Honeywell W7750A specifications Lonmark /Open System Points

Page 98

74-2958— 1

98

Table 26. LONMARK® /Open System Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CoolOccSpt

nciTempSetPts

occupied_cool

Degrees F

 

23

P,

 

X

X

 

 

 

The Cooling Occupied Setpoint is used if no wall module setpoint pot is

 

(SNVT_temp_setpt)

 

50 to 95

 

 

M

 

 

 

 

 

 

configured as the standard Occupied Cooling Setpoint. Actual Cooling

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

Setpoint can be affected by various control parameters (such as DlcShed,

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

SrcRmtTempSpt, etc.). Actual room temperature Setpoint is reflected in

 

 

 

 

 

 

 

 

 

 

 

 

 

RmTempActSpt. Overridden by nviSetPt. Used to compute ZEB.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CoolStbySpt

nciTempSetPts

standby_cool

Degrees F

 

25

P,

 

X

X

 

 

 

When the controller is in the Standby mode (typically via an occupancy

 

(SNVT_temp_setpt)

 

50 to 95

 

 

M

 

 

 

 

 

 

sensor), the base Cooling Setpoint is determined by the Cooling Standby

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

Setpoint value. Also, when a wall module setpoint pot is configured, this

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

value serves as the upper limit on the user adjustable remote setpoint pot

 

 

 

 

 

 

 

 

 

 

 

 

 

(wall module).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CoolUnoccSpt

nciTempSetPts

unoccupied_cool

Degrees F

 

28

P,

 

X

X

 

 

 

When the controller is in the Unoccupied mode, the unit responds to a call

 

(SNVT_temp_setpt)

 

50 to 95

 

 

M

 

 

 

 

 

 

for cooling based on the Cooling Unoccupied Setpoint.

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HeatOccSpt

nciTempSetPts

occupied_heat

Degrees F

 

21

P,

 

X

X

 

 

 

When the controller is in the Occupied mode, if the space temperature

 

(SNVT_temp_setpt)

 

50 to 95

 

 

M

 

 

 

 

 

 

drops below the Heating Occupied Setpoint, the unit switches to the

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

Heating mode. This Setpoint is used only when there is no wall module

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

setpoint pot configured. Overridden by nviSetPt. Used to compute ZEB.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HeatStbySpt

nciTempSetPts

standby_heat

Degrees F

 

19

P,

 

X

X

 

 

 

When the controller is in the Standby mode (typically via an occupancy

 

(SNVT_temp_setpt)

 

50 to 95

 

 

M

 

 

 

 

 

 

sensor), the base Heating Setpoint is determined by the Heating Standby

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

Setpoint value. Also, when a wall module setpoint pot is configured, this

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

value serves as the lower limit on the user adjustable remote setpoint pot

 

 

 

 

 

 

 

 

 

 

 

 

 

(wall module).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HeatUnoccSpt

nciTempSetPts

unoccupied_heat

Degrees F

 

16

P,

 

X

X

 

 

 

When the controller is in the Unoccupied mode, the unit responds to a call

 

(SNVT_temp_setpt)

 

50 to 95

 

 

M

 

 

 

 

 

 

for heating based on the Heating Unoccupied Setpoint.

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviRequest

object_id

0 to 65535

 

1

 

 

 

 

 

 

 

Request provides the mechanism to request a particular status report (via

 

(SNVT_obj_request)

 

 

 

 

 

 

 

 

 

 

 

Status) for a particular object within this node. Object_id selects the object

 

 

 

 

 

 

 

 

 

 

 

 

 

being referenced by nviRequest. The only valid value of object_id is 1 for

 

 

 

 

 

 

 

 

 

 

 

 

 

the RTU object and all others are invalid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviRequest

object_request

RQ_NORMAL

0

RQ_NORMAL

 

 

 

 

 

 

 

When object_request is RQ_NORMAL or RQ_UPDATE_STATUS then the

 

(SNVT_obj_request)

 

RQ_DISABLED

1

 

 

 

 

 

 

 

 

status (via Status) will be reported for the object addressed by object_id.

 

 

 

RQ_UPDATE_STATUS

2

 

 

 

 

 

 

 

 

When object_request is RQ_REPORT_MASK then the status bits will be

 

 

 

RQ_SELF_TEST

3

 

 

 

 

 

 

 

 

reported that are supported in nvoStatus by the object addressed by

 

 

 

RQ_UPDATE_ALARM

4

 

 

 

 

 

 

 

 

object_id. Bits that are supported by the object are set to one. All other

 

 

 

RQ_REPORT_MASK

5

 

 

 

 

 

 

 

 

object_request items are not supported at this time and will return an

 

 

 

RQ_OVERRIDE

6

 

 

 

 

 

 

 

 

invalid_request (Status) in the object status.

 

 

 

RQ_ENABLE

7

 

 

 

 

 

 

 

 

 

 

 

 

RQ_RMV_OVERRIDE

8

 

 

 

 

 

 

 

 

 

 

 

 

RQ_CLEAR_STATUS

9

 

 

 

 

 

 

 

 

 

 

 

 

RQ_CLEAR_ALARM

10

 

 

 

 

 

 

 

 

 

 

 

 

RQ_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Image 98
Contents Excel 72-2958 General Considerations W7750 ControllersAppendices List of Figures 74-2958Setpoint ramping parameters with ramp rate calculation 74-2958List of Tables Description of Devices Typical system overviewControl Application Control ProvidedApplicable Literature Products CoveredOrganization of Manual Form No TitleProduct Names Agency ListingsAbbreviations and Definitions Construction ControllersW7750A DI-1Special Note for the W7750B,C Unit Performance SpecificationsPower Memory Capacity Specified Space Temperature Sensing RangeCPU Excel 10 W7750C Constant Volume AHU Controller Jack DIN rail adapters Lonmark Functional ProfileInputs/Outputs Analog InputsDigital Outputs Digital InputsTriac Outputs on the W7750B,C Models only T7770A1006 Wall ModulesDuct Sensor T7770CT7560A,B construction in in. mm Configurations GeneralConfiguration Options Summary For W7750A,B,C Controllers Heat Pump Control Allowable Heating and Cooling Equipment ConfigurationsStaged HEATING/COOLING Control Modulating HEATING/COOLING ControlEconomizer Control Pneumatic Actuator ControlWall Module Options Occupancy SensorWindow Open/Closed Digital Input MIXED-OUTPUT-TYPE ControlIndoor Air Quality IAQ Override Modes of OperationDirty Filter Monitor Smoke ControlNot OFF ModeDisabled AssignedDetermine Other Bus Devices Required OverviewPlan the System Step No DescriptionLay Out Communications and Power Wiring Lonworks Bus LayoutExcel VAV Cvahu DeviceVA Information Obtained from Power WiringPower Budget Calculation Example ML7984B PWM Valve Actuator VA Ratings For Transformer Sizing Device DescriptionML6161A/B Damper Actuator, 35 lb-in R8242A Contactor Line LossPower wiring details for one Excel 10 per Transformer Nema class 2 transformer voltage output limitsPrepare Wiring Diagrams General ConsiderationsW7750 Controllers Factory Default Digital Outputs Terminal Terminal Number DescriptionConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Lonworks Bus Termination Module Pneumatic transducer to W7750B,C Shown, see triangle noteBrown Orange Lonworks Bus termination wiring options Order EquipmentSensor with Bypass/LED and Lonworks Jack T7770 and T7560 Wall ModulesHoneywell Logo T7770D1018 Echelon Based Components and Parts Accessories SensorsAccessories Troubleshooting Excel 10 Controllers and Wall Modules Configure ControllersTroubleshooting CablingResistance Value ohms AlarmsExcel 10 Alarms Broadcasting the Service Message W7750 Controller Status LEDT7770C,D Wall Module Bypass Pushbutton and Override LED Appendix A. Using E-Vision to Commission a W7750 ControllerSetting the Pid Parameters Sensor CalibrationAppendix B. Sequences of Operation Common Operations Economizer Room Temperature Sensor RmTempHeating IAQ OptionSetpoint Limits LoSetptLim and HiSetptLim Bypass Mode StatusOvrd and StatusLedRemote Setpoint RmtStptPot BypassTimeNot Assigned Continuous Unoccupied ModeOccupancy Mode and Manual Override Arbitration Bypass OccupiedSchedule Master SchedMaster Recovery Ramping for Heat Pump SystemsTime Clock OccTimeClock Setpoint RampingFAN Operation Window Sensor StatusWndwSmoke Control Demand Limit Control DLCDirty Filter Monitor Temperature Control OperationsSee for a diagram of a typical W7750 Unit TWO Stages Staged Cooling ControlONE Stage Three StagesPulse Width Modulating PWM Control Cascade Control of Modulating COOLING/HEATINGSeries 60 Modulating Control Outdoor AIR Lockout of HEATING/COOLINGFreeze Stat Economizer ENABLE/DISABLE ControlIndoor AIR Quality IAQ Override Discharge AIR LOW Limit ControlEnergy Management Points Address Input Output Points AddressControl Parameters Address Status Points AddressMappable User Addresses and Table Number CO2 Concentration Relative TemperatureAir Flow EnthalpyValid states and the corresponding Application reset therefore, these points canPlaced in manual mode through a menu Enumerated values are shownNvName Field Name DefaultInput/Output Points Comments255 NciIoSelect DigitalIn2 NciIoSelect DigitalIn1Occsensor Shcedmasterin Occsensor UnuseddiCOOLSTAGE3 COOLSTAGE1COOLSTAGE2 COOLSTAGE4Sixtyfifty SiinvalidTrue PPM SiinvalidFalse StatusDI3 NvoIO UbDigitalIn EconEnSw NvoIO EconEnableInPosition when poor indoor air quality is detected OccSensr NvoIODefault Comments NvNameControl Parameters MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr OdEnthalpyEnableMaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr MaxClRamp, OdTempMaxClRamp,PPM Gain for the cooling control loop Discharge air temperature cascade control loopGainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees CEnergy Management Points Auxiliary functions. nviFree1 controls the FREE1OUT Refer to WSHPEnable.valueNviFree1 Value Network variable input failsRefer to nviTimeClk.value NviTimeClk ValueDestTimeClk NviTimeClk State 255 SrcTimeClkCt NvoTimeClk ValueStatus Points Bit Offset = FrostProtectAlrm Alarmbit1Bit Offset = SensorFailAlrm Bit Offset = InvalidSetPtAlrmSmokealarm NoalarmNodedisabled UpdateallfieldsHeat DisabledmodeStartupwait CoolNciAux1SetPts.ubOdEnthalpyEnableS2 StatusEconEn NvoData1 EconEnableAir flow switch is configured StatusManOcc NvoData1 NetManOccCoolStgsOn NvoData1 CoolStagesOn HeatStgsOn NvoData1 HeatStagesOnAuxiliary heating stages are turned on For both heating or coolingController mode is switched to Freezeprotect Is 1, the algorithm controls as per the settings foundNciConfig.SmokeControl MonitorSw NvoData1 MonSwitchSpacetempfield BypasstimerfieldTempcontrolptfield DischargetempfieldUbinvalid NvoError Errorbit0 StatusError NvoError Errorbit0SpaceTempError Bit Offset = Temperature SetPtError NvoError Errorbit0Are disabled as if the sensor was not configured NvoError Errorbit1Bit Offset = RtnEnthalpyError NvoError Errorbit1 Bit Offset = SpaceCO2Error NvoError Errorbit1Bit Offset = NvTodEventError NvoError Errorbit3 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvByPassError NvoError Errorbit3Cfgnul CfglocalCfgexternal Calibration PointsConfiguration Parameters False True CascCntrl NciConfig CascadeControl DisMinHtTime NciConfig DisableHeatMinTimeDisMinClTime NciConfig DisableCoolMinTime UseRaTempCtl NciConfigNone Normal Last NETOffset Absolutemiddle BypassonlyLonmark /Open System Points Hvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge Hvacnul HvacautoHvacheat HvacoffSNVTtempp 14 to 74-2958 100DestRmTemp NviSpaceTemp Degrees F SrcRmTemp NvoSpaceTemp Degrees FHvactest Hvacauto HvacnulHvacmrngwrmup Alarmnotifydisabled 255 Not configured 74-2958 NvoStatus Electricalfault103 NvoStatus Inalarm NvoStatus UnabletomeasureSwon SrcEconEnable NvoEcon State On other nodes. If the economizer function is configured byCorresponding economizer function is not enabled because SrcEconEnCt NvoEcon ValueDirect Access And Special Points OFF Data Share Points = including mapped points and others for Approximate Memory Size Estimating Procedure=using One-to-Many and not using points Mapped points = number of mapped points per ExcelSensor Type Sensor Resistance Versus Temperature Resistance OhmsResistance Sensors Sensor UseT7770B,C 10K ohm setpoint potentiometer Relative Offset Setpoint TemperatureDirect Setpoint Temperature Above and Below Setpoint Resistance OhmsSensor Voltage Versus Humidity Relative Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Humidity Percentage Sensor Current Versus Enthalpy volts Enthalpy mA 113 74-2958MAmAmAmA AmA mA mA T7242 or equivalent74-2958 114 Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Inw Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc 50.0.13