HP Performance Optimized Data Center (POD) 240a manual Maintenance, Periodic maintenance

Page 74

Maintenance

Periodic maintenance

Perform periodic inspections to ensure that the HP POD 240e NA continues to perform according to design parameters. During periodic inspections, pay special attention to electrical connections and wiring.

You are responsible for creating and performing detailed preventative maintenance based on HP recommendations. Data sheets or additional operation and maintenance manuals will be provided for this task.

CAUTION: Failure to implement a comprehensive preventative maintenance schedule may result in reduced efficiency in the HP POD 240e NA, failure of main or subsidiary systems, and loss of warranty on third party components.

For more specific maintenance information, see the HP Performance Optimized Datacenter 240e NA Maintenance and Service Guide.

Preparing the Adiabatic units for winter

CAUTION: Because the Adiabatic units use water, you must take extra precautions during the winter months to establish safe operating conditions of the HP POD 240e NA.

IMPORTANT: HP recommends contacting your HP representative prior to winterizing your HP POD 240e NA for further instructions.

There are three major processes that you must complete to winterize the HP POD 240e NA Adiabatic units. Complete the following processes in the following order:

1.Supply header gravity drain (on page 76)

2.Adiabatic unit by unit blowdown (on page 77)

3.Supply header blowdown (on page 78)

Your site or POD might have different component locations or a different number of Adiabatic units. You will need the following items to winterize the Adiabatic units:

Air hose adapter—Connects the house air or compressor to the supply header.

Adiabatic unit splash deflector—Used inside of each Adiabatic unit to prevent unnecessary splashing.

This splash deflector consists of a hose barb adapter and enough flexible tubing to direct water to the drain.

Maintenance 74

Image 74
Contents Abstract Part Number November EditionPage Contents HP POD 240e NA optional components Power feeder pull boxes Air filter sensorRegulatory compliance notices Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginEnvironmental considerations Preventative maintenanceFire detection Component identification Structural component identificationParts and part number identification Component DescriptionLife safety component identification Exit sign locationsComponent identification Component identification Main breaker locations Electrical power component identificationEnd view shown Component Description Reminds you that the electrical panels must only be End view shown Callout Electrical safety label Description Electrical power disconnect map label locationControl cabinet component identification UPSSecurity component identification IT section B control cabinet Component DescriptionRacks Top view shown Component DescriptionEPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator color Description EPO accidental activationManual fire pulls Fire detection systemVesda air sampling smoke detection system Fire detection sequence of operations Fire alarm panelFire alarm indicators Emergency egress Site electrical system Power, electrical, and controlsPower safety Grounding and bondingCapacities Lightning protectionPower feeders Electrical panel labelsPower distribution electrical busway system Power distribution Adiabatic systemPanel schedules Wire color codeEnd view shown Feature Specification Wire color Description Electrical buswaysPage Rack power Drop boxesFeature Specification LightingEnvironmental control system overview Using the ECSEnvironmental control system Satellite control boxes Facility connections to the ECSComponents of the ECS Connecting to the ECS through the demarcation box Connecting to the ECS through connection portalsManaging the ECS from the HP POD 240e NA Configuring the ECS Environmental control system Logging in remotely to the ECS Locating the ECS IP address Click ConnectPassword protected Navigating the ECS interfaceTop screen Logging in to the ECS touchscreenView Callout Icon name DescriptionCA RH AD detail screen Information displayed DescriptionAisle in relation to the external ambient Alarm displayed Description Charts screenAD detail screen displays the following alarm conditions Operation displayed DescriptionPsychrometric chart Alarms chart Electrical Cabinets screenControls Network screen Alarms screen Stats screen Indicates the cold aisle combination temperature Configure Control settingsHMI settings Managing the ECS system Setting the Min and Max temperature and RH setpointsSetting the Min and Max range for alarms US Customary o MetricForcing an alarm Setting the offset alarmSetting the IP address Temperature and pressure sensors Maintaining the ECS parametersCallout Sensor Quantity per Description IT section Callout Sensor Quantity per Description Hot aisle Adiabatic unitsControlling the hot aisle fans Adiabatic components AHU systemOverview AHU theory of operation Adiabatic mediaAHU system AHU system Static pressure control Connection portals IT networking and communicationsNetworking Demarcation box Fire box Adding a phoneIT networking and communications Standard components Air filter sensorHP POD 240e NA optional components Power feeder pull boxesOptional components Rack specifications SpecificationsGeneral specifications Features SpecificationsEnvironmental specifications Preparing the Adiabatic units for winter MaintenancePeriodic maintenance Component Description Supply header gravity drain Adiabatic unit by unit blowdown Supply header blowdown Power up checklist Power up procedureStandard power up procedure Standard power up procedureCold weather power up procedure ElectricalCold weather power up checklist Cold weather operation Power down procedure Full power down procedureHP contact information Contacting HPBefore you contact HP HP POD 240e NA regulatory compliance Safety and NEC complianceRegulatory compliance notices Safety and regulatory compliance Warranty informationGlossary Programmable logic controller Power distribution unitNorth American Outside air Performance-Optimized DatacenterUninterruptible power system Power usage efficiency Relative humidityEnclosure of sufficient size to enable entry of personnel Pounds per square inchDocumentation feedback Index Index Safety, component Safety, power connections Warranty Winterize, Hvac units 74 wire color code
Related manuals
Manual 8 pages 155 b Manual 26 pages 60.09 Kb Manual 39 pages 18.56 Kb