Honeywell W7750A specifications Prepare Wiring Diagrams, General Considerations

Page 35

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

LINE VOLTAGE GREATER THAN 150 VAC

24 VAC

TRANSFORMER

1

EARTH

GROUND

1

W7750

• To minimize EMI noise, do not run Triac output wires

in the same conduit as the input wires or the LON-

WORKS Bus communications wiring.

• Unswitched 24 Vac power wiring can be run in the

same conduit as the LONWORKS Bus cable.

• Make earth ground connections with the shortest

possible wire run using 14 AWG (2.0 mm2) wire. A

good earth ground is essential for W7750 operation.

Ideally, connect the earth ground to the ground bus

at a motor control center or circuit breaker panel.

However, if the nearest ideal earth ground is inac-

cessible, consider an alternate source for earth

ground. Metal water pipe is generally a good ground,

but do not use sprinkler pipe if prohibited by local

EARTH

GROUND

1IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND 24 VAC COM

SIDE OF TRANSFORMER SECONDARY.

M10088A

Fig. 24. Transformer power wiring details for one Excel 10 used in UL 1995 equipment (U.S. only).

IMPORTANT

Notes on power wiring:

All field wiring must conform to local codes and ordi- nances or as specified on installation wiring dia- grams.

To maintain NEC Class 2 and UL ratings, the instal- lation must use transformers of 100 VA or less capacity.

For multiple controllers operating from a single trans- former, the same side of the transformer secondary must be connected to the same input terminal in each controller (21 on the W7750A and 24 on the W7750B,C) and the ground terminals must be con- nected to a verified earth ground for each controller in the group. See Fig. 23. (Controller configurations are not necessarily limited to three devices per trans- former.)

For the W7750B,C Controller (which has Triac out- puts), all output devices must be powered from the same transformer as the one powering the Excel 10 W7750 Controller.

Use the heaviest gauge wire available, up to 14 AWG (2.0 mm2) with a minimum of 18 AWG (1.0 mm2) for all power and earth ground connections.

codes. Attention must be given when duct work, con-

duit, or rebar are to be considered as ground

sources. It is the responsibility of the installer to

assure that these structures are tied back to a known

earth ground.

Step 4. Prepare Wiring Diagrams

General Considerations

The purpose of this step is to assist the application engineer in developing job drawings to meet job specifications. Wiring details are included for the W7750A,B,C Controllers and the T7770 and T7560A,B Wall Modules. The drawings detail I/O, power, and LONWORKS Bus communication wiring connections.

NOTE: For field wiring, when two or more wires, other than 14 AWG (2.0 mm2) are to be attached to the same connector block terminal, be sure to twist them together. Deviation from this rule can result in improper electrical contact. See Fig. 25.

The connector block terminals on the W7750 Controllers and on the T7770 Wall Modules accept 14 through 22 AWG (2.0 to

0.34mm2) wire. The connector block terminals on the T7560A,B Wall Modules accept 18 through 22 AWG (1.0 to

0.34mm2) wire. Table 9 lists wiring types, sizes, and length restrictions for Excel 10 products.

35

74-2958— 1

Image 35
Contents Excel 72-2958 General Considerations W7750 ControllersAppendices 74-2958 List of Figures74-2958 Setpoint ramping parameters with ramp rate calculationList of Tables Typical system overview Description of DevicesControl Provided Control ApplicationForm No Title Products CoveredOrganization of Manual Applicable LiteratureAgency Listings Product NamesAbbreviations and Definitions Controllers ConstructionDI-1 W7750ASpecial Note for the W7750B,C Unit Performance SpecificationsPower Memory Capacity Specified Space Temperature Sensing RangeCPU Excel 10 W7750C Constant Volume AHU Controller Jack Lonmark Functional Profile DIN rail adaptersAnalog Inputs Inputs/OutputsDigital Outputs Digital InputsTriac Outputs on the W7750B,C Models only T7770C Wall ModulesDuct Sensor T7770A1006T7560A,B construction in in. mm General ConfigurationsConfiguration Options Summary For W7750A,B,C Controllers Modulating HEATING/COOLING Control Allowable Heating and Cooling Equipment ConfigurationsStaged HEATING/COOLING Control Heat Pump ControlPneumatic Actuator Control Economizer ControlMIXED-OUTPUT-TYPE Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsSmoke Control Modes of OperationDirty Filter Monitor Indoor Air Quality IAQ OverrideAssigned OFF ModeDisabled NotStep No Description OverviewPlan the System Determine Other Bus Devices RequiredLonworks Bus Layout Lay Out Communications and Power WiringExcel VAV Cvahu DeviceVA Information Obtained from Power WiringPower Budget Calculation Example Line Loss VA Ratings For Transformer Sizing Device DescriptionML6161A/B Damper Actuator, 35 lb-in R8242A Contactor ML7984B PWM Valve ActuatorNema class 2 transformer voltage output limits Power wiring details for one Excel 10 per TransformerGeneral Considerations Prepare Wiring DiagramsW7750 Controllers Terminal Terminal Number Description Factory Default Digital OutputsConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Pneumatic transducer to W7750B,C Shown, see triangle note Lonworks Bus Termination ModuleBrown Orange Order Equipment Lonworks Bus termination wiring optionsSensor with Bypass/LED and Lonworks Jack T7770 and T7560 Wall ModulesHoneywell Logo T7770D1018 Echelon Based Components and Parts Accessories SensorsAccessories Cabling Configure ControllersTroubleshooting Troubleshooting Excel 10 Controllers and Wall ModulesResistance Value ohms AlarmsExcel 10 Alarms W7750 Controller Status LED Broadcasting the Service MessageSensor Calibration Appendix A. Using E-Vision to Commission a W7750 ControllerSetting the Pid Parameters T7770C,D Wall Module Bypass Pushbutton and Override LEDAppendix B. Sequences of Operation Common Operations IAQ Option Room Temperature Sensor RmTempHeating EconomizerBypassTime Bypass Mode StatusOvrd and StatusLedRemote Setpoint RmtStptPot Setpoint Limits LoSetptLim and HiSetptLimBypass Occupied Continuous Unoccupied ModeOccupancy Mode and Manual Override Arbitration Not AssignedSetpoint Ramping Recovery Ramping for Heat Pump SystemsTime Clock OccTimeClock Schedule Master SchedMasterDemand Limit Control DLC Window Sensor StatusWndwSmoke Control FAN OperationDirty Filter Monitor Temperature Control OperationsSee for a diagram of a typical W7750 Unit Three Stages Staged Cooling ControlONE Stage TWO StagesOutdoor AIR Lockout of HEATING/COOLING Cascade Control of Modulating COOLING/HEATINGSeries 60 Modulating Control Pulse Width Modulating PWM ControlDischarge AIR LOW Limit Control Economizer ENABLE/DISABLE ControlIndoor AIR Quality IAQ Override Freeze StatStatus Points Address Input Output Points AddressControl Parameters Address Energy Management Points AddressMappable User Addresses and Table Number Enthalpy Relative TemperatureAir Flow CO2 ConcentrationEnumerated values are shown Application reset therefore, these points canPlaced in manual mode through a menu Valid states and the correspondingComments DefaultInput/Output Points NvName Field NameOccsensor Unuseddi NciIoSelect DigitalIn1Occsensor Shcedmasterin 255 NciIoSelect DigitalIn2COOLSTAGE4 COOLSTAGE1COOLSTAGE2 COOLSTAGE3Siinvalid SixtyfiftyTrue PPM SiinvalidFalse OccSensr NvoIO EconEnSw NvoIO EconEnableInPosition when poor indoor air quality is detected StatusDI3 NvoIO UbDigitalInNvName Default CommentsControl Parameters MaxClRamp, OdTempMaxClRamp, OdEnthalpyEnableMaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/HrPPM GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees C Discharge air temperature cascade control loopGainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C Gain for the cooling control loopEnergy Management Points Network variable input fails Refer to WSHPEnable.valueNviFree1 Value Auxiliary functions. nviFree1 controls the FREE1OUT255 SrcTimeClkCt NvoTimeClk Value NviTimeClk ValueDestTimeClk NviTimeClk State Refer to nviTimeClk.valueStatus Points Bit Offset = InvalidSetPtAlrm Alarmbit1Bit Offset = SensorFailAlrm Bit Offset = FrostProtectAlrmUpdateallfields NoalarmNodedisabled SmokealarmCool DisabledmodeStartupwait HeatStatusManOcc NvoData1 NetManOcc StatusEconEn NvoData1 EconEnableAir flow switch is configured NciAux1SetPts.ubOdEnthalpyEnableS2For both heating or cooling HeatStgsOn NvoData1 HeatStagesOnAuxiliary heating stages are turned on CoolStgsOn NvoData1 CoolStagesOnMonitorSw NvoData1 MonSwitch Is 1, the algorithm controls as per the settings foundNciConfig.SmokeControl Controller mode is switched to FreezeprotectDischargetempfield BypasstimerfieldTempcontrolptfield SpacetempfieldUbinvalid Bit Offset = Temperature SetPtError NvoError Errorbit0 StatusError NvoError Errorbit0SpaceTempError NvoError Errorbit0Bit Offset = SpaceCO2Error NvoError Errorbit1 NvoError Errorbit1Bit Offset = RtnEnthalpyError NvoError Errorbit1 Are disabled as if the sensor was not configuredBit Offset = NvByPassError NvoError Errorbit3 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvTodEventError NvoError Errorbit3Calibration Points CfglocalCfgexternal CfgnulConfiguration Parameters False True UseRaTempCtl NciConfig DisMinHtTime NciConfig DisableHeatMinTimeDisMinClTime NciConfig DisableCoolMinTime CascCntrl NciConfig CascadeControlBypassonly Last NETOffset Absolutemiddle None NormalLonmark /Open System Points Hvacoff HvacautoHvacheat Hvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge HvacnulSrcRmTemp NvoSpaceTemp Degrees F 74-2958 100DestRmTemp NviSpaceTemp Degrees F SNVTtempp 14 toHvactest Hvacauto HvacnulHvacmrngwrmup Alarmnotifydisabled NvoStatus Unabletomeasure NvoStatus Electricalfault103 NvoStatus Inalarm 255 Not configured 74-2958Swon SrcEconEnCt NvoEcon Value On other nodes. If the economizer function is configured byCorresponding economizer function is not enabled because SrcEconEnable NvoEcon StateDirect Access And Special Points OFF Data Share Points Mapped points = number of mapped points per Excel Approximate Memory Size Estimating Procedure=using One-to-Many and not using points = including mapped points and others forSensor Use Sensor Resistance Versus Temperature Resistance OhmsResistance Sensors Sensor TypeAbove and Below Setpoint Resistance Ohms Offset Setpoint TemperatureDirect Setpoint Temperature T7770B,C 10K ohm setpoint potentiometer RelativeSensor Voltage Versus Humidity Relative Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Humidity Percentage 113 74-2958 Sensor Current Versus Enthalpy volts Enthalpy mAMAmAmAmA AmA mA mA T7242 or equivalent74-2958 114 Sensor Voltage Versus Input Voltage To A/D Voltage to A/D 50.0.13 Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc Inw