Page 11

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

PWMPulse Width Modulated output; allows analog modulating control of equipment using a digital output on the controller.

RTDResistance Temperature Detector; refers to a type of temperature sensor whose resistance output changes according to the temperature change of the sensing element.

SubnetA LONWORKS Bus segment that is separated by a router from its Q7750A Zone Manager.

TODTime-Of-Day; the scheduling of Occupied and Unoccupied times of operation.

TPTTwisted Pair Transceiver.

VAVolt Amperes; a measure of electrical power output or consumption as applies to an ac device.

VacVoltage alternating current; ac voltage rather than dc voltage.

VAVVariable Air Volume; refers to either a type of air distribution system, or to the W7751 Excel 10 VAV Box Controller that controls a single zone in a variable air volume delivery system.

VOCVolatile Organic Compound; refers to a class of common pollutants sometimes found in buildings. Sources include out-gassing of construction materials, production-line by-products, and general cleaning solvents. A VOC is occasionally used as a measure of indoor air quality.

W7750The model number of the Excel 10 CVAHU Controllers (also see CVAHU).

W7751The model number of the Excel 10 VAV Box Controllers (also see VAV).

Wall ModuleThe Excel 10 Space Temperature Sensor and other optional controller inputs are contained in the T7770 or the T7560A,B Wall Modules. See Application Step 5. Order Equipment for details on the various models of Wall Modules.

XBSExcel Building Supervisor; a PC based tool for monitoring and changing parameters in C-Bus devices.

Construction

Controllers

The Excel 10 W7750 Controller is available in three different models. The W7750A Model, which is a low cost controller made for simple single zone air handlers and heat pump controls. The W7750B,C Models are intended for more complex applications.

The W7750B,C Models use Triacs for their digital outputs, where as the W7750A Model uses dry-contact relays. The W7750C Model also has three analog outputs available on terminals 16, 17 and 18.

All wiring connections to the controller are made at screw terminal blocks. Connection for operator access to the LONWORKS Bus is provided by plugging the SLTA connector cable into the LONWORKS Bus communications jack.

The W7750A,B,C Models consist of a single circuit board that is mounted in a sheet metal subbase and protected by a factory snap-on cover. The three controllers have the same physical appearance except for terminals 16 through 20 (W7750A) and different labels next to the wiring terminals (see Fig. 3, 5 or 6). Wires are attached to the screw terminal blocks on both sides of the controller. The controllers mount with two screws (see Fig. 4 or 7). The W7750 can also be mounted using DIN rail. To mount the W7750 on DIN rail, purchase two DIN rail adapters (obtain locally) part number TKAD, from Thomas and Betts, see Fig. 8, then snap onto standard EN 50 022 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) DIN rail. DIN rail is available through local suppliers.

A channel in the cover allows the controller status LED to be visible when the cover is in place. There are no field- serviceable parts on the circuit board and, therefore, it is intended that the cover never be removed.

The W7750A,B,C can be mounted in any orientation. Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation. See Fig. 4 and 7.

The input/output and control differences between the two models are summarized in Table 2. The I/O points in Table 2 are the free I/O points that are not reserved for Wall Module use.

Table 2. List of Differences in W7750A and W7750B,C Controllers.

 

 

 

 

W7750A Model

W7750B,C Models

 

 

 

Digital Outputs

Six Relay Outputs

Eight Triac Outputs

 

 

 

Digital Inputs

Two

Four

 

 

 

Wall Module

One*

One*

 

 

 

Analog Outputs

None

Three 4 to 20 mA Outputs (W7750C only)

 

 

 

Analog Inputs

One (Resistive Input Only)

Four (Two Resistive and two Voltage/Current Inputs)

 

 

 

DC Power

None

20 Vdc available to power optional sensors

 

 

 

Floating (Series 60) Control

Economizer Only

Heating, Cooling, and/or Economizer

 

 

 

PWM Control

None

Heating, Cooling, and/or Economizer

 

 

 

*The T7770 or the T7560 Wall Modules includes I/O points for two analog inputs for the space temperature and the setpoint knob, a digital input for the Bypass pushbutton, and a digital

output for the LED Bypass Indicator. These W7750 I/O points are configurable, but are normally used for the Wall Module.

11

74-2958— 1

Image 11
Contents Excel 72-2958 General Considerations W7750 ControllersAppendices 74-2958 List of Figures74-2958 Setpoint ramping parameters with ramp rate calculationList of Tables Typical system overview Description of DevicesControl Provided Control ApplicationForm No Title Products CoveredOrganization of Manual Applicable LiteratureAgency Listings Product NamesAbbreviations and Definitions Controllers ConstructionDI-1 W7750ASpecial Note for the W7750B,C Unit Performance SpecificationsPower Memory Capacity Specified Space Temperature Sensing RangeCPU Excel 10 W7750C Constant Volume AHU Controller Jack Lonmark Functional Profile DIN rail adaptersAnalog Inputs Inputs/OutputsDigital Outputs Digital InputsTriac Outputs on the W7750B,C Models only T7770C Wall ModulesDuct Sensor T7770A1006T7560A,B construction in in. mm General ConfigurationsConfiguration Options Summary For W7750A,B,C Controllers Modulating HEATING/COOLING Control Allowable Heating and Cooling Equipment ConfigurationsStaged HEATING/COOLING Control Heat Pump ControlPneumatic Actuator Control Economizer ControlMIXED-OUTPUT-TYPE Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsSmoke Control Modes of OperationDirty Filter Monitor Indoor Air Quality IAQ OverrideAssigned OFF ModeDisabled NotStep No Description OverviewPlan the System Determine Other Bus Devices RequiredLonworks Bus Layout Lay Out Communications and Power WiringExcel VAV Cvahu DeviceVA Information Obtained from Power WiringPower Budget Calculation Example Line Loss VA Ratings For Transformer Sizing Device DescriptionML6161A/B Damper Actuator, 35 lb-in R8242A Contactor ML7984B PWM Valve ActuatorNema class 2 transformer voltage output limits Power wiring details for one Excel 10 per TransformerGeneral Considerations Prepare Wiring DiagramsW7750 Controllers Terminal Terminal Number Description Factory Default Digital OutputsConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Pneumatic transducer to W7750B,C Shown, see triangle note Lonworks Bus Termination ModuleBrown Orange Order Equipment Lonworks Bus termination wiring optionsSensor with Bypass/LED and Lonworks Jack T7770 and T7560 Wall ModulesHoneywell Logo T7770D1018 Echelon Based Components and Parts Accessories SensorsAccessories Cabling Configure ControllersTroubleshooting Troubleshooting Excel 10 Controllers and Wall ModulesResistance Value ohms AlarmsExcel 10 Alarms W7750 Controller Status LED Broadcasting the Service MessageSensor Calibration Appendix A. Using E-Vision to Commission a W7750 ControllerSetting the Pid Parameters T7770C,D Wall Module Bypass Pushbutton and Override LEDAppendix B. Sequences of Operation Common Operations IAQ Option Room Temperature Sensor RmTempHeating EconomizerBypassTime Bypass Mode StatusOvrd and StatusLedRemote Setpoint RmtStptPot Setpoint Limits LoSetptLim and HiSetptLimBypass Occupied Continuous Unoccupied ModeOccupancy Mode and Manual Override Arbitration Not AssignedSetpoint Ramping Recovery Ramping for Heat Pump SystemsTime Clock OccTimeClock Schedule Master SchedMasterDemand Limit Control DLC Window Sensor StatusWndwSmoke Control FAN OperationDirty Filter Monitor Temperature Control OperationsSee for a diagram of a typical W7750 Unit Three Stages Staged Cooling ControlONE Stage TWO StagesOutdoor AIR Lockout of HEATING/COOLING Cascade Control of Modulating COOLING/HEATINGSeries 60 Modulating Control Pulse Width Modulating PWM ControlDischarge AIR LOW Limit Control Economizer ENABLE/DISABLE ControlIndoor AIR Quality IAQ Override Freeze StatStatus Points Address Input Output Points AddressControl Parameters Address Energy Management Points AddressMappable User Addresses and Table Number Enthalpy Relative TemperatureAir Flow CO2 ConcentrationEnumerated values are shown Application reset therefore, these points canPlaced in manual mode through a menu Valid states and the correspondingComments DefaultInput/Output Points NvName Field NameOccsensor Unuseddi NciIoSelect DigitalIn1Occsensor Shcedmasterin 255 NciIoSelect DigitalIn2COOLSTAGE4 COOLSTAGE1COOLSTAGE2 COOLSTAGE3Siinvalid SixtyfiftyTrue PPM SiinvalidFalse OccSensr NvoIO EconEnSw NvoIO EconEnableInPosition when poor indoor air quality is detected StatusDI3 NvoIO UbDigitalInNvName Default CommentsControl Parameters MaxClRamp, OdTempMaxClRamp, OdEnthalpyEnableMaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/HrPPM GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees C Discharge air temperature cascade control loopGainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C Gain for the cooling control loopEnergy Management Points Network variable input fails Refer to WSHPEnable.valueNviFree1 Value Auxiliary functions. nviFree1 controls the FREE1OUT255 SrcTimeClkCt NvoTimeClk Value NviTimeClk ValueDestTimeClk NviTimeClk State Refer to nviTimeClk.valueStatus Points Bit Offset = InvalidSetPtAlrm Alarmbit1Bit Offset = SensorFailAlrm Bit Offset = FrostProtectAlrmUpdateallfields NoalarmNodedisabled SmokealarmCool DisabledmodeStartupwait HeatStatusManOcc NvoData1 NetManOcc StatusEconEn NvoData1 EconEnableAir flow switch is configured NciAux1SetPts.ubOdEnthalpyEnableS2For both heating or cooling HeatStgsOn NvoData1 HeatStagesOnAuxiliary heating stages are turned on CoolStgsOn NvoData1 CoolStagesOnMonitorSw NvoData1 MonSwitch Is 1, the algorithm controls as per the settings foundNciConfig.SmokeControl Controller mode is switched to FreezeprotectDischargetempfield BypasstimerfieldTempcontrolptfield SpacetempfieldUbinvalid Bit Offset = Temperature SetPtError NvoError Errorbit0 StatusError NvoError Errorbit0SpaceTempError NvoError Errorbit0Bit Offset = SpaceCO2Error NvoError Errorbit1 NvoError Errorbit1Bit Offset = RtnEnthalpyError NvoError Errorbit1 Are disabled as if the sensor was not configuredBit Offset = NvByPassError NvoError Errorbit3 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvTodEventError NvoError Errorbit3Calibration Points CfglocalCfgexternal CfgnulConfiguration Parameters False True UseRaTempCtl NciConfig DisMinHtTime NciConfig DisableHeatMinTimeDisMinClTime NciConfig DisableCoolMinTime CascCntrl NciConfig CascadeControlBypassonly Last NETOffset Absolutemiddle None NormalLonmark /Open System Points Hvacoff HvacautoHvacheat Hvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge HvacnulSrcRmTemp NvoSpaceTemp Degrees F 74-2958 100DestRmTemp NviSpaceTemp Degrees F SNVTtempp 14 toHvactest Hvacauto HvacnulHvacmrngwrmup Alarmnotifydisabled NvoStatus Unabletomeasure NvoStatus Electricalfault103 NvoStatus Inalarm 255 Not configured 74-2958Swon SrcEconEnCt NvoEcon Value On other nodes. If the economizer function is configured byCorresponding economizer function is not enabled because SrcEconEnable NvoEcon StateDirect Access And Special Points OFF Data Share Points Mapped points = number of mapped points per Excel Approximate Memory Size Estimating Procedure=using One-to-Many and not using points = including mapped points and others forSensor Use Sensor Resistance Versus Temperature Resistance OhmsResistance Sensors Sensor TypeAbove and Below Setpoint Resistance Ohms Offset Setpoint TemperatureDirect Setpoint Temperature T7770B,C 10K ohm setpoint potentiometer RelativeSensor Voltage Versus Humidity Relative Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Humidity Percentage 113 74-2958 Sensor Current Versus Enthalpy volts Enthalpy mAMAmAmAmA AmA mA mA T7242 or equivalent74-2958 114 Sensor Voltage Versus Input Voltage To A/D Voltage to A/D 50.0.13 Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc Inw