Grounding feature | Specification |
|
|
Grounding electrode | • The grounding electrode conductor connection bus pad is located on the outside of |
conductor pad | the HP POD 40c G2 on the cold aisle adjacent to the power cabinet. |
| • The grounding pad must be connected to the grounding electrode system or |
| building steel in accordance with Article 250 of the NEC or equivalent regional |
| regulation. |
|
|
Grounding lugs | • Grounding lugs cannot be attached to any painted surface. |
| • Grounding lugs must be |
| grounding. |
|
|
Ground rod system or | The customer must provide an effective grounding system with a ground rod or a |
ground well | ground well. |
IMPORTANT: Before installing the HP POD 40c G2, consult your local AHJ for applicable codes and to review
The following figure shows the grounding electrode conductor connection that is located on the cold aisle of the HP POD 40c G2.
Side view shown
Utilities
Consider the proximity to required utilities, such as power, water, and network connections. While the required utilities can be brought to nearly any selected site, there is the potential for increased costs and decreased efficiency when the HP POD 40c G2 is located farther from the utility sources.
For utility clearance information, see "Dimensions and clearances (on page 8)."
Humidifier water supply
The HP POD 40c G2 requires supply water for the humidifier. The supply water must meet the following requirements.
Requirement | Specification |
|
|
Pressure | Between 20 and 110 psi, 0.1 and 0.8 MPa |
Temperature | Between 1º and 40°C (33º and 104°F) |
Minimum flow rate | 1.45 lpm (0.12 gpm) |