Honeywell W7750A Not, Assigned, Start-Up, Wait, Cooling, Heating, Emergency, OFF Mode, Disabled

Page 28

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Table 5. Modes Of Operation For The Excel 10 W7750 Controller (Continued).

 

 

 

Mode

Description

Events causing a controller to switch to this mode

 

 

 

UNOCCUPIED

Controller occupancy mode was

Network input (DestManOcc) containing a time-of-day schedule

 

overridden to Unoccupied mode

override signal of UNOCCUPIED from the Excel 10 Zone Manager or

 

 

other LONWORKS Bus device.

 

 

 

BYPASS

Controller occupancy mode was

DI (Bypass) was pressed, and the Bypass duration timer has not yet

 

overridden to Bypass the current

expired, or the network input DestManOcc has a value of BYPASS.

 

Unoccupied mode

 

 

 

 

NOT

No Bypass action

No Override input received.

ASSIGNED

 

 

 

 

 

Operational Modes (User Address: StatusMode)

 

 

 

 

START-UP

On power-up, provides a staggered

This mode occurs on controller power-up, and after downloading to the

AND WAIT

start sequence to evenly apply the load

controller from the configuration tool. Temperature control loops are

 

to the electrical system.

disabled.

 

 

 

COOLING

The Excel 10 is controlling the Cooling

Space temperature has risen above the current cooling setpoint, or the

 

mode.

network input (DestHvacMode) is COOL.

 

 

 

HEATING

The Excel 10 is controlling the Heating

Space temperature has fallen below the current heating setpoint, or the

 

mode.

network input (DestHvacMode) is HEAT.

 

 

 

EMERGENCY

Compressors are disabled and only

The network input (DestManHvacMode) is EMERG_HEAT.

HEAT

Auxiliary Heat stages are allowed to

 

 

operate.

 

 

 

 

OFF MODE

The heat/cool control is turned off

Network input (DestManMode) containing AHU operational mode

 

immediately. The node is not running its

information from C-Bus has value of MORNING WARM-UP.

 

normal temperature control.

 

 

 

 

DISABLED

The heat/cool control and frost

MODE

protection are turned off immediately.

 

 

The node is not running its normal

 

 

temperature control.

 

 

 

 

SMOKE

The node has entered a smoke

Network input (DestEmergCmd) containing smoke control signal from

EMERGENCY

emergency. The fan and dampers are

another LONWORKS Bus device has value of SMOKE_EMERG.

 

then set to the conditions configured by

 

 

SmkCtlMode. The control remains in

 

 

SMOKE_ EMERGENCY until power is

 

 

cycled or the node receives

 

 

DestEmergCmd set to

 

 

EMERG_NORMAL.

 

 

 

 

FREEZE

The temperature control is set to HEAT

The Window digital input detects an open window.

PROTECT

with the setpoint set to the frost limit

 

 

setpoint 46.4°F (8°C).

 

 

 

 

MANUAL

The physical outputs are being

Typically this is done by the user through E-Vision or XBS by setting

POSITION

controlled manually. The temperature

the point DestManMode to MANUAL mode.

 

control loop is turned off.

 

 

 

 

FAN ONLY

Control algorithm is disabled, except

The space temperature sensor has failed, or the network input

 

that the fan is turned on.

(DestHvacMode) is FAN ONLY.

 

 

 

DISABLED

Control algorithm is shut off.

Network input (DestManMode) containing AHU operational mode

 

 

information from an operator or the network that has a value of

 

 

DISABLED.

 

 

 

NOTE: During all modes all digital and analog physical inputs are periodically read, the diagnostic output network variables can be polled, the input network variables are received, and the output network variables are sent periodically.

74-2958— 1

28

Image 28
Contents Excel Appendices General Considerations W7750 Controllers72-2958 List of Figures 74-2958Setpoint ramping parameters with ramp rate calculation 74-2958List of Tables Description of Devices Typical system overviewControl Application Control ProvidedProducts Covered Organization of ManualApplicable Literature Form No TitleProduct Names Agency ListingsAbbreviations and Definitions Construction ControllersW7750A DI-1Power Performance SpecificationsSpecial Note for the W7750B,C Unit CPU Specified Space Temperature Sensing RangeMemory Capacity Excel 10 W7750C Constant Volume AHU Controller Jack DIN rail adapters Lonmark Functional ProfileInputs/Outputs Analog InputsTriac Outputs on the W7750B,C Models only Digital InputsDigital Outputs Wall Modules Duct SensorT7770A1006 T7770CT7560A,B construction in in. mm Configurations GeneralConfiguration Options Summary For W7750A,B,C Controllers Allowable Heating and Cooling Equipment Configurations Staged HEATING/COOLING ControlHeat Pump Control Modulating HEATING/COOLING ControlEconomizer Control Pneumatic Actuator ControlOccupancy Sensor Window Open/Closed Digital InputWall Module Options MIXED-OUTPUT-TYPE ControlModes of Operation Dirty Filter MonitorIndoor Air Quality IAQ Override Smoke ControlOFF Mode DisabledNot AssignedOverview Plan the SystemDetermine Other Bus Devices Required Step No DescriptionLay Out Communications and Power Wiring Lonworks Bus LayoutExcel VAV Cvahu Power Budget Calculation Example Power WiringDeviceVA Information Obtained from VA Ratings For Transformer Sizing Device Description ML6161A/B Damper Actuator, 35 lb-in R8242A ContactorML7984B PWM Valve Actuator Line LossPower wiring details for one Excel 10 per Transformer Nema class 2 transformer voltage output limitsPrepare Wiring Diagrams General ConsiderationsW7750 Controllers Factory Default Digital Outputs Terminal Terminal Number DescriptionConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Lonworks Bus Termination Module Pneumatic transducer to W7750B,C Shown, see triangle noteBrown Orange Lonworks Bus termination wiring options Order EquipmentHoneywell Logo T7770D1018 T7770 and T7560 Wall ModulesSensor with Bypass/LED and Lonworks Jack Accessories Accessories SensorsEchelon Based Components and Parts Configure Controllers TroubleshootingTroubleshooting Excel 10 Controllers and Wall Modules CablingExcel 10 Alarms AlarmsResistance Value ohms Broadcasting the Service Message W7750 Controller Status LEDAppendix A. Using E-Vision to Commission a W7750 Controller Setting the Pid ParametersT7770C,D Wall Module Bypass Pushbutton and Override LED Sensor CalibrationAppendix B. Sequences of Operation Common Operations Room Temperature Sensor RmTemp HeatingEconomizer IAQ OptionBypass Mode StatusOvrd and StatusLed Remote Setpoint RmtStptPotSetpoint Limits LoSetptLim and HiSetptLim BypassTimeContinuous Unoccupied Mode Occupancy Mode and Manual Override ArbitrationNot Assigned Bypass OccupiedRecovery Ramping for Heat Pump Systems Time Clock OccTimeClockSchedule Master SchedMaster Setpoint RampingWindow Sensor StatusWndw Smoke ControlFAN Operation Demand Limit Control DLCSee for a diagram of a typical W7750 Unit Temperature Control OperationsDirty Filter Monitor Staged Cooling Control ONE StageTWO Stages Three StagesCascade Control of Modulating COOLING/HEATING Series 60 Modulating ControlPulse Width Modulating PWM Control Outdoor AIR Lockout of HEATING/COOLINGEconomizer ENABLE/DISABLE Control Indoor AIR Quality IAQ OverrideFreeze Stat Discharge AIR LOW Limit ControlInput Output Points Address Control Parameters AddressEnergy Management Points Address Status Points AddressMappable User Addresses and Table Number Relative Temperature Air FlowCO2 Concentration EnthalpyApplication reset therefore, these points can Placed in manual mode through a menuValid states and the corresponding Enumerated values are shownDefault Input/Output PointsNvName Field Name CommentsNciIoSelect DigitalIn1 Occsensor Shcedmasterin255 NciIoSelect DigitalIn2 Occsensor UnuseddiCOOLSTAGE1 COOLSTAGE2COOLSTAGE3 COOLSTAGE4Sixtyfifty SiinvalidFalse PPM SiinvalidTrue EconEnSw NvoIO EconEnableIn Position when poor indoor air quality is detectedStatusDI3 NvoIO UbDigitalIn OccSensr NvoIODefault Comments NvNameControl Parameters OdEnthalpyEnable MaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/HrMinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr MaxClRamp, OdTempMaxClRamp,PPM Discharge air temperature cascade control loop GainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees CGain for the cooling control loop GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees CEnergy Management Points Refer to WSHPEnable.value NviFree1 ValueAuxiliary functions. nviFree1 controls the FREE1OUT Network variable input failsNviTimeClk Value DestTimeClk NviTimeClk StateRefer to nviTimeClk.value 255 SrcTimeClkCt NvoTimeClk ValueStatus Points Alarmbit1 Bit Offset = SensorFailAlrmBit Offset = FrostProtectAlrm Bit Offset = InvalidSetPtAlrmNoalarm NodedisabledSmokealarm UpdateallfieldsDisabledmode StartupwaitHeat CoolStatusEconEn NvoData1 EconEnable Air flow switch is configuredNciAux1SetPts.ubOdEnthalpyEnableS2 StatusManOcc NvoData1 NetManOccHeatStgsOn NvoData1 HeatStagesOn Auxiliary heating stages are turned onCoolStgsOn NvoData1 CoolStagesOn For both heating or coolingIs 1, the algorithm controls as per the settings found NciConfig.SmokeControlController mode is switched to Freezeprotect MonitorSw NvoData1 MonSwitchBypasstimerfield TempcontrolptfieldSpacetempfield DischargetempfieldUbinvalid StatusError NvoError Errorbit0 SpaceTempErrorNvoError Errorbit0 Bit Offset = Temperature SetPtError NvoError Errorbit0NvoError Errorbit1 Bit Offset = RtnEnthalpyError NvoError Errorbit1Are disabled as if the sensor was not configured Bit Offset = SpaceCO2Error NvoError Errorbit1Bit Offset = NvWindowError NvoError Errorbit2 Bit Offset = NvDlcShedError NvoError Errorbit2Bit Offset = NvTodEventError NvoError Errorbit3 Bit Offset = NvByPassError NvoError Errorbit3Cfglocal CfgexternalCfgnul Calibration PointsConfiguration Parameters False True DisMinHtTime NciConfig DisableHeatMinTime DisMinClTime NciConfig DisableCoolMinTimeCascCntrl NciConfig CascadeControl UseRaTempCtl NciConfigLast NET Offset AbsolutemiddleNone Normal BypassonlyLonmark /Open System Points Hvacauto HvacheatHvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge Hvacnul Hvacoff74-2958 100 DestRmTemp NviSpaceTemp Degrees FSNVTtempp 14 to SrcRmTemp NvoSpaceTemp Degrees FHvacmrngwrmup Hvacauto HvacnulHvactest Alarmnotifydisabled NvoStatus Electricalfault 103 NvoStatus Inalarm255 Not configured 74-2958 NvoStatus UnabletomeasureSwon On other nodes. If the economizer function is configured by Corresponding economizer function is not enabled becauseSrcEconEnable NvoEcon State SrcEconEnCt NvoEcon ValueDirect Access And Special Points OFF Data Share Points Approximate Memory Size Estimating Procedure =using One-to-Many and not using points= including mapped points and others for Mapped points = number of mapped points per ExcelSensor Resistance Versus Temperature Resistance Ohms Resistance SensorsSensor Type Sensor UseOffset Setpoint Temperature Direct Setpoint TemperatureT7770B,C 10K ohm setpoint potentiometer Relative Above and Below Setpoint Resistance OhmsSensor Voltage Versus Humidity Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Relative Humidity Percentage Sensor Current Versus Enthalpy volts Enthalpy mA 113 74-295874-2958 114 T7242 or equivalentMAmAmAmA AmA mA mA Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Sensor Voltage Vdc Versus Pressure Inw Pressure Inw kPa Sensor Voltage VdcInw 50.0.13