Table 20. Input/Output Points. (Continued)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Value | Digital |
|
|
| Direct | Hardware | Manual |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
User Address | NvName | Field Name | (Metric) or States plus Range | ofState | Stateor | Default | (M, P,S) | Share | Map | Access | Config. | Config. | Test | Comments | |
|
|
| Engineering Units: English |
|
|
|
|
|
|
|
|
|
|
| |
| nciIoSelect | FiftySixtyHz | SIXTYFIFTY |
| 01 |
| SIXTY | P |
|
| X |
|
|
| FiftySixtyHz specifies the frequency of the main power input for the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| controller. Correctly selecting the FiftySixtyHz decreases the noise picked |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| up by analog switch wiring from the power mains. When FiftySixtyHz is 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (SIXTY is the default), the mains frequency is sixty Hz and when |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| FiftySixtyHz is 1 (FIFTY), the mains frequency is fifty Hz. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| nciIoSelect | SpaceSensorType | T7770 |
| 0 |
| T7770 |
|
|
|
| X |
|
| SpaceSensorType specifies the type of space temperature sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| connected to the node. When SpaceSensorType is 0, a T7770 sensor is |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| connected to the sensor terminals. No other options are currently valid. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RmtStptPot | nvoIO | siSetPointTempS7 | Degrees F |
|
|
| SI_INVALID | M, |
| X | X |
| X |
| SetPointTemp is the wall module setpoint temperature. When |
|
|
|
|
|
|
| S |
|
|
|
|
|
| nciConfig.SetPointTemp is ABSOLUTE_COOL or ABSOLUTE_MIDDLE, | |
|
|
| Degrees C |
|
|
|
|
|
|
|
|
|
|
| the reported value is the absolute setpoint temperature. When |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Config.SetPntKnob is OFFSET, the reported value is the offset (from the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| current active TempSetPts) temperature. If the input is not configured or |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| has failed, the value is SI_INVALID. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RmTempSensr | nvoIO | siSpaceTempS7 | Degrees F |
|
|
| SI_INVALID | M, |
|
|
|
|
|
| SpaceTemp is the measured space temperature. If the sensor is not |
|
|
| 40 to 100 |
|
|
|
| S |
|
|
|
|
|
| configured or has failed, the value is SI_INVALID.NOTE: The reported |
|
|
| Degrees C |
|
|
|
|
|
|
|
|
|
|
| temperatures includes the offset correction provided by |
|
|
| (4 to 38) |
|
|
|
|
|
|
|
|
|
|
| Config.ResistiveOffsetCal. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DaTempSensr | nvoIO | siDischargeTempS7 | Degrees F | Degrees C |
|
| SI_INVALID |
|
|
|
|
|
|
| DischargeTemp is the measured discharge air temperature. If the sensor is |
|
|
| 30 to 122 |
|
|
|
|
|
|
|
|
|
| not configured or has failed, the value is SI_INVALID. Refer to the note on | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SpaceTemp. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RaTempSensr | nvoIO | siReturnTempS7 | Degrees F | Degrees C |
|
| SI_INVALID |
|
|
|
|
|
|
| ReturnTemp is the measured return air temperature. If the sensor is not |
|
|
| 30 to 122 |
|
|
|
|
|
|
|
|
|
| configured or has failed, the value is SI_INVALID. Refer to the note on | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SpaceTemp. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RaHumSensr | nvoIO | ReturnHumidity | Percentage |
|
|
| SI_INVALID |
|
|
|
|
|
|
| ReturnHumidity is the measured return air humidity. If the sensor is not |
|
|
| 10 to 90 |
|
|
|
|
|
|
|
|
|
|
| configured or has failed, the value is UB_INVALID.NOTE: The reported |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| temperatures includes the offset correction provided by |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Config.VoltageOffsetCal. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RaEnthSensr | nvoIO | siReturnEnthalpyS7 | mA |
|
|
| SI_INVALID |
|
|
|
|
|
|
| ReturnEnthalpy is the measured return air enthalpy. If the sensor is not |
|
|
| 4 to 20 |
|
|
|
|
|
|
|
|
|
|
| configured or has failed, the value is SI_INVALID. Since the C7400 reports |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| comfort due to enthalpy (btu/lb) in milliamps, enthalpy is also reported in |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| milliamps. Refer to the NOTE on ReturnHumidity. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OaTempSensr | nvoIO | siOutdoorTempS7 | Degrees F | Degrees C |
|
| SI_INVALID | M, |
|
|
|
|
|
| OutdoorTemp is the measured outdoor air temperature. If the sensor is not |
|
|
|
|
|
| S |
|
|
|
|
|
| configured or has failed, the value is SI_INVALID. Refer to the NOTE on | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ReturnHumidity. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OaHumSensr | nvoIO | OutdoorHumidity | Percentage |
|
|
| SI_INVALID | M, |
|
|
|
|
|
| OutdoorHumidity is the measured outdoor air humidity. If the sensor is not |
|
|
| 10 to 90 |
|
|
|
| S |
|
|
|
|
|
| configured or has failed, the value is UB_INVALID. Refer to the NOTE on |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ReturnHumidity. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OaEnthSensr | nvoIO | siOutdoorEnthalpyS7 | mA |
|
|
| SI_INVALID | M, |
|
|
|
|
|
| OutdoorEnthalpy is the measured outdoor air enthalpy. If the sensor is not |
|
|
| 4 to 20 |
|
|
|
| S |
|
|
|
|
|
| configured or has failed, the value is SI_INVALID. Since the C7400 reports |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| comfort due to enthalpy (btu/lb) in milliamps, enthalpy is also reported in |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| milliamps. Refer to the NOTE on ReturnHumidity. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FltrPressSensr | nvoIO | siFilterPressureS10 | inw (kPa) |
|
|
| SI_INVALID |
|
|
|
|
|
|
| FilterPressure is the measured differential pressure across the return air |
|
|
| 0 to 5 (0 to 1.25) |
|
|
|
|
|
|
|
|
|
|
| filter. If the sensor is not configured or has failed, the value is the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SI_INVALID. Refer to the NOTE on ReturnHumidity. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER