Item | Component | Indicator color | Description | |
|
|
|
| |
7 | EPO mode | Key control | The key control allows you to select the | |
|
|
| EPO mode: | |
|
|
| • | Armed |
|
|
| • | Test |
|
|
| • | Bypass |
|
|
|
| |
8 | EPO reset | White button | Select to reset the EPO system |
EPO modes
The EPO system has three operating modes:
•
•
•
For more information, see "ECS touchscreen and EPO indicators (on page 20)."
The illuminated external EPO status indicator displays the current EPO mode.
•
•
•
EPO accidental activation
To help prevent accidentally pressing the EPO button and activating the EPO system, each EPO button is covered with a clear Lexan cover.
Battery backup during an EPO event
The following components are equipped with a UPS to help be sure that service is not interrupted during a loss of power to the HP POD 240e NA:
•Environmental control system (on page 34)
•VESDA air sampling smoke detection system (on page 22)
•Fire detection system (on page 22)
•Lighting (on page 33)
IMPORTANT: All critical IT UPS devices with batteries that exceed 700VA must be connected to the HP POD 240e NA EPO system, to be sure that the UPS batteries are disconnected during an EPO event. For more information about connecting UPS devices to the EPO system, see the HP Performance Optimized Datacenter 240e NA Maintenance and Service Guide.
Life safety systems 21