IMPORTANT: The EPO system must be reset before you can power up and restart the HP POD 240e NA.
To reset the EPO system:
1.Determine and correct the reason for EPO system initiation.
2.If the EPO was triggered manually, the EPO button that was pushed must be reset by rotating the button as indicated.
3.Verify the key control for the EPO mode is in the Armed position.
4.Press and release the white EPO reset button.
ECS touchscreen and EPO indicators
The ECS touchscreen and EPO indicators are located on the IT section A control panel door.
The touchscreen enables easy configuration of environmental parameters and access data, and also monitors environmental, life safety, and security conditions within the HP POD 240e NA.
The EPO indicators provide the EPO status and enable the EPO system mode to be adjusted.
Item | Component | Indicator color | Description | |
|
|
|
|
|
1 | External EPO status | • | Indicates the operating status of the HP | |
| indicator | • | POD 240e NA | |
|
| • |
| |
|
|
|
| |
2 | Power on | White | Indicates the EPO power status | |
3 | EPO shutdown | Red |
| Indicates an EPO shutdown or alarm |
|
|
|
| condition |
4 | EPO armed | White | Indicates the EPO system is armed and | |
|
|
|
| operational |
|
|
|
| |
5 | EPO bypass mode | Yellow | Indicates the EPO is operating in bypass | |
|
|
|
| mode |
|
|
|
| |
6 | EPO bypassed | Green | Indicates that the EPO functionality and | |
|
|
|
| shutdown is bypassed |
Life safety systems 20