Information displayed | Description |
|
|
Static pressure | Indicates the cold and hot aisle static pressure |
| readings for each Adiabatic in relation to the |
| external ambient pressure |
|
|
Temps | Indicates the cold and hot aisle temperature |
| readings for each Adiabatic unit |
|
|
Fan speed | Indicates the fan speed for each Adiabatic unit |
Water valve | Indicates the water valve percentage for each |
| Adiabatic unit |
Dampers | Indicates the damper position for each Adiabatic |
| unit |
|
|
To change the charts that display at the bottom of the screen:
1.Click a chart to bring up the chart menu.
2.Select the information that you want to view.
Alarms chart
The alarms chart displays critical and warning alarms that are active in the system. For more information, see "Alarms screen (on page 51)."
Electrical Cabinets screen
The Electrical Cabinets screen displays detailed power meter information that is monitored from the HP POD 240e NA power input. This screen displays the voltage and current average for all
The power information that displays on this screen is
Static IP addresses can be viewed from this screen when the
IMPORTANT: The ECS system subtracts the power measurements for the house panel from the Starline power measurements to be sure that the PUE measurements are accurate.