required Step No DescriptionLonworks Bus Layout Lay Out Communications and Power WiringExcel VAV Cvahu DeviceVA Information Obtained from Power WiringPower Budget Calculation Example ML6161A/B Damper Actuator, 35 lb-in R8242A Contactor VA Ratings For Transformer Sizing Device DescriptionML7984B PWM Valve Actuator Line LossNema class 2 transformer voltage output limits Power wiring details for one Excel 10 per TransformerGeneral Considerations Prepare Wiring DiagramsW7750 Controllers Terminal Terminal Number Description Factory Default Digital OutputsConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Pneumatic transducer to W7750B,C Shown, see triangle note Lonworks Bus Termination ModuleBrown Orange Order Equipment Lonworks Bus termination wiring optionsSensor with Bypass/LED and Lonworks Jack T7770 and T7560 Wall ModulesHoneywell Logo T7770D1018 Echelon Based Components and Parts Accessories SensorsAccessories Troubleshooting Configure ControllersTroubleshooting Excel 10 Controllers and Wall Modules CablingResistance Value ohms AlarmsExcel 10 Alarms W7750 Controller Status LED Broadcasting the Service MessageSetting the Pid Parameters Appendix A. Using E-Vision to Commission a W7750 ControllerT7770C,D Wall Module Bypass Pushbutton and Override LED Sensor CalibrationAppendix B. Sequences of Operation Common Operations Heating Room Temperature Sensor RmTempEconomizer IAQ OptionRemote Setpoint RmtStptPot Bypass Mode StatusOvrd and StatusLedSetpoint Limits LoSetptLim and HiSetptLim BypassTimeOccupancy Mode and Manual Override Arbitration Continuous Unoccupied ModeNot Assigned Bypass OccupiedTime Clock OccTimeClock Recovery Ramping for Heat Pump SystemsSchedule Master SchedMaster Setpoint RampingSmoke Control Window Sensor StatusWndwFAN Operation Demand Limit Control DLCDirty Filter Monitor Temperature Control OperationsSee for a diagram of a typical W7750 Unit ONE Stage Staged Cooling ControlTWO Stages Three StagesSeries 60 Modulating Control Cascade Control of Modulating COOLING/HEATINGPulse Width Modulating PWM Control Outdoor AIR Lockout of HEATING/COOLINGIndoor AIR Quality IAQ Override Economizer ENABLE/DISABLE ControlFreeze Stat Discharge AIR LOW Limit ControlControl Parameters Address Input Output Points AddressEnergy Management Points Address Status Points AddressMappable User Addresses and Table Number Air Flow Relative TemperatureCO2 Concentration EnthalpyPlaced in manual mode through a menu Application reset therefore, these points canValid states and the corresponding Enumerated values are shownInput/Output Points DefaultNvName Field Name CommentsOccsensor Shcedmasterin NciIoSelect DigitalIn1255 NciIoSelect DigitalIn2 Occsensor UnuseddiCOOLSTAGE2 COOLSTAGE1COOLSTAGE3 COOLSTAGE4Siinvalid SixtyfiftyTrue PPM SiinvalidFalse Position when poor indoor air quality is detected EconEnSw NvoIO EconEnableInStatusDI3 NvoIO UbDigitalIn OccSensr NvoIONvName Default CommentsControl Parameters MaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr OdEnthalpyEnableMinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr MaxClRamp, OdTempMaxClRamp,PPM GainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C Discharge air temperature cascade control loopGain for the cooling control loop GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees CEnergy Management Points NviFree1 Value Refer to WSHPEnable.valueAuxiliary functions. nviFree1 controls the FREE1OUT Network variable input failsDestTimeClk NviTimeClk State NviTimeClk ValueRefer to nviTimeClk.value 255 SrcTimeClkCt NvoTimeClk ValueStatus Points Bit Offset = SensorFailAlrm Alarmbit1Bit Offset = FrostProtectAlrm Bit Offset = InvalidSetPtAlrmNodedisabled NoalarmSmokealarm UpdateallfieldsStartupwait DisabledmodeHeat CoolAir flow switch is configured StatusEconEn NvoData1 EconEnableNciAux1SetPts.ubOdEnthalpyEnableS2 StatusManOcc NvoData1 NetManOccAuxiliary heating stages are turned on HeatStgsOn NvoData1 HeatStagesOnCoolStgsOn NvoData1 CoolStagesOn For both heating or coolingNciConfig.SmokeControl Is 1, the algorithm controls as per the settings foundController mode is switched to Freezeprotect MonitorSw NvoData1 MonSwitchTempcontrolptfield BypasstimerfieldSpacetempfield DischargetempfieldUbinvalid SpaceTempError StatusError NvoError Errorbit0NvoError Errorbit0 Bit Offset = Temperature SetPtError NvoError Errorbit0Bit Offset = RtnEnthalpyError NvoError Errorbit1 NvoError Errorbit1Are disabled as if the sensor was not configured Bit Offset = SpaceCO2Error NvoError Errorbit1Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvTodEventError NvoError Errorbit3 Bit Offset = NvByPassError NvoError Errorbit3Cfgexternal CfglocalCfgnul Calibration PointsConfiguration Parameters False True DisMinClTime NciConfig DisableCoolMinTime DisMinHtTime NciConfig DisableHeatMinTimeCascCntrl NciConfig CascadeControl UseRaTempCtl NciConfigOffset Absolutemiddle Last NETNone Normal BypassonlyLonmark /Open System Points Hvacheat HvacautoHvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge Hvacnul HvacoffDestRmTemp NviSpaceTemp Degrees F 74-2958 100SNVTtempp 14 to SrcRmTemp NvoSpaceTemp Degrees FHvactest Hvacauto HvacnulHvacmrngwrmup Alarmnotifydisabled 103 NvoStatus Inalarm NvoStatus Electricalfault255 Not configured 74-2958 NvoStatus UnabletomeasureSwon Corresponding economizer function is not enabled because On other nodes. If the economizer function is configured bySrcEconEnable NvoEcon State SrcEconEnCt NvoEcon ValueDirect Access And Special Points OFF Data Share Points =using One-to-Many and not using points Approximate Memory Size Estimating Procedure= including mapped points and others for Mapped points = number of mapped points per ExcelResistance Sensors Sensor Resistance Versus Temperature Resistance OhmsSensor Type Sensor UseDirect Setpoint Temperature Offset Setpoint TemperatureT7770B,C 10K ohm setpoint potentiometer Relative Above and Below Setpoint Resistance OhmsSensor Voltage Versus Humidity Relative Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Humidity Percentage 113 74-2958 Sensor Current Versus Enthalpy volts Enthalpy mAMAmAmAmA AmA mA mA T7242 or equivalent74-2958 114 Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Pressure Inw kPa Sensor Voltage Vdc Sensor Voltage Vdc Versus Pressure InwInw 50.0.13