Honeywell W7750A NviTimeClk Value, DestTimeClk NviTimeClk State, Refer to nviTimeClk.value

Page 80

74-2958— 1

80

Table 22. Energy Management Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviTimeClk

value

0 to 100

 

0

 

 

 

 

 

 

 

nviTimeClk.value:nviTimeClk allows a time clock at one node to be shared

 

 

 

 

 

 

 

 

 

 

 

 

 

with other nodes over the network. nviTimeClk is ORed with the local time

 

 

 

 

 

 

 

 

 

 

 

 

 

clock sensor and the results are placed in Data1.OccTimeClock. TimeClk is

 

 

 

 

 

 

 

 

 

 

 

 

 

received from another node and may have the following values: If the state

 

 

 

 

 

 

 

 

 

 

 

 

 

is SW_OFF, the space is scheduled to be unoccupied. If the state is

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_ON and the value is 0, the space is scheduled to be unoccupied. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

node receives this combination of state and value, then state is set to

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_OFF. If the state is SW_ON and the value is not zero, the space is

 

 

 

 

 

 

 

 

 

 

 

 

 

scheduled to be occupied. If the state is SW_NUL or other and the value is

 

 

 

 

 

 

 

 

 

 

 

 

 

don’t care, the network variable is not bound and is ignored.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestTimeClk

nviTimeClk

state

SW_OFF

0

SW_NUL

 

 

 

 

 

 

X

Refer to nviTimeClk.value.

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcTimeClkCt

nvoTimeClk

value

0 to 100

 

0

 

 

 

 

 

 

 

nvoTimeClk reports the current state of the physical time clock input. The

 

 

 

 

 

 

 

 

 

 

 

 

 

output values have the following meanings: If the state is SW_OFF and the

 

 

 

 

 

 

 

 

 

 

 

 

 

value is 0, the time clock input is configured and the input is open circuit. If

 

 

 

 

 

 

 

 

 

 

 

 

 

SCHEDULE_MASTER_IN is configured, then the schedule master input

 

 

 

 

 

 

 

 

 

 

 

 

 

must be shorted to ground to reach this state. If the state is SW_ON and the

 

 

 

 

 

 

 

 

 

 

 

 

 

value is 100 precent, the time clock input is configured and the input is a

 

 

 

 

 

 

 

 

 

 

 

 

 

closed circuit. If SCHEDULE_MASTER_IN is configured, then the schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

master input must be shorted to ground to reach this state. If the state is

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL and the value is 0, the time clock input is not configured by Select

 

 

 

 

 

 

 

 

 

 

 

 

 

or the SCHEDULE_MASTER_IN physical input is configured and the input

 

 

 

 

 

 

 

 

 

 

 

 

 

is open (nvoIO.ScheduleMaster = 0).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcTimeClk

nvoTimeClk

state

SW_OFF

0

SW_NUL

 

 

 

 

 

 

 

Refer to nvoTimeClk.value.

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Image 80
Contents Excel 72-2958 General Considerations W7750 ControllersAppendices List of Figures 74-2958Setpoint ramping parameters with ramp rate calculation 74-2958List of Tables Description of Devices Typical system overviewControl Application Control ProvidedProducts Covered Organization of ManualApplicable Literature Form No TitleProduct Names Agency ListingsAbbreviations and Definitions Construction ControllersW7750A DI-1Special Note for the W7750B,C Unit Performance SpecificationsPower Memory Capacity Specified Space Temperature Sensing RangeCPU Excel 10 W7750C Constant Volume AHU Controller Jack DIN rail adapters Lonmark Functional ProfileInputs/Outputs Analog InputsDigital Outputs Digital InputsTriac Outputs on the W7750B,C Models only Wall Modules Duct SensorT7770A1006 T7770CT7560A,B construction in in. mm Configurations GeneralConfiguration Options Summary For W7750A,B,C Controllers Allowable Heating and Cooling Equipment Configurations Staged HEATING/COOLING ControlHeat Pump Control Modulating HEATING/COOLING ControlEconomizer Control Pneumatic Actuator ControlOccupancy Sensor Window Open/Closed Digital InputWall Module Options MIXED-OUTPUT-TYPE ControlModes of Operation Dirty Filter MonitorIndoor Air Quality IAQ Override Smoke ControlOFF Mode DisabledNot AssignedOverview Plan the SystemDetermine Other Bus Devices Required Step No DescriptionLay Out Communications and Power Wiring Lonworks Bus LayoutExcel VAV Cvahu DeviceVA Information Obtained from Power WiringPower Budget Calculation Example VA Ratings For Transformer Sizing Device Description ML6161A/B Damper Actuator, 35 lb-in R8242A ContactorML7984B PWM Valve Actuator Line LossPower wiring details for one Excel 10 per Transformer Nema class 2 transformer voltage output limitsPrepare Wiring Diagrams General ConsiderationsW7750 Controllers Factory Default Digital Outputs Terminal Terminal Number DescriptionConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Lonworks Bus Termination Module Pneumatic transducer to W7750B,C Shown, see triangle noteBrown Orange Lonworks Bus termination wiring options Order EquipmentSensor with Bypass/LED and Lonworks Jack T7770 and T7560 Wall ModulesHoneywell Logo T7770D1018 Echelon Based Components and Parts Accessories SensorsAccessories Configure Controllers TroubleshootingTroubleshooting Excel 10 Controllers and Wall Modules CablingResistance Value ohms AlarmsExcel 10 Alarms Broadcasting the Service Message W7750 Controller Status LEDAppendix A. Using E-Vision to Commission a W7750 Controller Setting the Pid ParametersT7770C,D Wall Module Bypass Pushbutton and Override LED Sensor CalibrationAppendix B. Sequences of Operation Common Operations Room Temperature Sensor RmTemp HeatingEconomizer IAQ OptionBypass Mode StatusOvrd and StatusLed Remote Setpoint RmtStptPotSetpoint Limits LoSetptLim and HiSetptLim BypassTimeContinuous Unoccupied Mode Occupancy Mode and Manual Override ArbitrationNot Assigned Bypass OccupiedRecovery Ramping for Heat Pump Systems Time Clock OccTimeClockSchedule Master SchedMaster Setpoint RampingWindow Sensor StatusWndw Smoke ControlFAN Operation Demand Limit Control DLCDirty Filter Monitor Temperature Control OperationsSee for a diagram of a typical W7750 Unit Staged Cooling Control ONE StageTWO Stages Three StagesCascade Control of Modulating COOLING/HEATING Series 60 Modulating ControlPulse Width Modulating PWM Control Outdoor AIR Lockout of HEATING/COOLINGEconomizer ENABLE/DISABLE Control Indoor AIR Quality IAQ OverrideFreeze Stat Discharge AIR LOW Limit ControlInput Output Points Address Control Parameters AddressEnergy Management Points Address Status Points AddressMappable User Addresses and Table Number Relative Temperature Air FlowCO2 Concentration EnthalpyApplication reset therefore, these points can Placed in manual mode through a menuValid states and the corresponding Enumerated values are shownDefault Input/Output PointsNvName Field Name CommentsNciIoSelect DigitalIn1 Occsensor Shcedmasterin255 NciIoSelect DigitalIn2 Occsensor UnuseddiCOOLSTAGE1 COOLSTAGE2COOLSTAGE3 COOLSTAGE4Sixtyfifty SiinvalidTrue PPM SiinvalidFalse EconEnSw NvoIO EconEnableIn Position when poor indoor air quality is detectedStatusDI3 NvoIO UbDigitalIn OccSensr NvoIODefault Comments NvNameControl Parameters OdEnthalpyEnable MaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/HrMinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr MaxClRamp, OdTempMaxClRamp,PPM Discharge air temperature cascade control loop GainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees CGain for the cooling control loop GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees CEnergy Management Points Refer to WSHPEnable.value NviFree1 ValueAuxiliary functions. nviFree1 controls the FREE1OUT Network variable input failsNviTimeClk Value DestTimeClk NviTimeClk StateRefer to nviTimeClk.value 255 SrcTimeClkCt NvoTimeClk ValueStatus Points Alarmbit1 Bit Offset = SensorFailAlrmBit Offset = FrostProtectAlrm Bit Offset = InvalidSetPtAlrmNoalarm NodedisabledSmokealarm UpdateallfieldsDisabledmode StartupwaitHeat CoolStatusEconEn NvoData1 EconEnable Air flow switch is configuredNciAux1SetPts.ubOdEnthalpyEnableS2 StatusManOcc NvoData1 NetManOccHeatStgsOn NvoData1 HeatStagesOn Auxiliary heating stages are turned onCoolStgsOn NvoData1 CoolStagesOn For both heating or coolingIs 1, the algorithm controls as per the settings found NciConfig.SmokeControlController mode is switched to Freezeprotect MonitorSw NvoData1 MonSwitchBypasstimerfield TempcontrolptfieldSpacetempfield DischargetempfieldUbinvalid StatusError NvoError Errorbit0 SpaceTempErrorNvoError Errorbit0 Bit Offset = Temperature SetPtError NvoError Errorbit0NvoError Errorbit1 Bit Offset = RtnEnthalpyError NvoError Errorbit1Are disabled as if the sensor was not configured Bit Offset = SpaceCO2Error NvoError Errorbit1Bit Offset = NvWindowError NvoError Errorbit2 Bit Offset = NvDlcShedError NvoError Errorbit2Bit Offset = NvTodEventError NvoError Errorbit3 Bit Offset = NvByPassError NvoError Errorbit3Cfglocal CfgexternalCfgnul Calibration PointsConfiguration Parameters False True DisMinHtTime NciConfig DisableHeatMinTime DisMinClTime NciConfig DisableCoolMinTimeCascCntrl NciConfig CascadeControl UseRaTempCtl NciConfigLast NET Offset AbsolutemiddleNone Normal BypassonlyLonmark /Open System Points Hvacauto HvacheatHvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge Hvacnul Hvacoff74-2958 100 DestRmTemp NviSpaceTemp Degrees FSNVTtempp 14 to SrcRmTemp NvoSpaceTemp Degrees FHvactest Hvacauto HvacnulHvacmrngwrmup Alarmnotifydisabled NvoStatus Electricalfault 103 NvoStatus Inalarm255 Not configured 74-2958 NvoStatus UnabletomeasureSwon On other nodes. If the economizer function is configured by Corresponding economizer function is not enabled becauseSrcEconEnable NvoEcon State SrcEconEnCt NvoEcon ValueDirect Access And Special Points OFF Data Share Points Approximate Memory Size Estimating Procedure =using One-to-Many and not using points= including mapped points and others for Mapped points = number of mapped points per ExcelSensor Resistance Versus Temperature Resistance Ohms Resistance SensorsSensor Type Sensor UseOffset Setpoint Temperature Direct Setpoint TemperatureT7770B,C 10K ohm setpoint potentiometer Relative Above and Below Setpoint Resistance OhmsSensor Voltage Versus Humidity Relative Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Humidity Percentage Sensor Current Versus Enthalpy volts Enthalpy mA 113 74-2958MAmAmAmA AmA mA mA T7242 or equivalent74-2958 114 Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Sensor Voltage Vdc Versus Pressure Inw Pressure Inw kPa Sensor Voltage VdcInw 50.0.13