Honeywell W7750A VA Ratings For Transformer Sizing Device Description, ML7984B PWM Valve Actuator

Page 33

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Table 8. VA Ratings For Transformer Sizing.

 

 

 

Device

Description

VA

 

 

 

W7750A

Excel 10 W7750 Controller

6.0

 

 

 

W7750B,C

Excel 10 W7750 Controllers

12.0

 

 

 

ML6161A/B

Damper Actuator, 35 lb-in.

2.2

 

 

 

R8242A

Contactor

21.0

 

 

 

M6410A

Valve Actuator

0.7

 

 

 

MMC325

Pneumatic Transducer

5.0

 

 

 

ML684

Versadrive Valve Actuator

12.0

 

 

 

ML6464

Damper Actuator, 66 lb-in.

3.0

 

 

 

ML6474

Damper Actuator, 132 lb-in.

3.0

 

 

 

ML6185

Damper Actuator SR 50 lb-in.

12.0

 

 

 

ML7984B

PWM Valve Actuator

6.0

 

 

 

For contactors and similar devices, the in-rush power ratings should be used as the worst case values when performing power budget calculations. Also, the application engineer must consider the possible combinations of simultaneously energized outputs and calculate the VA ratings accordingly. The worst case, that uses the largest possible VA load, should be determined when sizing the transformer.

LINE LOSS

Excel 10 Controllers must receive a minimum supply voltage of 20 Vac. If long power or output wire runs are required, a voltage drop due to Ohms Law (I x R) line loss must be considered. This line loss can result in a significant increase in total power required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft. (61m) run from the transformer to a W7750 Controller drawing 37 VA using two 18 AWG (1.0 mm2) wires.

The formula is:

Loss = [length of round-trip wire run (ft.)] X [resistance in wire (ohms per ft.)] X [current in wire (amperes)]

From specification data:

18 AWG twisted pair wire has 6.52 ohms per 1000 feet. Loss = [(400 ft.) X (6.52/1000 ohms per ft.)] X

[(37 VA)/(24V)] = 4.02 volts

This means that four volts are going to be lost between the transformer and the controller; therefore, to assure the controller receives at least 20 volts, the transformer must output more than 24 volts. Because all transformer output voltage levels depend on the size of the connected load, a larger transformer outputs a higher voltage than a smaller one for a given load. Fig. 21 shows this voltage load dependence.

In the preceding I x R loss example, even though the controller load is only 37 VA, a standard 40 VA transformer is not sufficient due to the line loss. From Fig. 21, a 40 VA transformer is just under 100 percent loaded (for the 37 VA

controller) and, therefore, has a secondary voltage of 22.9 volts. (Use the lower edge of the shaded zone in Fig. 21 that represents the worst case conditions.) When the I x R loss of four volts is subtracted, only 18.9 volts reaches the controller, which is not enough voltage for proper operation.

In this situation, the engineer basically has three alternatives:

1.Use a larger transformer; for example, if an 80 VA model is used, see Fig. 21, an output of 24.4 volts minus the four volt line loss supplies 20.4V to the controller. Although acceptable, the four-volt line-loss in this example is higher than recommended. See the following IMPORTANT.

2.Use heavier gauge wire for the power run. 14 AWG (2.0 mm2) wire has a resistance of 2.57 ohms per 1000 ft. which, using the preceding formula, gives a line-loss of only 1.58 volts (compared with 4.02 volts). This would allow a 40 VA transformer to be used. 14 AWG (2.0 mm2) wire is the recommended wire size for 24 Vac wiring.

3.Locate the transformer closer to the controller, thereby reducing the length of the wire run, and the line loss. The issue of line-loss is also important in the case of the output wiring connected to the Triac digital outputs. The same formula and method are used. The rule to remember is to keep all power and output wire runs as short as practical. When necessary, use heavier gauge wire, a bigger transformer, or install the transformer closer to the controller.

IMPORTANT

No installation should be designed where the line loss is greater than two volts to allow for nominal operation if the primary voltage drops to 102 Vac (120 Vac minus 15 percent).

To meet the National Electrical Manufacturers Association (NEMA) standards, a transformer must stay within the NEMA limits. The chart in Fig. 21 shows the required limits at various loads.

With 100 percent load, the transformer secondary must supply between 23 and 25 volts to meet the NEMA standard. When a purchased transformer meets the NEMA standard DC20-1986, the transformer voltage-regulating ability can be considered reliable. Compliance with the NEMA standard is voluntary.

The following Honeywell transformers meet this NEMA

standard:

 

Transformer Type

VA Rating

AT20A

20

AT40A

40

AT72D

40

AT87A

50

AK3310 Assembly

100

33

74-2958— 1

Image 33
Contents Excel General Considerations W7750 Controllers Appendices72-2958 74-2958 List of Figures74-2958 Setpoint ramping parameters with ramp rate calculationList of Tables Typical system overview Description of DevicesControl Provided Control ApplicationOrganization of Manual Products CoveredApplicable Literature Form No TitleAgency Listings Product NamesAbbreviations and Definitions Controllers ConstructionDI-1 W7750APerformance Specifications PowerSpecial Note for the W7750B,C Unit Specified Space Temperature Sensing Range CPUMemory Capacity Excel 10 W7750C Constant Volume AHU Controller Jack Lonmark Functional Profile DIN rail adaptersAnalog Inputs Inputs/OutputsDigital Inputs Triac Outputs on the W7750B,C Models onlyDigital Outputs Duct Sensor Wall ModulesT7770A1006 T7770CT7560A,B construction in in. mm General ConfigurationsConfiguration Options Summary For W7750A,B,C Controllers Staged HEATING/COOLING Control Allowable Heating and Cooling Equipment ConfigurationsHeat Pump Control Modulating HEATING/COOLING ControlPneumatic Actuator Control Economizer ControlWindow Open/Closed Digital Input Occupancy SensorWall Module Options MIXED-OUTPUT-TYPE ControlDirty Filter Monitor Modes of OperationIndoor Air Quality IAQ Override Smoke ControlDisabled OFF ModeNot AssignedPlan the System OverviewDetermine Other Bus Devices Required Step No DescriptionLonworks Bus Layout Lay Out Communications and Power WiringExcel VAV Cvahu Power Wiring Power Budget Calculation ExampleDeviceVA Information Obtained from ML6161A/B Damper Actuator, 35 lb-in R8242A Contactor VA Ratings For Transformer Sizing Device DescriptionML7984B PWM Valve Actuator Line LossNema class 2 transformer voltage output limits Power wiring details for one Excel 10 per TransformerGeneral Considerations Prepare Wiring DiagramsW7750 Controllers Terminal Terminal Number Description Factory Default Digital OutputsConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Pneumatic transducer to W7750B,C Shown, see triangle note Lonworks Bus Termination ModuleBrown Orange Order Equipment Lonworks Bus termination wiring optionsT7770 and T7560 Wall Modules Honeywell Logo T7770D1018Sensor with Bypass/LED and Lonworks Jack Accessories Sensors AccessoriesEchelon Based Components and Parts Troubleshooting Configure ControllersTroubleshooting Excel 10 Controllers and Wall Modules CablingAlarms Excel 10 AlarmsResistance Value ohms W7750 Controller Status LED Broadcasting the Service MessageSetting the Pid Parameters Appendix A. Using E-Vision to Commission a W7750 ControllerT7770C,D Wall Module Bypass Pushbutton and Override LED Sensor CalibrationAppendix B. Sequences of Operation Common Operations Heating Room Temperature Sensor RmTempEconomizer IAQ OptionRemote Setpoint RmtStptPot Bypass Mode StatusOvrd and StatusLedSetpoint Limits LoSetptLim and HiSetptLim BypassTimeOccupancy Mode and Manual Override Arbitration Continuous Unoccupied ModeNot Assigned Bypass OccupiedTime Clock OccTimeClock Recovery Ramping for Heat Pump SystemsSchedule Master SchedMaster Setpoint RampingSmoke Control Window Sensor StatusWndwFAN Operation Demand Limit Control DLCTemperature Control Operations See for a diagram of a typical W7750 UnitDirty Filter Monitor ONE Stage Staged Cooling ControlTWO Stages Three StagesSeries 60 Modulating Control Cascade Control of Modulating COOLING/HEATINGPulse Width Modulating PWM Control Outdoor AIR Lockout of HEATING/COOLINGIndoor AIR Quality IAQ Override Economizer ENABLE/DISABLE ControlFreeze Stat Discharge AIR LOW Limit ControlControl Parameters Address Input Output Points AddressEnergy Management Points Address Status Points AddressMappable User Addresses and Table Number Air Flow Relative TemperatureCO2 Concentration EnthalpyPlaced in manual mode through a menu Application reset therefore, these points canValid states and the corresponding Enumerated values are shownInput/Output Points DefaultNvName Field Name CommentsOccsensor Shcedmasterin NciIoSelect DigitalIn1255 NciIoSelect DigitalIn2 Occsensor UnuseddiCOOLSTAGE2 COOLSTAGE1COOLSTAGE3 COOLSTAGE4Siinvalid SixtyfiftyPPM Siinvalid FalseTrue Position when poor indoor air quality is detected EconEnSw NvoIO EconEnableInStatusDI3 NvoIO UbDigitalIn OccSensr NvoIONvName Default CommentsControl Parameters MaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr OdEnthalpyEnableMinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr MaxClRamp, OdTempMaxClRamp,PPM GainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C Discharge air temperature cascade control loopGain for the cooling control loop GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees CEnergy Management Points NviFree1 Value Refer to WSHPEnable.valueAuxiliary functions. nviFree1 controls the FREE1OUT Network variable input failsDestTimeClk NviTimeClk State NviTimeClk ValueRefer to nviTimeClk.value 255 SrcTimeClkCt NvoTimeClk ValueStatus Points Bit Offset = SensorFailAlrm Alarmbit1Bit Offset = FrostProtectAlrm Bit Offset = InvalidSetPtAlrmNodedisabled NoalarmSmokealarm UpdateallfieldsStartupwait DisabledmodeHeat CoolAir flow switch is configured StatusEconEn NvoData1 EconEnableNciAux1SetPts.ubOdEnthalpyEnableS2 StatusManOcc NvoData1 NetManOccAuxiliary heating stages are turned on HeatStgsOn NvoData1 HeatStagesOnCoolStgsOn NvoData1 CoolStagesOn For both heating or coolingNciConfig.SmokeControl Is 1, the algorithm controls as per the settings foundController mode is switched to Freezeprotect MonitorSw NvoData1 MonSwitchTempcontrolptfield BypasstimerfieldSpacetempfield DischargetempfieldUbinvalid SpaceTempError StatusError NvoError Errorbit0NvoError Errorbit0 Bit Offset = Temperature SetPtError NvoError Errorbit0Bit Offset = RtnEnthalpyError NvoError Errorbit1 NvoError Errorbit1Are disabled as if the sensor was not configured Bit Offset = SpaceCO2Error NvoError Errorbit1Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvTodEventError NvoError Errorbit3 Bit Offset = NvByPassError NvoError Errorbit3Cfgexternal CfglocalCfgnul Calibration PointsConfiguration Parameters False True DisMinClTime NciConfig DisableCoolMinTime DisMinHtTime NciConfig DisableHeatMinTimeCascCntrl NciConfig CascadeControl UseRaTempCtl NciConfigOffset Absolutemiddle Last NETNone Normal BypassonlyLonmark /Open System Points Hvacheat HvacautoHvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge Hvacnul HvacoffDestRmTemp NviSpaceTemp Degrees F 74-2958 100SNVTtempp 14 to SrcRmTemp NvoSpaceTemp Degrees FHvacauto Hvacnul HvacmrngwrmupHvactest Alarmnotifydisabled 103 NvoStatus Inalarm NvoStatus Electricalfault255 Not configured 74-2958 NvoStatus UnabletomeasureSwon Corresponding economizer function is not enabled because On other nodes. If the economizer function is configured bySrcEconEnable NvoEcon State SrcEconEnCt NvoEcon ValueDirect Access And Special Points OFF Data Share Points =using One-to-Many and not using points Approximate Memory Size Estimating Procedure= including mapped points and others for Mapped points = number of mapped points per ExcelResistance Sensors Sensor Resistance Versus Temperature Resistance OhmsSensor Type Sensor UseDirect Setpoint Temperature Offset Setpoint TemperatureT7770B,C 10K ohm setpoint potentiometer Relative Above and Below Setpoint Resistance OhmsVoltage/Current Sensors Sensor Voltage Versus Humidity Humidity PercentageSensor Voltage Versus Humidity Relative Humidity Percentage 113 74-2958 Sensor Current Versus Enthalpy volts Enthalpy mAT7242 or equivalent 74-2958 114MAmAmAmA AmA mA mA Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Pressure Inw kPa Sensor Voltage Vdc Sensor Voltage Vdc Versus Pressure InwInw 50.0.13