HP Performance Optimized Data Center (POD) 240a manual Supply header blowdown

Page 78

Continue preparing the Adiabatic units for winter by completing the instructions in "Supply header blowdown (on page 78)."

Supply header blowdown

Before you begin the process below, be sure to complete the steps in the following sections:

1.Supply header gravity drain (on page 76)

2.Adiabatic unit by unit blowdown (on page 77)

Be sure that all Adiabatic units are isolated from the supply header. If all Adiabatic units are not isolated from the supply header, see "Adiabatic unit by unit blowdown (on page 77)." To be sure the maximum amount of water is removed from the entire supply header(s), complete the following steps:

IMPORTANT: Be sure air pressure is available to complete the next steps.

1.Pressurize the supply header to 20-50 psi with a pressure gauge, if installed, and close the Y-strainer flushing valve.

2.Open the supply header drain valve to release the air pressure and water.

3.Close the supply header drain valve when the header pressure is zero.

4.Repeat the steps to open and close the drain valve for five cycles, or until no water remains.

At this point, all headers are at atmospheric pressure, all water is removed from the system, and all power is removed at each Adiabatic unit.

5.Remove the garden hose and air adapter assemblies, and then replace the previously removed plugs.

Maintenance 78

Image 78
Contents Abstract Part Number November EditionPage Contents HP POD 240e NA optional components Power feeder pull boxes Air filter sensorRegulatory compliance notices Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginPreventative maintenance Fire detectionEnvironmental considerations Component identification Structural component identificationParts and part number identification Component DescriptionLife safety component identification Exit sign locationsComponent identification Component identification Electrical power component identification End view shown Component DescriptionMain breaker locations Reminds you that the electrical panels must only be End view shown Callout Electrical safety label Description Electrical power disconnect map label locationControl cabinet component identification UPSSecurity component identification IT section B control cabinet Component DescriptionRacks Top view shown Component DescriptionLife safety systems Life safety overviewEPO system ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator color Description EPO accidental activationFire detection system Vesda air sampling smoke detection systemManual fire pulls Fire alarm panel Fire alarm indicatorsFire detection sequence of operations Emergency egress Site electrical system Power, electrical, and controlsPower safety Grounding and bondingCapacities Lightning protectionPower feeders Electrical panel labelsPower distribution electrical busway system Power distribution Adiabatic systemWire color code End view shown Feature SpecificationPanel schedules Wire color Description Electrical buswaysPage Rack power Drop boxesFeature Specification LightingUsing the ECS Environmental control systemEnvironmental control system overview Facility connections to the ECS Components of the ECSSatellite control boxes Connecting to the ECS through the demarcation box Connecting to the ECS through connection portalsManaging the ECS from the HP POD 240e NA Configuring the ECS Environmental control system Logging in remotely to the ECS Locating the ECS IP address Click ConnectPassword protected Navigating the ECS interfaceTop screen Logging in to the ECS touchscreenView Callout Icon name DescriptionCA RH AD detail screen Information displayed DescriptionAisle in relation to the external ambient Alarm displayed Description Charts screenAD detail screen displays the following alarm conditions Operation displayed DescriptionPsychrometric chart Alarms chart Electrical Cabinets screenControls Network screen Alarms screen Stats screen Indicates the cold aisle combination temperature Configure Control settingsHMI settings Managing the ECS system Setting the Min and Max temperature and RH setpointsSetting the Min and Max range for alarms US Customary o MetricSetting the offset alarm Setting the IP addressForcing an alarm Temperature and pressure sensors Maintaining the ECS parametersCallout Sensor Quantity per Description IT section Adiabatic units Controlling the hot aisle fansCallout Sensor Quantity per Description Hot aisle AHU system OverviewAdiabatic components AHU theory of operation Adiabatic mediaAHU system AHU system Static pressure control IT networking and communications NetworkingConnection portals Demarcation box Fire box Adding a phoneIT networking and communications Standard components Air filter sensorPower feeder pull boxes Optional componentsHP POD 240e NA optional components Rack specifications SpecificationsGeneral specifications Features SpecificationsEnvironmental specifications Maintenance Periodic maintenancePreparing the Adiabatic units for winter Component Description Supply header gravity drain Adiabatic unit by unit blowdown Supply header blowdown Power up checklist Power up procedureStandard power up procedure Standard power up procedureCold weather power up procedure ElectricalCold weather power up checklist Cold weather operation Power down procedure Full power down procedureContacting HP Before you contact HPHP contact information Safety and NEC compliance Regulatory compliance noticesHP POD 240e NA regulatory compliance Safety and regulatory compliance Warranty informationGlossary Programmable logic controller Power distribution unitNorth American Outside air Performance-Optimized DatacenterUninterruptible power system Power usage efficiency Relative humidityEnclosure of sufficient size to enable entry of personnel Pounds per square inchDocumentation feedback Index Index Safety, component Safety, power connections Warranty Winterize, Hvac units 74 wire color code