Thermo Products OL6RA072D48(B/R) Low Capacity, High Capacity, = Recommended heating speed setting

Page 31
Heating Speed Set-ups ( 2 – Stage )

Heating Speed Set-ups ( 2 – Stage )

OL6*X072DV5

 

 

 

 

 

LOW CAPACITY

 

 

HIGH CAPACITY

 

FAN

BTUH

 

LOW FIRE

 

 

HI FIRE

 

 

LOW FIRE

 

 

HI FIRE

 

CONTROL

60,000

 

72,000

 

 

72,000

 

90,000

 

 

 

 

 

 

 

 

 

SW 1

HEATING

 

APPROX.

 

 

APPROX.

 

 

APPROX.

 

 

APPROX.

 

SWITCH

 

CFM/RISE (ºF)

 

 

CFM/RISE (ºF)

 

 

CFM/RISE (ºF)

 

 

CFM/RISE (ºF)

 

CFM

 

 

 

 

 

 

 

 

SETTINGS

 

AMPS/WATTS

 

 

AMPS/WATTS

 

 

AMPS/WATTS

 

 

AMPS/WATTS

 

 

 

 

 

 

 

 

 

 

3

– OFF

 

604 / 91º

 

755 / 87º

 

 

604 / 109º

 

755 / 109º

 

 

2

– OFF

755

 

 

 

 

 

 

0.8/80

 

1.2/107

 

 

0.8/80

 

1.2/107

 

 

1

– OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

– OFF

 

 

661 / 83º

 

 

826 / 80º

 

 

661 / 100º

 

826 / 100º

 

 

2

– OFF

826

 

 

 

 

 

 

 

 

 

0.9/83

 

 

1.4/120

 

 

0.9/83

 

1.4/120

 

 

1

– ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

– OFF

 

 

718 / 70º

 

 

898 / 74º

 

 

718 / 92º

 

898 / 92º

 

 

2

– ON

898

 

 

 

 

 

 

 

 

 

0.95/96

 

 

1.5/139

 

 

0.95/96

 

1.5/139

 

 

1

– OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

– OFF

 

 

786 / 64º

 

 

983 / 67º

 

 

 

786 / 84º

 

 

983 / 84º

 

 

2

– ON

983

 

 

 

 

 

 

 

 

 

 

 

1.1/117

 

 

1.8/169

 

 

 

1.1/117

 

 

1.8/169

 

 

1

– ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

– ON

 

 

854 / 59º

 

 

1068 / 62º

 

 

 

854 /

 

 

1068 / 77º

 

 

2

– OFF

1068

 

 

 

 

 

 

 

 

 

 

 

1.3/131

 

 

2.0/190

 

 

 

77º1.3/131

 

 

2.0/190

 

 

1

– OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

– ON

 

 

934 / 54º

 

 

1168 / 57º

 

 

 

934 / 71º

 

 

1168 / 71º

 

 

2

– OFF

1168

 

 

 

 

 

 

 

 

 

 

 

1.5/139

 

 

2.4/222

 

 

 

1.5/139

 

 

2.4/222

 

 

1

– ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FACTORY

3 – ON

 

1025 / 50º

 

1282 / 52º

 

 

 

1025 / 64º

 

 

1282 / 64º

 

SW1 SWITCH

2 – ON

1282

 

 

 

 

 

 

 

2.0/190

 

2.9/277

 

 

 

2.0/190

 

 

2.9/277

 

SETTINGS

1

– OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

– ON

 

1139 / 48º

 

1397/ 46º

 

 

 

1139 / 58º

 

 

1397 / 60º

 

 

2

– ON

1397

 

 

 

 

 

 

 

 

2.4/222

 

4.0/378

 

 

 

2.4/222

 

 

4.0/378

 

 

1

– ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW CAPACITYHIGH CAPACITY = Recommended heating speed setting = Recommended heating speed setting

Figure 18-2: ECM 2-stage blower motor speed chart

28

Image 31
Contents OL6RX072DV5R OL6RA072D48B/ROL6FA072D48B/R OL6RA072DV5B/RCONTENTS Fuel ConfigurationFeature Model Number Digit1.Excess oil has accumulated I. SAFETY SECTIONcWARNING AND CAUTIONS cCAUTION DO NOT ATTEMPT TO START THE BURNER WHENPage a. Combustible material A. CODES AND CLEARANCESb. Non-combustiblematerial MODEL NO A. CHIMNEYTYPE OF FROM2. PREVENTION OF CHIMNEY CONDENSING 1. PROPER CHIMNEY SIZE3. PROPER CHIMNEY HEIGHT 4. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION9 FLUE PIPE CLEARANCES, SIZING AND TYPE 7. TIGHT CLEAN-OUTDOORS AND CONNECTIONS6. TIGHT JOINTS 8. NO INTERCONNECTED CHIMNEY FLUESB. VENTING C. DRAFT REGULATORS ROTATION OF FRONT FLUE ELBOWNote Do not use with Direct Vent application Airflow Requirements and Sizing of Duct Work D. DUCT WORK/AIR CONDITIONINGPage The ASHRAE Handbook - Fundamentalsis an excellent source of duct system design principles and pressure drop data. Conversely, for a specified type of fitting, it is also possible to determine the required size or diameter of the component for a specified pressure drop and flow rate 1.1 X TR TEMPERATURE RISE, F = HEATINGCFM 1.HEATING CFM HEAT OUTPUT OF FURNACE BTUHFilter Type E. Air Filters Mounted Internal to FurnaceMaximum Model NumberF. LIMIT POSITION AND LOCATION DO NOT CHANGE POSITION OF THE CHAMBER G. BURNER INSTALLATIONNOZZLE SIZE H. BURNER SPECIFICATIONS AND APPLICATIONSOIL NOZZLE CAPACITY CHART + INSULATOR S = SLEEVE OR N = NONENOZZLE SIZE 2 STAGE FIRING RATESCAPACITY FIRINGI. OIL TANK AND PIPING MOUNTING THE 2-STAGERIELLO BURNER5.A readily accessible, design-certified,manual oil shutoff valve, with a non-displaceablerotor member, shall be installed in the fuel oil supply piping within 6 feet of the appliance Maximum J. OIL FILTERK. ELECTRICAL WIRIING AssemblyWire size selections in Table 10 are based upon Table 310-16of the National Electrical Codefor three copper conductors, with insulation rated for 75 degrees Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation temperature ratings and ambient conditions, refer to the National Electrical Codefor the minimum wire sizing requirements Thermostat Anticipator Setting Preferred method of adjustment L. Blower Motor Speed Selection Draw Amps/ / Watts vs Heating Speed Set-upsOL6*A072DV5 Furnace Motor CurrentHeating Speed Set-ups 2 - Stage OL6*X072DV5 LOW CAPACITYHIGH CAPACITY = Recommended heating speed settingExternal Static Pressure in W.C Cooling Speed Set-ups OL6**072DV5Furnace Motor Current Draw Amps / Watts vsPage TERMINAL DEFINITIONS & FIELD WIRING M. BLOWER CONTROLLER INFORMATION FOR PSC MOTORB. Outputs A. InputsC. Operating Modes Heat Mode DIAGNOSTIC FEATURES PSC TROUBLE SHOOTINGi.STOP! Read the safety information above N. STARTUP PROCEDURESOperating Instructions For Your Safety Read Before OperatingTo Turn Off Oil to Appliance 2. Adjustment of Burner CombustionCOMBUSTION HEAD SETTING FOR 2-STAGERIELLO BURNER TURN TO THE RIGHT SIGN + AIR DAMPER ADJUSTMENTTURN TO THE LEFT SIGN 2nd STAGE ADJUSTMENT 1st STAGE ADJUSTMENTNotice Minimum return air temperature is 55F 3. Adjustment Of Heat Input Rate4. Setting Supply Air Temperature Rise 5. Checkout Procedure cCAUTION DO NOT ATTEMPT TO START THE BURNER WHEN III. USERS INFORMATION SECTIONC. INSPECTION AREAS cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELFD. STARTING THE BURNER E. FILTER CLEANING AND LOCATIONIV. INSTALLERS INSTRUCTIONS TO USER A.GENERAL INSPECTION V. DEALER MAINTENANCESAFETY DURING SERVICING AND INSPECTION B. HEAT EXCHANGER C. HEAT EXCHANGER CLEANING INSTRUCTIONSVacuum Hose Length OL6 8FT Figure 24 Heat Exchanger Clean-OutsF. SUPPLY/RETURN AIR FILTER Filter maintenance procedureD. ELECTRICAL SYSTEM E. SUPPLY/RETURN AIR BLOWERG. EXTENDED APPLIANCE SHUTDOWN Filter replacementON STARTUP 2.Remove the furnace front door Riello Burner Beckett BurnerPERSONNEL, AND NOT BY THE FURNACE OWNER VII. TROUBLESHOOTINGA. DIAGNOSTICS Diagnostic FeaturesB. CAD CELL CHECKOUT PROCEDURE VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page HEATING CUSTOMERSYSTEM Replacement Parts for OL6F*072D Appendix - A Replacement PartsPage Replacement Parts for OL6R*072D Page OL6*A072D48 PSC Wiring Diagram Appendix - B Wiring DiagramsOL6*A072DV5 ECM Wiring Diagram OL6*X072DV5 ECM 2-StageWiring Diagram