HP Performance Optimized Data Center (POD) 40c manual Grounding requirements, Future expansions

Page 11

Verify the following clearances prior to delivery:

Working distance clearance—Maintain a safe working clearance according to the local utility company or AHJ for each of the following items:

o Buildings o Fences

o Gate headers

o Underground and overhead utilities

Infrastructure clearance

o Underground power conduits, excluding power, water, and drainage lines connected to the HP POD 40c G2

o Underground water lines, excluding power, water, and drainage lines connected to the HP POD 40c G2

o Underground sewage lines, excluding power, water, and drainage lines connected to the HP POD 40c G2

Traffic clearance

For more information, see the local and national requirements, and site safety requirements.

Future expansions

When selecting a site location, consider future space and accessibility requirements. Adequate space around the HP POD 40c G2 is necessary for locating additional equipment within close proximity, such as generators and UPS devices. When installing additional equipment within close proximity to the HP POD 40c G2, consult with HP for site locations.

For specific space requirements, see "Dimensions and clearances (on page 8)."

Grounding requirements

The HP POD 40c G2 structure and internal components are all bonded together. A common grounding electrode conductor connection point is provided on the utility-end cold aisle.

WARNING: To avoid the risk of personal injury or electric shock, the HP POD 40c G2 must be properly grounded (earthed) in accordance with local and national requirements.

The following is a list of component requirements for grounding and bonding:

Grounding of the HP POD 40c G2 must comply with the requirements of Article 250 of the NEC, NFPA 70-2011 (NA/JPN) and with local and regional regulations (IEC for EMEA and AP).

Bonding of the piping systems and any exposed structural steel, installed to support the HP POD 40c G2, must be in accordance with NEC (NA) and with local and regional regulations (IEC for EMEA and APJ).

Site requirements 11

Image 11
Contents Part Number August Edition AbstractPage Contents Appendix C Regulatory compliance notices HP POD 40c G2 site assessment checklistAbout this document Safety and NEC complianceOverview Fire detection and suppression Site safety and securitySite assessment Site preparationOverall system capacities Electrical power capacities critical IT powerHP POD 40c G2 capacities HP POD 40c G2 capacity limitationsSite pad HP POD 40c G2 weightDimensions and clearances Site requirementsSite requirements Safety and clearance area Future expansions Grounding requirementsHumidifier water supply Grounding feature SpecificationUtilities Chilled water supply Requirement SpecificationRequirement Location Specification Drainage10-2500 µmhos Site electrical system Power infrastructure installationElectrical power system configuration Piping materialsTransformers and switchboards Connection portals Supported facility connectionsEnvironmental control system Additional POD connectionsDemarcation box Fire box HP POD 40c G2 security Fire, safety, and security notificationsHumidifier G2 is shut down Cold weather Areas prone to lightning or power surgesEnvironmental considerations Environmental risksZoning and permit requirements Site plan requirements and actionsCompleting a site assessment HP Site Preparation Drawing PackageSite planning HP POD 40c G2 installationHP POD 40c G2 storage requirements Assembly equipment locationsSite plan requirements and actions Appendix a HP site assessment HP POD 40c G2 site assessment checklistAs stated by the site engineering personnel can be Description Sign-offExisting or planned supply/return headers Security Customer responsibilities Description Sign-offProvide assistance in instances where a temporary Pre-delivery tasks HP POD 40c G2 site readiness checklistInstallation prerequisites Appendix B Preparing for deliveryWhen installing on an elevated surface, verify that General Description Sign-off Power requirements Description Sign-offGeneral water supply Description Sign-off Chilled water system Description Sign-offDescription Sign-off Federal Communications Commission notice Appendix C Regulatory compliance noticesHP POD 40c G2 regulatory compliance Regulatory compliance identification numbersCanadian notice Avis Canadien CablesGlossary Very early smoke detection apparatus Uninterruptible power systemNorth American Documentation feedback Index Index
Related manuals
Manual 84 pages 34.53 Kb

Performance Optimized Data Center (POD) 40c specifications

The HP Performance Optimized Data Center (POD) 40c is a state-of-the-art data center solution designed to meet the increasing demands for efficiency, scalability, and flexibility in enterprise environments. Aimed at delivering high-performance computing with minimal environmental impact, the POD 40c integrates innovative technologies and features to optimize operations.

One of the standout characteristics of the POD 40c is its modular design, allowing for easy deployment and scalability. Customers can configure their data center according to specific requirements, enabling rapid expansion as business needs evolve. The POD can house up to 240 servers, providing ample capacity to support intensive workloads while ensuring that users can quickly adapt to changing technological landscapes.

The energy efficiency of the POD 40c is a significant highlight. By employing advanced cooling technologies, including hot aisle/cold aisle containment and direct expansion cooling, it minimizes energy consumption while maintaining optimal temperatures for hardware components. This focus on efficiency also extends to power management, with redundant power supplies and the integration of high-efficiency power distribution units (PDUs) that help reduce operational costs.

In terms of connectivity, the HP POD 40c is equipped with comprehensive networking capabilities. The design includes integrated cabling systems that ensure organized and efficient routing of power and data. This dedication to streamlined connectivity facilitates faster data transfer rates and decreases latency, enhancing overall system performance.

Moreover, security is a paramount consideration in the POD 40c design. The unit incorporates various security features, including access controls, environmental monitoring, and surveillance options, which provide peace of mind for data-sensitive businesses. These elements work together to ensure that critical data remains protected from unauthorized access and environmental threats.

Sustainability is another key aspect, as the POD 40c is designed to be environmentally friendly. The system's effective cooling mechanisms and efficient power usage contribute to reduced carbon emissions, aligning with corporate sustainability goals and industry regulations.

In conclusion, the HP Performance Optimized Data Center (POD) 40c represents a cutting-edge solution for modern data center requirements. Its modularity, energy efficiency, robust connectivity, enhanced security, and sustainability make it an attractive option for organizations aiming to optimize their IT infrastructure while maintaining agility in a rapidly evolving digital landscape. The POD 40c exemplifies HP's commitment to providing innovative and performance-driven data center solutions, positioning it as a transformative asset for businesses seeking to thrive in a data-driven world.