HP Performance Optimized Data Center (POD) 240a manual Drop boxes, Rack power

Page 32

Drop boxes

The internal electrical busways provide a location to connect each of the drop boxes, which then power the PDUs. For each IT section, stagger the drop boxes on the electrical busways by connecting one drop box to busway #1 and connecting the next drop box to busway #2. A staggered configuration allows for load balancing with the rack equipment and is necessary to create redundancy.

Side view shown

Disabling power

To disable power to a single PDU, open the drop box breaker feeding that PDU and disconnect the PDU from the drop box.

To disable power to a single rack, open the corresponding breakers on the drop boxes feeding each of the PDUs installed in that rack.

To disable power to a single electrical busway, open the appropriate breaker for that busway on the corresponding electrical busway panel outside of the HP POD 240e NA.

To disable power to all racks on the A-side busways, open each breaker for each busway on the corresponding electrical panel outside of the HP POD 240e NA.

Rack power

Power is provided to each rack by PDUs and drop boxes. The PDUs are powered by the drop boxes attached to each electrical busway. For more information about electrical busway drop boxes, see the HP Performance Optimized Datacenter 240e NA Maintenance and Service Guide.

Feature

Specification

 

 

Rack type

HP POD 240e NA rack

Max number of racks

44 (22 per IT section)

Max U space per rack

50U

Max U space per HP POD 240e NA

2,200U

Total number of PDU's

88 (2 per rack)

Power, electrical, and controls 32

Image 32
Contents Abstract Part Number November EditionPage Contents HP POD 240e NA optional components Power feeder pull boxes Air filter sensorRegulatory compliance notices Before you contact HP HP contact informationOperator safety Component safetyOverview Before you beginEnvironmental considerations Preventative maintenanceFire detection Component identification Structural component identificationParts and part number identification Component DescriptionLife safety component identification Exit sign locationsComponent identification Component identification Main breaker locations Electrical power component identificationEnd view shown Component Description Reminds you that the electrical panels must only be End view shown Callout Electrical safety label Description Electrical power disconnect map label locationControl cabinet component identification UPSSecurity component identification IT section B control cabinet Component DescriptionRacks Top view shown Component DescriptionEPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators Battery backup during an EPO event Component Indicator color DescriptionEPO modes EPO accidental activationManual fire pulls Fire detection systemVesda air sampling smoke detection system Fire detection sequence of operations Fire alarm panelFire alarm indicators Emergency egress Power, electrical, and controls Power safetySite electrical system Grounding and bondingCapacities Lightning protectionPower feeders Electrical panel labelsPower distribution electrical busway system Power distribution Adiabatic systemPanel schedules Wire color codeEnd view shown Feature Specification Wire color Description Electrical buswaysPage Rack power Drop boxesFeature Specification LightingEnvironmental control system overview Using the ECSEnvironmental control system Satellite control boxes Facility connections to the ECSComponents of the ECS Connecting to the ECS through the demarcation box Connecting to the ECS through connection portalsManaging the ECS from the HP POD 240e NA Configuring the ECS Environmental control system Logging in remotely to the ECS Locating the ECS IP address Click ConnectPassword protected Navigating the ECS interfaceLogging in to the ECS touchscreen ViewTop screen Callout Icon name DescriptionCA RH AD detail screen Information displayed DescriptionAisle in relation to the external ambient Charts screen AD detail screen displays the following alarm conditionsAlarm displayed Description Operation displayed DescriptionPsychrometric chart Alarms chart Electrical Cabinets screenControls Network screen Alarms screen Stats screen Indicates the cold aisle combination temperature Configure Control settingsHMI settings Setting the Min and Max temperature and RH setpoints Setting the Min and Max range for alarmsManaging the ECS system US Customary o MetricForcing an alarm Setting the offset alarmSetting the IP address Temperature and pressure sensors Maintaining the ECS parametersCallout Sensor Quantity per Description IT section Callout Sensor Quantity per Description Hot aisle Adiabatic unitsControlling the hot aisle fans Adiabatic components AHU systemOverview AHU theory of operation Adiabatic mediaAHU system AHU system Static pressure control Connection portals IT networking and communicationsNetworking Demarcation box Fire box Adding a phoneIT networking and communications Standard components Air filter sensorHP POD 240e NA optional components Power feeder pull boxesOptional components Specifications General specificationsRack specifications Features SpecificationsEnvironmental specifications Preparing the Adiabatic units for winter MaintenancePeriodic maintenance Component Description Supply header gravity drain Adiabatic unit by unit blowdown Supply header blowdown Power up procedure Standard power up procedurePower up checklist Standard power up procedureCold weather power up procedure ElectricalCold weather power up checklist Cold weather operation Power down procedure Full power down procedureHP contact information Contacting HPBefore you contact HP HP POD 240e NA regulatory compliance Safety and NEC complianceRegulatory compliance notices Safety and regulatory compliance Warranty informationGlossary Power distribution unit North American Outside airProgrammable logic controller Performance-Optimized DatacenterPower usage efficiency Relative humidity Enclosure of sufficient size to enable entry of personnelUninterruptible power system Pounds per square inchDocumentation feedback Index Index Safety, component Safety, power connections Warranty Winterize, Hvac units 74 wire color code