Feature | Specification |
|
|
Max power per PDU | 30 A = 17 kW; 60A = 34 kW |
Average capacity per rack | 30 kW |
Peak capacity per rack | 69.12 kW |
Voltage to rack | 240V |
Rack configuration |
Lighting
The HP POD 240e NA includes lighting in each section:
•IT section
•IT section
•Hot
•Service
A light switch is located at every personnel door. For more information about light switch locations, see "Life safety component identification (on page 10)."
The IT sections and the hot aisle LED lights are tied to battery backup power, so the emergency lights will activate to keep the interior of the HP POD 240e NA illuminated during a power outage or emergency.
For more information about lighting, see the HP Performance Optimized Datacenter 240e NA Maintenance and Service Guide.
Power, electrical, and controls 33