HP Performance Optimized Data Center (POD) 240a Indicates the cold aisle combination temperature

Page 53

The Stats screen allows you to set the following minimum and maximum setpoint alarm ranges for IT section A and IT section B.

Setpoint displayed

Description

 

 

Outdoor temperature

Indicates the outdoor temperature

Outdoor relative

Indicates the outdoor relative humidity

humidity

 

CA combo temperature

Indicates the cold aisle combination temperature

CA relative humidity

Indicates the cold aisle relative humidity

Cold aisle dew point

Indicates the cold aisle dew point

CA pressure

Indicates the cold aisle pressure

Return temperature

Indicates the return temperature

HA pressure

Indicates the hot aisle pressure

Supply fans

Indicates the supply fan percentage

Min and Max value

Indicates the specific sensor that is reading the

sensor number

minimum and maximum value for each statistic

Offset alarms can be configured to alert the BMS when an AHU sensor is offset by the average or median from the remaining AHUs in the IT section. For more information, see "Setting the offset alarm (on page 57)."

Environmental control system 53

Image 53
Contents Part Number November Edition AbstractPage Contents Air filter sensor HP POD 240e NA optional components Power feeder pull boxesBefore you contact HP HP contact information Regulatory compliance noticesComponent safety Operator safetyOverview Before you beginEnvironmental considerations Preventative maintenanceFire detection Structural component identification Component identificationComponent Description Parts and part number identificationExit sign locations Life safety component identificationComponent identification Component identification Main breaker locations Electrical power component identificationEnd view shown Component Description Reminds you that the electrical panels must only be Electrical power disconnect map label location End view shown Callout Electrical safety label DescriptionUPS Control cabinet component identificationIT section B control cabinet Component Description Security component identificationTop view shown Component Description RacksEPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators Component Indicator color Description Battery backup during an EPO eventEPO modes EPO accidental activationManual fire pulls Fire detection systemVesda air sampling smoke detection system Fire detection sequence of operations Fire alarm panelFire alarm indicators Emergency egress Power safety Power, electrical, and controlsSite electrical system Grounding and bondingLightning protection CapacitiesElectrical panel labels Power feedersPower distribution Adiabatic system Power distribution electrical busway systemPanel schedules Wire color codeEnd view shown Feature Specification Electrical busways Wire color DescriptionPage Drop boxes Rack powerLighting Feature SpecificationEnvironmental control system overview Using the ECSEnvironmental control system Satellite control boxes Facility connections to the ECSComponents of the ECS Connecting to the ECS through connection portals Connecting to the ECS through the demarcation boxManaging the ECS from the HP POD 240e NA Configuring the ECS Environmental control system Logging in remotely to the ECS Click Connect Locating the ECS IP addressNavigating the ECS interface Password protectedView Logging in to the ECS touchscreenTop screen Callout Icon name DescriptionCA RH Information displayed Description AD detail screenAisle in relation to the external ambient AD detail screen displays the following alarm conditions Charts screenAlarm displayed Description Operation displayed DescriptionPsychrometric chart Electrical Cabinets screen Alarms chart Controls Network screen Alarms screen Stats screen Indicates the cold aisle combination temperature Control settings ConfigureHMI settings Setting the Min and Max range for alarms Setting the Min and Max temperature and RH setpointsManaging the ECS system US Customary o MetricForcing an alarm Setting the offset alarmSetting the IP address Maintaining the ECS parameters Temperature and pressure sensorsCallout Sensor Quantity per Description IT section Callout Sensor Quantity per Description Hot aisle Adiabatic unitsControlling the hot aisle fans Adiabatic components AHU systemOverview Adiabatic media AHU theory of operationAHU system AHU system Static pressure control Connection portals IT networking and communicationsNetworking Demarcation box Adding a phone Fire boxIT networking and communications Air filter sensor Standard componentsHP POD 240e NA optional components Power feeder pull boxesOptional components General specifications SpecificationsRack specifications Features SpecificationsEnvironmental specifications Preparing the Adiabatic units for winter MaintenancePeriodic maintenance Component Description Supply header gravity drain Adiabatic unit by unit blowdown Supply header blowdown Standard power up procedure Power up procedurePower up checklist Standard power up procedureElectrical Cold weather power up procedureCold weather power up checklist Cold weather operation Full power down procedure Power down procedureHP contact information Contacting HPBefore you contact HP HP POD 240e NA regulatory compliance Safety and NEC complianceRegulatory compliance notices Warranty information Safety and regulatory complianceGlossary North American Outside air Power distribution unitProgrammable logic controller Performance-Optimized DatacenterEnclosure of sufficient size to enable entry of personnel Power usage efficiency Relative humidityUninterruptible power system Pounds per square inchDocumentation feedback Index Index Warranty Winterize, Hvac units 74 wire color code Safety, component Safety, power connections