HP Performance Optimized Data Center (POD) 240a Charts screen, Operation displayed Description

Page 47

Operation displayed

Description

 

 

Isolation damper

Indicates the position of the isolation damper,

 

100% means the damper is open

 

 

Water PID

Indicates the percentage of full flow water usage

Return damper

Indicates the position of the return damper, 100%

 

means the damper is open

Bypass damper

Indicates the position of the bypass damper,

 

100% means the damper is open

 

 

Cold aisle fan

Indicates the speed of the cold aisle fan

Outdoor damper

Indicates the position of the return damper, 100%

 

means the damper is open

OA temperature

Indicates the OA temperature

OA relative humidity

Indicates the OA relative humidity

OA dew point

Indicates the OA dew point temperature

The AD detail screen displays the following alarm conditions:

Alarm displayed

Description

 

 

Filter

Indicates that a filter needs to be changed

Fire/smoke

Indicates fire or smoke is detected

Hi water warning

Indicates water in the Adiabatic drain pan

Hi-Hi water critical

Indicates excessive water in the Adiabatic drain

 

pan

Heater over temperature

Indicates the AHU heater temperature is too high

AC power failure

Indicates the AHU power is in failure

CA temperature compare

Indicates the AHU discharge temperature is in

 

range of the other AHUs in the IT section

Winterize

Indicates the Adiabatic units are operating in

 

Winterize mode

If an alarm condition exists for the Adiabatic unit, the parameter that is out of range will turn amber or red, based on the severity of the alarm condition. For more information about alarm conditions, see "Alarms screen (on page 51)".

To view the details of another Adiabatic unit, click the PREV/NEXT buttons on the top of the screen. These buttons allow you to scroll numerically through all of the Adiabatic units.

Charts screen

The Charts screen displays the following information:

Psychrometric chart (on page 48)—Displays recommended and operational ranges for the HP POD 240e NA.

Readings chart (on page 48)—Displays static pressure, temperature, fan speed, water valve, or damper readings.

Environmental control system 47

Image 47
Contents Part Number November Edition AbstractPage Contents Air filter sensor HP POD 240e NA optional components Power feeder pull boxesBefore you contact HP HP contact information Regulatory compliance noticesBefore you begin Operator safetyComponent safety OverviewEnvironmental considerations Preventative maintenanceFire detection Structural component identification Component identificationComponent Description Parts and part number identificationExit sign locations Life safety component identificationComponent identification Component identification Main breaker locations Electrical power component identificationEnd view shown Component Description Reminds you that the electrical panels must only be Electrical power disconnect map label location End view shown Callout Electrical safety label DescriptionUPS Control cabinet component identificationIT section B control cabinet Component Description Security component identificationTop view shown Component Description RacksEPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators EPO accidental activation Battery backup during an EPO eventComponent Indicator color Description EPO modesManual fire pulls Fire detection systemVesda air sampling smoke detection system Fire detection sequence of operations Fire alarm panelFire alarm indicators Emergency egress Grounding and bonding Power, electrical, and controlsPower safety Site electrical systemLightning protection CapacitiesElectrical panel labels Power feedersPower distribution Adiabatic system Power distribution electrical busway systemPanel schedules Wire color codeEnd view shown Feature Specification Electrical busways Wire color DescriptionPage Drop boxes Rack powerLighting Feature SpecificationEnvironmental control system overview Using the ECSEnvironmental control system Satellite control boxes Facility connections to the ECSComponents of the ECS Connecting to the ECS through connection portals Connecting to the ECS through the demarcation boxManaging the ECS from the HP POD 240e NA Configuring the ECS Environmental control system Logging in remotely to the ECS Click Connect Locating the ECS IP addressNavigating the ECS interface Password protectedCallout Icon name Description Logging in to the ECS touchscreenView Top screen CA RH Information displayed Description AD detail screenAisle in relation to the external ambient Operation displayed Description Charts screenAD detail screen displays the following alarm conditions Alarm displayed DescriptionPsychrometric chart Electrical Cabinets screen Alarms chartControls Network screen Alarms screen Stats screen Indicates the cold aisle combination temperature Control settings ConfigureHMI settings US Customary o Metric Setting the Min and Max temperature and RH setpointsSetting the Min and Max range for alarms Managing the ECS systemForcing an alarm Setting the offset alarmSetting the IP address Maintaining the ECS parameters Temperature and pressure sensorsCallout Sensor Quantity per Description IT section Callout Sensor Quantity per Description Hot aisle Adiabatic unitsControlling the hot aisle fans Adiabatic components AHU systemOverview Adiabatic media AHU theory of operationAHU system AHU system Static pressure control Connection portals IT networking and communicationsNetworking Demarcation box Adding a phone Fire boxIT networking and communications Air filter sensor Standard componentsHP POD 240e NA optional components Power feeder pull boxesOptional components Features Specifications SpecificationsGeneral specifications Rack specificationsEnvironmental specifications Preparing the Adiabatic units for winter MaintenancePeriodic maintenance Component Description Supply header gravity drain Adiabatic unit by unit blowdown Supply header blowdown Standard power up procedure Power up procedureStandard power up procedure Power up checklistElectrical Cold weather power up procedureCold weather power up checklist Cold weather operation Full power down procedure Power down procedureHP contact information Contacting HPBefore you contact HP HP POD 240e NA regulatory compliance Safety and NEC complianceRegulatory compliance notices Warranty information Safety and regulatory complianceGlossary Performance-Optimized Datacenter Power distribution unitNorth American Outside air Programmable logic controllerPounds per square inch Power usage efficiency Relative humidityEnclosure of sufficient size to enable entry of personnel Uninterruptible power systemDocumentation feedback Index Index Warranty Winterize, Hvac units 74 wire color code Safety, component Safety, power connections
Related manuals
Manual 8 pages 155 b Manual 26 pages 60.09 Kb Manual 39 pages 18.56 Kb