Honeywell W7750A Heating, Economizer, IAQ Option, Coil Freeze, Stat Option, Filter Monitor

Page 54

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Table 15. Configuration Options Summary For W7750A,B,C Controllers.

 

 

 

 

 

 

 

Possible Configurations for the

 

 

Option

 

W7750A Model

 

Possible Configurations for the W7750B,C Models

 

 

 

 

 

Type of

1.

One stage.

1.

One stage.

Heating

 

 

 

 

2.

Two stages.

2.

Two stages.

 

 

 

 

 

 

3.

Three stages.

3.

Three stages.

 

 

 

 

 

 

4.

Four stages.

4.

Four stages.

 

 

 

 

 

 

5.

None.

5.

Series 60 Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

6.

Pulse Width Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

7.

None.

 

 

 

 

 

Type of

1.

One stage.

1.

One stage.

Cooling

 

 

 

 

2.

Two stages.

2.

Two stages.

 

 

 

 

 

 

3.

Three stages.

3.

Three stages.

 

 

 

 

 

 

4.

Four stages.

4.

Four stages.

 

 

 

 

 

 

5.

None.

5.

Series 60 Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

6.

Pulse Width Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

7.

None.

 

 

 

 

 

Type of

1.

Digital Output Enable/Disable

1.

Digital Output Enable/Disable signal for controlling an external

Economizer

 

signal for controlling an external

 

economizer package.

 

 

economizer package.

 

 

 

 

 

 

 

 

2.

Series 60 Modulating electric

2.

Series 60 Modulating electric damper motor, or pneumatic via

 

 

damper motor, or pneumatic via

 

transducer.

 

 

transducer.

 

 

 

 

 

 

 

 

3.

None.

3.

Pulse Width Modulating electric damper motor, or pneumatic via

 

 

 

 

transducer.

 

 

 

 

 

 

 

 

4.

None.

 

 

 

 

 

IAQ Option

1.

None.

1.

None.

 

 

 

 

 

 

2.

Local IAQ Digital Input— directly

2.

Local IAQ Digital Input— directly wired to the controller. (Contacts

 

 

wired to the controller. (Contacts

 

closed means poor IAQ is detected.)

 

 

closed means poor IAQ is

 

 

 

 

detected.)

 

 

 

 

 

 

 

 

3.

Network (IAQ Override signal

3.

Network (IAQ Override signal received via the LONWORKS Bus).

 

 

received via the LONWORKS Bus).

 

 

 

 

 

 

 

 

 

4. Local CO2 Analog Input— directly wired to the controller. (The sensor

 

 

 

 

must be a 0 to 10V device representing 0 to 2000 PPM CO2.)

Coil Freeze

1.

None.

1.

None.

Stat Option

 

 

 

 

2.

Local Coil Freeze Stat Digital

2.

Local Coil Freeze Stat Digital Input— directly wired to the controller.

 

Input— directly wired to the controller.

(Contacts closed means that coil freeze condition is sensed.)

 

(Contacts closed means that coil

 

 

 

freeze condition is sensed.)

 

 

 

 

 

 

 

Filter Monitor

1.

None.

1.

None.

Option

 

 

 

 

2.

Local Dirty Filter Digital

2.

Local Dirty Filter Digital Input— directly wired to the controller.

 

 

Input— directly wired to the

 

(Contacts closed means that the filter is dirty.)

 

 

controller. (Contacts closed means

 

 

 

 

that the filter is dirty.)

 

 

 

 

 

 

 

 

 

 

3.

Local Analog Input for Differential Pressure across the Filter (directly

 

 

 

 

wired to the controller). The sensor must be a 2 to 10V device

 

 

 

 

representing 0 to 5 inw (1.25 kPa).

 

 

 

 

 

ROOM TEMPERATURE SENSOR (RmTemp)

This is the room space temperature sensor. This sensor is the T7770 or the T7560A,B Wall Module. When it is configured, it provides the temperature input for the W7750 temperature control loop. If it is not configured, it is required that a room temperature sensor value be transmitted from another

LONWORKS Bus device. If no valid room temperature value is available to the W7750 Controller, the temperature control algorithm in the controller is disabled, causing the heating, cooling, and economizer control outputs to be turned off. If the W7750 Controller is configured for Continuous Fan (rather

74-2958— 1

54

Image 54
Contents Excel General Considerations W7750 Controllers Appendices72-2958 List of Figures 74-2958Setpoint ramping parameters with ramp rate calculation 74-2958List of Tables Description of Devices Typical system overviewControl Application Control ProvidedApplicable Literature Products CoveredOrganization of Manual Form No TitleProduct Names Agency ListingsAbbreviations and Definitions Construction ControllersW7750A DI-1Performance Specifications PowerSpecial Note for the W7750B,C Unit Specified Space Temperature Sensing Range CPUMemory Capacity Excel 10 W7750C Constant Volume AHU Controller Jack DIN rail adapters Lonmark Functional ProfileInputs/Outputs Analog InputsDigital Inputs Triac Outputs on the W7750B,C Models onlyDigital Outputs T7770A1006 Wall ModulesDuct Sensor T7770CT7560A,B construction in in. mm Configurations GeneralConfiguration Options Summary For W7750A,B,C Controllers Heat Pump Control Allowable Heating and Cooling Equipment ConfigurationsStaged HEATING/COOLING Control Modulating HEATING/COOLING ControlEconomizer Control Pneumatic Actuator ControlWall Module Options Occupancy SensorWindow Open/Closed Digital Input MIXED-OUTPUT-TYPE ControlIndoor Air Quality IAQ Override Modes of OperationDirty Filter Monitor Smoke ControlNot OFF ModeDisabled AssignedDetermine Other Bus Devices Required OverviewPlan the System Step No DescriptionLay Out Communications and Power Wiring Lonworks Bus LayoutExcel VAV Cvahu Power Wiring Power Budget Calculation ExampleDeviceVA Information Obtained from ML7984B PWM Valve Actuator VA Ratings For Transformer Sizing Device DescriptionML6161A/B Damper Actuator, 35 lb-in R8242A Contactor Line LossPower wiring details for one Excel 10 per Transformer Nema class 2 transformer voltage output limitsPrepare Wiring Diagrams General ConsiderationsW7750 Controllers Factory Default Digital Outputs Terminal Terminal Number DescriptionConstant Volume AHU Controller ML6161 Floating Actuator COM CCW Load Controller Power Heat Wall Economizer Damper PWM Actuator Power Signal W7750C Constant Lonworks Bus Termination Module Pneumatic transducer to W7750B,C Shown, see triangle noteBrown Orange Lonworks Bus termination wiring options Order EquipmentT7770 and T7560 Wall Modules Honeywell Logo T7770D1018Sensor with Bypass/LED and Lonworks Jack Accessories Sensors AccessoriesEchelon Based Components and Parts Troubleshooting Excel 10 Controllers and Wall Modules Configure ControllersTroubleshooting CablingAlarms Excel 10 AlarmsResistance Value ohms Broadcasting the Service Message W7750 Controller Status LEDT7770C,D Wall Module Bypass Pushbutton and Override LED Appendix A. Using E-Vision to Commission a W7750 ControllerSetting the Pid Parameters Sensor CalibrationAppendix B. Sequences of Operation Common Operations Economizer Room Temperature Sensor RmTempHeating IAQ OptionSetpoint Limits LoSetptLim and HiSetptLim Bypass Mode StatusOvrd and StatusLedRemote Setpoint RmtStptPot BypassTimeNot Assigned Continuous Unoccupied ModeOccupancy Mode and Manual Override Arbitration Bypass OccupiedSchedule Master SchedMaster Recovery Ramping for Heat Pump SystemsTime Clock OccTimeClock Setpoint RampingFAN Operation Window Sensor StatusWndwSmoke Control Demand Limit Control DLCTemperature Control Operations See for a diagram of a typical W7750 UnitDirty Filter Monitor TWO Stages Staged Cooling ControlONE Stage Three StagesPulse Width Modulating PWM Control Cascade Control of Modulating COOLING/HEATINGSeries 60 Modulating Control Outdoor AIR Lockout of HEATING/COOLINGFreeze Stat Economizer ENABLE/DISABLE ControlIndoor AIR Quality IAQ Override Discharge AIR LOW Limit ControlEnergy Management Points Address Input Output Points AddressControl Parameters Address Status Points AddressMappable User Addresses and Table Number CO2 Concentration Relative TemperatureAir Flow EnthalpyValid states and the corresponding Application reset therefore, these points canPlaced in manual mode through a menu Enumerated values are shownNvName Field Name DefaultInput/Output Points Comments255 NciIoSelect DigitalIn2 NciIoSelect DigitalIn1Occsensor Shcedmasterin Occsensor UnuseddiCOOLSTAGE3 COOLSTAGE1COOLSTAGE2 COOLSTAGE4Sixtyfifty SiinvalidPPM Siinvalid FalseTrue StatusDI3 NvoIO UbDigitalIn EconEnSw NvoIO EconEnableInPosition when poor indoor air quality is detected OccSensr NvoIODefault Comments NvNameControl Parameters MinClRamp NciAux1SetPt UbMinClRampS0 Degrees F/Hr OdEnthalpyEnableMaxClRamp NciAux1SetPt UbMaxClRampS0 Degrees F/Hr MaxClRamp, OdTempMaxClRamp,PPM Gain for the cooling control loop Discharge air temperature cascade control loopGainCoolProp NciAux2SetPt UbKpCoolS2 Degrees F Degrees C GainHeatProp NciAux2SetPt UbKpHeatS2 Degrees F Degrees CEnergy Management Points Auxiliary functions. nviFree1 controls the FREE1OUT Refer to WSHPEnable.valueNviFree1 Value Network variable input failsRefer to nviTimeClk.value NviTimeClk ValueDestTimeClk NviTimeClk State 255 SrcTimeClkCt NvoTimeClk ValueStatus Points Bit Offset = FrostProtectAlrm Alarmbit1Bit Offset = SensorFailAlrm Bit Offset = InvalidSetPtAlrmSmokealarm NoalarmNodedisabled UpdateallfieldsHeat DisabledmodeStartupwait CoolNciAux1SetPts.ubOdEnthalpyEnableS2 StatusEconEn NvoData1 EconEnableAir flow switch is configured StatusManOcc NvoData1 NetManOccCoolStgsOn NvoData1 CoolStagesOn HeatStgsOn NvoData1 HeatStagesOnAuxiliary heating stages are turned on For both heating or coolingController mode is switched to Freezeprotect Is 1, the algorithm controls as per the settings foundNciConfig.SmokeControl MonitorSw NvoData1 MonSwitchSpacetempfield BypasstimerfieldTempcontrolptfield DischargetempfieldUbinvalid NvoError Errorbit0 StatusError NvoError Errorbit0SpaceTempError Bit Offset = Temperature SetPtError NvoError Errorbit0Are disabled as if the sensor was not configured NvoError Errorbit1Bit Offset = RtnEnthalpyError NvoError Errorbit1 Bit Offset = SpaceCO2Error NvoError Errorbit1Bit Offset = NvTodEventError NvoError Errorbit3 Bit Offset = NvWindowError NvoError Errorbit2Bit Offset = NvDlcShedError NvoError Errorbit2 Bit Offset = NvByPassError NvoError Errorbit3Cfgnul CfglocalCfgexternal Calibration PointsConfiguration Parameters False True CascCntrl NciConfig CascadeControl DisMinHtTime NciConfig DisableHeatMinTimeDisMinClTime NciConfig DisableCoolMinTime UseRaTempCtl NciConfigNone Normal Last NETOffset Absolutemiddle BypassonlyLonmark /Open System Points Hvacmrngwrmup Hvacprecool Hvaccool Hvacnightpurge Hvacnul HvacautoHvacheat HvacoffSNVTtempp 14 to 74-2958 100DestRmTemp NviSpaceTemp Degrees F SrcRmTemp NvoSpaceTemp Degrees FHvacauto Hvacnul HvacmrngwrmupHvactest Alarmnotifydisabled 255 Not configured 74-2958 NvoStatus Electricalfault103 NvoStatus Inalarm NvoStatus UnabletomeasureSwon SrcEconEnable NvoEcon State On other nodes. If the economizer function is configured byCorresponding economizer function is not enabled because SrcEconEnCt NvoEcon ValueDirect Access And Special Points OFF Data Share Points = including mapped points and others for Approximate Memory Size Estimating Procedure=using One-to-Many and not using points Mapped points = number of mapped points per ExcelSensor Type Sensor Resistance Versus Temperature Resistance OhmsResistance Sensors Sensor UseT7770B,C 10K ohm setpoint potentiometer Relative Offset Setpoint TemperatureDirect Setpoint Temperature Above and Below Setpoint Resistance OhmsVoltage/Current Sensors Sensor Voltage Versus Humidity Humidity PercentageSensor Voltage Versus Humidity Relative Humidity Percentage Sensor Current Versus Enthalpy volts Enthalpy mA 113 74-2958T7242 or equivalent 74-2958 114MAmAmAmA AmA mA mA Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Inw Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc 50.0.13