EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

DIRTY FILTER MONITOR

The air filter in the air handler can be monitored by the W7750 and an alarm issued when the filter media needs replacement. The two methods of monitoring the filter are:

1.A differential pressure switch whose contacts are con- nected to a digital input on the W7750A or W7750B,C; and

2.A 2-to-10V differential pressure sensor wired to a current input on the W7750B,C. If the analog input sensor is used, its measured value 0 to 5 inw

(0 to 1.25 kPa) is compared to a user-selectable setpoint (FltrPressStPt— valid range: 0 to 5 inw

(0 to 1.25 kPa)), and the Dirty Filter alarm is issued when the pressure drop across the filter exceeds the setpoint.

START-UP

START_UP_WAIT is the first mode after application restart or power-up.During START_UP_WAIT, the analog and digital inputs are being read for the first time, no control algorithms are active, and the physical outputs (fan and heat/cooling stages) are in the de-energized position. The node remains in

OA TEMP

the START_UP_WAIT mode for a pseudo-random period (depending on neuron_id) between 12 and 22 seconds and then transitions to one of the operating modes, depending on the inputs that are read from the physical and network inputs. The pseudo random period prevents multiple controllers from simultaneously starting major electrical loads when power is restored to a building.

NOTES: After a controller download via Care/E-Vision, the delayed reset time is bypassed and the controller starts after a 40-second initialization.

Not all network inputs can be received during the START_UP_WAIT period because many network variables are updated at a slower rate; therefore some control decisions can be considered tempo- rarily inappropriate.

Temperature Control Operations

See Fig. 49 for a diagram of a typical W7750 Unit.

OUTDOOR AIR

 

COOL

HEAT

FILTER

COIL

COIL

 

FAN

 

 

-

+

M

 

 

EXCEL 10

W7750

CVAHU

DA TEMP

RA TEMP

OCCUPANCY

SENSOR

RETURN

T7770 OR T7560A,B

AIR

 

 

WINDOW CONTACT

Fig. 49. Schematic diagram for a typical W7750B Unit.

ROOF

CEILING

DISCHARGE

AIR

M17488

59

74-2958— 1

Image 59
Contents Excel 72-2958 General Considerations W7750 ControllersAppendices 74-2958 List of Figures74-2958 Setpoint ramping parameters with ramp rate calculationList of Tables Typical system overview Description of DevicesControl Provided Control ApplicationForm No Title Products CoveredOrganization of Manual Applicable LiteratureAgency Listings Product NamesAbbreviations and Definitions Controllers ConstructionDI-1 W7750ASpecial Note for the W7750B,C Unit Performance SpecificationsPower Memory Capacity Specified Space Temperature Sensing RangeCPU Excel 10 W7750C Constant Volume AHU Controller Jack Lonmark Functional Profile DIN rail adaptersAnalog Inputs Inputs/OutputsDigital Outputs Digital InputsTriac Outputs on the W7750B,C Models only T7770C Wall ModulesDuct Sensor T7770A1006T7560A,B construction in in. mm General ConfigurationsConfiguration Options Summary For W7750A,B,C Controllers Modulating HEATING/COOLING Control Allowable Heating and Cooling Equipment ConfigurationsStaged HEATING/COOLING Control Heat Pump ControlPneumatic Actuator Control Economizer ControlMIXED-OUTPUT-TYPE Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsSmoke Control Modes of OperationDirty Filter Monitor Indoor Air Quality IAQ OverrideAssigned OFF ModeDisabled NotStep No Description OverviewPlan the System Determine Other Bus Devices RequiredLonworks Bus Layout Lay Out Communications and Power WiringExcel VAV Cvahu DeviceVA Information Obtained from Power WiringPower Budget Calculation Example Line Loss VA Ratings For Transformer Sizing Device DescriptionML6161A/B Damper Actuator, 35 lb-in R8242A Contactor ML7984B PWM Valve ActuatorNema class 2 transformer voltage output limits Power wiring details for one Excel 10 per TransformerGeneral Considerations Prepare Wiring DiagramsW7750 Controllers Terminal Terminal Number Description Factory Default Digital OutputsConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Pneumatic transducer to W7750B,C Shown, see triangle note Lonworks Bus Termination ModuleBrown Orange Order Equipment Lonworks Bus termination wiring optionsSensor with Bypass/LED and Lonworks Jack T7770 and T7560 Wall ModulesHoneywell Logo T7770D1018 Echelon Based Components and Parts Accessories SensorsAccessories Cabling Configure ControllersTroubleshooting Troubleshooting Excel 10 Controllers and Wall ModulesResistance Value ohms AlarmsExcel 10 Alarms W7750 Controller Status LED Broadcasting the Service MessageSensor Calibration Appendix A. Using E-Vision to Commission a W7750 ControllerSetting the Pid Parameters T7770C,D Wall Module Bypass Pushbutton and Override LEDAppendix B. Sequences of Operation Common Operations IAQ Option Room Temperature Sensor RmTempHeating EconomizerBypassTime Bypass Mode StatusOvrd and StatusLedRemote Setpoint RmtStptPot Setpoint Limits LoSetptLim and HiSetptLimBypass Occupied Continuous Unoccupied ModeOccupancy Mode and Manual Override Arbitration Not AssignedSetpoint Ramping Recovery Ramping for Heat Pump SystemsTime Clock OccTimeClock Schedule Master SchedMasterDemand Limit Control DLC Window Sensor StatusWndwSmoke Control FAN OperationDirty Filter Monitor Temperature Control OperationsSee for a diagram of a typical W7750 Unit Three Stages Staged Cooling ControlONE Stage TWO StagesOutdoor AIR Lockout of HEATING/COOLING Cascade Control of Modulating COOLING/HEATINGSeries 60 Modulating Control Pulse Width Modulating PWM ControlDischarge AIR LOW Limit Control Economizer ENABLE/DISABLE ControlIndoor AIR Quality IAQ Override Freeze StatStatus Points Address Input Output Points AddressControl Parameters Address Energy Management Points AddressMappable User Addresses and Table Number Enthalpy Relative TemperatureAir Flow CO2 ConcentrationEnumerated values are shown Application reset therefore, these points canPlaced in manual mode through a menu Valid states and the correspondingComments DefaultInput/Output Points NvName Field NameOccsensor Unuseddi NciIoSelect DigitalIn1Occsensor Shcedmasterin 255 NciIoSelect DigitalIn2COOLSTAGE4 COOLSTAGE1COOLSTAGE2 COOLSTAGE3Siinvalid SixtyfiftyTrue PPM SiinvalidFalse OccSensr NvoIO EconEnSw NvoIO EconEnableInPosition when poor indoor air quality is detected StatusDI3 NvoIO UbDigitalInNvName Default CommentsControl Parameters MaxClRamp, OdTempMaxClRamp, OdEnthalpyEnableMaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/HrPPM GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees C Discharge air temperature cascade control loopGainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C Gain for the cooling control loopEnergy Management Points Network variable input fails Refer to WSHPEnable.valueNviFree1 Value Auxiliary functions. nviFree1 controls the FREE1OUT255 SrcTimeClkCt NvoTimeClk Value NviTimeClk ValueDestTimeClk NviTimeClk State Refer to nviTimeClk.valueStatus Points Bit Offset = InvalidSetPtAlrm Alarmbit1Bit Offset = SensorFailAlrm Bit Offset = FrostProtectAlrmUpdateallfields NoalarmNodedisabled SmokealarmCool DisabledmodeStartupwait HeatStatusManOcc NvoData1 NetManOcc StatusEconEn NvoData1 EconEnableAir flow switch is configured NciAux1SetPts.ubOdEnthalpyEnableS2For both heating or cooling HeatStgsOn NvoData1 HeatStagesOnAuxiliary heating stages are turned on CoolStgsOn NvoData1 CoolStagesOnMonitorSw NvoData1 MonSwitch Is 1, the algorithm controls as per the settings foundNciConfig.SmokeControl Controller mode is switched to FreezeprotectDischargetempfield BypasstimerfieldTempcontrolptfield SpacetempfieldUbinvalid Bit Offset = Temperature SetPtError NvoError Errorbit0 StatusError NvoError Errorbit0SpaceTempError NvoError Errorbit0Bit Offset = SpaceCO2Error NvoError Errorbit1 NvoError Errorbit1Bit Offset = RtnEnthalpyError NvoError Errorbit1 Are disabled as if the sensor was not configuredBit Offset = NvByPassError NvoError Errorbit3 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvTodEventError NvoError Errorbit3Calibration Points CfglocalCfgexternal CfgnulConfiguration Parameters False True UseRaTempCtl NciConfig DisMinHtTime NciConfig DisableHeatMinTimeDisMinClTime NciConfig DisableCoolMinTime CascCntrl NciConfig CascadeControlBypassonly Last NETOffset Absolutemiddle None NormalLonmark /Open System Points Hvacoff HvacautoHvacheat Hvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge HvacnulSrcRmTemp NvoSpaceTemp Degrees F 74-2958 100DestRmTemp NviSpaceTemp Degrees F SNVTtempp 14 toHvactest Hvacauto HvacnulHvacmrngwrmup Alarmnotifydisabled NvoStatus Unabletomeasure NvoStatus Electricalfault103 NvoStatus Inalarm 255 Not configured 74-2958Swon SrcEconEnCt NvoEcon Value On other nodes. If the economizer function is configured byCorresponding economizer function is not enabled because SrcEconEnable NvoEcon StateDirect Access And Special Points OFF Data Share Points Mapped points = number of mapped points per Excel Approximate Memory Size Estimating Procedure=using One-to-Many and not using points = including mapped points and others forSensor Use Sensor Resistance Versus Temperature Resistance OhmsResistance Sensors Sensor TypeAbove and Below Setpoint Resistance Ohms Offset Setpoint TemperatureDirect Setpoint Temperature T7770B,C 10K ohm setpoint potentiometer RelativeSensor Voltage Versus Humidity Relative Humidity Percentage Voltage/Current SensorsSensor Voltage Versus Humidity Humidity Percentage 113 74-2958 Sensor Current Versus Enthalpy volts Enthalpy mAMAmAmAmA AmA mA mA T7242 or equivalent74-2958 114 Sensor Voltage Versus Input Voltage To A/D Voltage to A/D 50.0.13 Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc Inw