Thermo Products OL6RA072DV5(B/R), OL6FA072DV5(B/R), OL6RA072D48(B/R) Beckett Burner, Riello Burner

Page 57
Beckett Burner

Beckett Burner

Riello Burner

Figure 28: Location of oil primary control reset button

If this action does not reactivate the unit, contact a qualified service agency for assistance.

In general, if the thermostat is set in the heating mode, the heating system functions entirely automatically. However, under certain circumstances, the appliance may not be able to fire the burner. For instance, if the manual oil shutoff valve has been closed or the oil tank is out of fuel, the oil line may have air trapped in it. It will be necessary to purge the air by bleeding the supply line from the tank to the burner again for the heating system to operate. Refer to the instructions under the Extended Appliance Shutdown section of this manual.

NOTICE: Thermo Products recommends that the user/homeowner, contact a qualified service agency for assistance in bleeding the fuel line(s) and lighting off the heating section.

The following maintenance points should be reviewed periodically to assure the heating and cooling systems continue to function properly.

Riello BurnerManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background: Shut off unit and disconnect the power source before disassembling the unit.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background: Never operate the appliance without clean air filters in place.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background : This appliance requires air for combustion, ventilation, and cooling. Do not block or obstruct air openings in the unit and the air space around the perimeter of the unit.

1.At least every three months, under normal usage conditions, check and clean all air filters in the appliance and, if present, in the duct system. If excessively dirty air filters are not cleaned, or changed, poor system performance will result due to reduced airflow. Low airflow places unnecessary strain on the compressor, possibly causing the system to shutdown on the refrigerant high-pressure switch. Refer to Figure 23 for a sketch of the filter location.

2.Do not allow the fuel oil tank to run completely empty. During the summer, keep the tank full to reduce condensation of moisture on the inside surface of the tank. If the fuel tank runs completely dry, it may be necessary to bleed air from the fuel lines. Contact a qualified heating contractor to bleed the lines and restart the burner.

3.Check the supply and return air connections to the appliance to insure the seals between the duct and appliance and the appliance and home are intact. Check the ducts for any signs of collapse, holes, or excessive corrosion. Repair or replace components as required.

54

Image 57
Contents OL6FA072D48B/R OL6RA072D48B/ROL6RA072DV5B/R OL6RX072DV5RCONTENTS Feature ConfigurationModel Number Digit FuelcWARNING AND CAUTIONS I. SAFETY SECTIONcCAUTION DO NOT ATTEMPT TO START THE BURNER WHEN 1.Excess oil has accumulatedPage a. Combustible material A. CODES AND CLEARANCESb. Non-combustiblematerial TYPE OF A. CHIMNEYFROM MODEL NO2. PREVENTION OF CHIMNEY CONDENSING 1. PROPER CHIMNEY SIZE3. PROPER CHIMNEY HEIGHT 4. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION6. TIGHT JOINTS 7. TIGHT CLEAN-OUTDOORS AND CONNECTIONS8. NO INTERCONNECTED CHIMNEY FLUES 9 FLUE PIPE CLEARANCES, SIZING AND TYPEB. VENTING ROTATION OF FRONT FLUE ELBOW C. DRAFT REGULATORSNote Do not use with Direct Vent application Airflow Requirements and Sizing of Duct Work D. DUCT WORK/AIR CONDITIONINGPage The ASHRAE Handbook - Fundamentalsis an excellent source of duct system design principles and pressure drop data. Conversely, for a specified type of fitting, it is also possible to determine the required size or diameter of the component for a specified pressure drop and flow rate 1.1 X TR TEMPERATURE RISE, F = HEATINGCFM 1.HEATING CFM HEAT OUTPUT OF FURNACE BTUHMaximum E. Air Filters Mounted Internal to FurnaceModel Number Filter TypeF. LIMIT POSITION AND LOCATION DO NOT CHANGE POSITION OF THE CHAMBER G. BURNER INSTALLATIONOIL NOZZLE CAPACITY CHART H. BURNER SPECIFICATIONS AND APPLICATIONS+ INSULATOR S = SLEEVE OR N = NONE NOZZLE SIZECAPACITY 2 STAGE FIRING RATESFIRING NOZZLE SIZEI. OIL TANK AND PIPING MOUNTING THE 2-STAGERIELLO BURNER5.A readily accessible, design-certified,manual oil shutoff valve, with a non-displaceablerotor member, shall be installed in the fuel oil supply piping within 6 feet of the appliance K. ELECTRICAL WIRIING J. OIL FILTERAssembly MaximumWire size selections in Table 10 are based upon Table 310-16of the National Electrical Codefor three copper conductors, with insulation rated for 75 degrees Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation temperature ratings and ambient conditions, refer to the National Electrical Codefor the minimum wire sizing requirements Thermostat Anticipator Setting Preferred method of adjustment L. Blower Motor Speed Selection OL6*A072DV5 Heating Speed Set-upsFurnace Motor Current Draw Amps/ / Watts vsHIGH CAPACITY LOW CAPACITY= Recommended heating speed setting Heating Speed Set-ups 2 - Stage OL6*X072DV5Furnace Motor Current Cooling Speed Set-ups OL6**072DV5Draw Amps / Watts vs External Static Pressure in W.CPage TERMINAL DEFINITIONS & FIELD WIRING M. BLOWER CONTROLLER INFORMATION FOR PSC MOTORB. Outputs A. InputsC. Operating Modes Heat Mode DIAGNOSTIC FEATURES PSC TROUBLE SHOOTINGOperating Instructions N. STARTUP PROCEDURESFor Your Safety Read Before Operating i.STOP! Read the safety information aboveTo Turn Off Oil to Appliance 2. Adjustment of Burner CombustionCOMBUSTION HEAD SETTING FOR 2-STAGERIELLO BURNER AIR DAMPER ADJUSTMENT TURN TO THE RIGHT SIGN +TURN TO THE LEFT SIGN 2nd STAGE ADJUSTMENT 1st STAGE ADJUSTMENTNotice Minimum return air temperature is 55F 3. Adjustment Of Heat Input Rate4. Setting Supply Air Temperature Rise 5. Checkout Procedure C. INSPECTION AREAS III. USERS INFORMATION SECTIONcCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF cCAUTION DO NOT ATTEMPT TO START THE BURNER WHEND. STARTING THE BURNER E. FILTER CLEANING AND LOCATIONIV. INSTALLERS INSTRUCTIONS TO USER V. DEALER MAINTENANCE A.GENERAL INSPECTIONSAFETY DURING SERVICING AND INSPECTION B. HEAT EXCHANGER C. HEAT EXCHANGER CLEANING INSTRUCTIONSVacuum Hose Length OL6 8FT Figure 24 Heat Exchanger Clean-OutsD. ELECTRICAL SYSTEM Filter maintenance procedureE. SUPPLY/RETURN AIR BLOWER F. SUPPLY/RETURN AIR FILTERG. EXTENDED APPLIANCE SHUTDOWN Filter replacementON STARTUP 2.Remove the furnace front door Riello Burner Beckett BurnerA. DIAGNOSTICS VII. TROUBLESHOOTINGDiagnostic Features PERSONNEL, AND NOT BY THE FURNACE OWNERB. CAD CELL CHECKOUT PROCEDURE VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page CUSTOMER HEATINGSYSTEM Replacement Parts for OL6F*072D Appendix - A Replacement PartsPage Replacement Parts for OL6R*072D Page OL6*A072D48 PSC Wiring Diagram Appendix - B Wiring DiagramsOL6*A072DV5 ECM Wiring Diagram OL6*X072DV5 ECM 2-StageWiring Diagram