Appendix A: HP site assessment
HP POD 40c G2 site assessment checklist
During a survey of the readiness of a proposed customer site for the HP POD 40c G2, the site is inspected for the following:
•Accessibility of machinery for the transportation and installation of the HP POD 40c G2
•Assessment of the suitability of the site infrastructure for installing the HP POD 40c G2 and for supporting infrastructure preparation and serviceability requirements
HP responsibilities
Item | Description |
| |
|
|
|
|
1. Engagement plan | Develop an engagement plan with specific |
|
|
| requirements relating to the proposed installation site. |
|
|
2. Site visits | Schedule site visits on mutually acceptable dates, |
|
|
| during normal HP business hours. |
|
|
3. Test equipment | Document any test equipment used in the customer |
|
|
| report. |
|
|
4. Installation site | Review and discuss the proposed installation site with |
|
|
review | the customer. This initial review includes physical |
|
|
| examination of the proposed installation site and, at |
|
|
| the sole discretion of HP, can include physical |
|
|
| measurements of the area size and clearances. |
|
|
5. Indoor/outdoor | Identify whether the HP POD 40c G2 installation is |
|
|
installation | indoors or outdoors as this can affect the degree and |
|
|
| type of infrastructure required and the mounting needs. |
|
|
6. Site pad | Inspect the proposed installation site to assess |
|
|
| compliance with the HP POD 40c G2 mounting |
|
|
| specifications. Ensure that the customer is fully aware |
|
|
| of the following requirements: |
|
|
| • Proper support capabilities must exist. If the |
|
|
| customer intends to edge or point load on the utility |
|
|
| and cargo ends, there must be support in the center |
|
|
| to prevent deflection. |
|
|
| • Upon installation, the POD structure must be |
|
|
| leveled to ≤ 0.5º, which can be checked at that |
|
|
| time with a surveyor’s transit. |
|
|
| • Shimming is allowed around the perimeter of the |
|
|
| POD. |
|
|
| • Place shims in increments across the length of the |
|
|
| HP POD 40c G2 to ensure that the HP POD 40c |
|
|
| G2 is level. |
|
|
|
|
|
|
7. Materials and | Visually inspect the materials and construction at the |
|
|
construction | proposed installation site to identify issues that can |
|
|
inspection | impact the HP POD 40c G2 installation. Verify that the |
|
|
| area is adequate for truck delivery, staging, and crane |
|
|
| location. |
|
|
|
| Appendix A: HP site assessment 27 |