HP POD 40c G2 capacities
HP POD 40c G2 capacity limitations
The capacity limitations for the HP POD 40c G2 are separated into two categories: electrical power and mechanical cooling capacities. Both of these categories are interdependent and must be considered in conjunction with the overall customer requirements.
Electrical power capacities (critical IT power)
The electrical system of the HP POD 40c G2 has two main feeds, A and B, each rated at 800 A 415 VAC Wye
Mechanical cooling capacities
The HP POD 40c G2 cooling system consists of 6 zones. Each zone includes 2 heat exchangers and 18 fans. Cooling capacities are based on:
•Chilled water inlet temperature of 15.6ºC (60ºF)
•Heat exchanger fluid delta temperature of 5.5ºC (10ºF)
•Pure water cooling
•Chilled water flow rate of 908 lpm (240 gpm)
•Average air flow of 2000 cfm per rack
Overall system capacities
The HP POD 40c G2 overall system capacities are provided in the following table. It is the customer's responsibility to understand the level of redundancy required for their particular application and its associated limiting factor.
Redundancy level | Electrical (kW) | Thermal (kW) | Limiting factor |
|
|
|
|
N | — | 600 | Thermal* |
N+1 | — | 400 | Thermal* |
2N | 576 | 300 | Thermal* |
*The thermal limitation factors are described in "Mechanical cooling capacities (on page 7)."
HP POD 40c G2 capacities 7