Thermo Products OL6RX072DV5(R), OL6FA072DV5(B/R), OL6RA072D48(B/R) Preferred method of adjustment

Page 28
Preferred method of adjustment:

Figure 16: Heat Anticipator Adjustment Scale

In many cases, this setting can be found in the thermostat installation instructions. If this information is not available, or if the correct setting is questioned, the following procedures should be followed:

Preferred method of adjustment:

Using an analog ammeter on the lowest scale, such as an Amp Check, connect the meter across terminals “R” and “W” on the sub-base (“RH” & “W” on an isolating thermostat sub-base). If the reading is too low to move the needle on to the measurement scale of the instrument, proceed as follows:

1.Wrap 10 loops of single strand, insulated, thermostat wire around the prongs of an ammeter, refer to Figure 17. Set the scale to the 1 to 5 or 1 to 6 amp. scale.

Figure 17: Analog Ammeter w/ Wire Loops to Boost Reading

2.Connect the bare ends of this wire jumper across terminals “R” and “W” on the sub-base (“RH” and “W” on an isolating thermostat sub-base). This test must be performed without the thermostat attached to the sub-base.

3.Let the heating system operate in this position for about one minute. Read the amp meter scale. Regardless of the value of the meter reading, divide the value by 10 (for 10 loops of wire).

25

Image 28
Contents OL6RA072D48B/R OL6FA072D48B/ROL6RA072DV5B/R OL6RX072DV5RCONTENTS Configuration FeatureModel Number Digit FuelI. SAFETY SECTION cWARNING AND CAUTIONScCAUTION DO NOT ATTEMPT TO START THE BURNER WHEN 1.Excess oil has accumulatedPage A. CODES AND CLEARANCES a. Combustible materialb. Non-combustiblematerial A. CHIMNEY TYPE OFFROM MODEL NO1. PROPER CHIMNEY SIZE 2. PREVENTION OF CHIMNEY CONDENSING4. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION 3. PROPER CHIMNEY HEIGHT7. TIGHT CLEAN-OUTDOORS AND CONNECTIONS 6. TIGHT JOINTS8. NO INTERCONNECTED CHIMNEY FLUES 9 FLUE PIPE CLEARANCES, SIZING AND TYPEB. VENTING C. DRAFT REGULATORS ROTATION OF FRONT FLUE ELBOWNote Do not use with Direct Vent application D. DUCT WORK/AIR CONDITIONING Airflow Requirements and Sizing of Duct WorkPage The ASHRAE Handbook - Fundamentalsis an excellent source of duct system design principles and pressure drop data. Conversely, for a specified type of fitting, it is also possible to determine the required size or diameter of the component for a specified pressure drop and flow rate 1.HEATING CFM HEAT OUTPUT OF FURNACE BTUH 1.1 X TR TEMPERATURE RISE, F = HEATINGCFME. Air Filters Mounted Internal to Furnace MaximumModel Number Filter TypeF. LIMIT POSITION AND LOCATION G. BURNER INSTALLATION DO NOT CHANGE POSITION OF THE CHAMBERH. BURNER SPECIFICATIONS AND APPLICATIONS OIL NOZZLE CAPACITY CHART+ INSULATOR S = SLEEVE OR N = NONE NOZZLE SIZE2 STAGE FIRING RATES CAPACITYFIRING NOZZLE SIZEMOUNTING THE 2-STAGERIELLO BURNER I. OIL TANK AND PIPING5.A readily accessible, design-certified,manual oil shutoff valve, with a non-displaceablerotor member, shall be installed in the fuel oil supply piping within 6 feet of the appliance J. OIL FILTER K. ELECTRICAL WIRIINGAssembly MaximumWire size selections in Table 10 are based upon Table 310-16of the National Electrical Codefor three copper conductors, with insulation rated for 75 degrees Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation temperature ratings and ambient conditions, refer to the National Electrical Codefor the minimum wire sizing requirements Thermostat Anticipator Setting Preferred method of adjustment L. Blower Motor Speed Selection Heating Speed Set-ups OL6*A072DV5Furnace Motor Current Draw Amps/ / Watts vsLOW CAPACITY HIGH CAPACITY= Recommended heating speed setting Heating Speed Set-ups 2 - Stage OL6*X072DV5Cooling Speed Set-ups OL6**072DV5 Furnace Motor CurrentDraw Amps / Watts vs External Static Pressure in W.CPage M. BLOWER CONTROLLER INFORMATION FOR PSC MOTOR TERMINAL DEFINITIONS & FIELD WIRINGA. Inputs B. OutputsC. Operating Modes Heat Mode PSC TROUBLE SHOOTING DIAGNOSTIC FEATURESN. STARTUP PROCEDURES Operating InstructionsFor Your Safety Read Before Operating i.STOP! Read the safety information above2. Adjustment of Burner Combustion To Turn Off Oil to ApplianceCOMBUSTION HEAD SETTING FOR 2-STAGERIELLO BURNER TURN TO THE RIGHT SIGN + AIR DAMPER ADJUSTMENTTURN TO THE LEFT SIGN 1st STAGE ADJUSTMENT 2nd STAGE ADJUSTMENT3. Adjustment Of Heat Input Rate Notice Minimum return air temperature is 55F4. Setting Supply Air Temperature Rise 5. Checkout Procedure III. USERS INFORMATION SECTION C. INSPECTION AREAScCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF cCAUTION DO NOT ATTEMPT TO START THE BURNER WHENE. FILTER CLEANING AND LOCATION D. STARTING THE BURNERIV. INSTALLERS INSTRUCTIONS TO USER A.GENERAL INSPECTION V. DEALER MAINTENANCESAFETY DURING SERVICING AND INSPECTION C. HEAT EXCHANGER CLEANING INSTRUCTIONS B. HEAT EXCHANGERFigure 24 Heat Exchanger Clean-Outs Vacuum Hose Length OL6 8FTFilter maintenance procedure D. ELECTRICAL SYSTEME. SUPPLY/RETURN AIR BLOWER F. SUPPLY/RETURN AIR FILTERFilter replacement G. EXTENDED APPLIANCE SHUTDOWNON STARTUP 2.Remove the furnace front door Beckett Burner Riello BurnerVII. TROUBLESHOOTING A. DIAGNOSTICSDiagnostic Features PERSONNEL, AND NOT BY THE FURNACE OWNERB. CAD CELL CHECKOUT PROCEDURE VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page HEATING CUSTOMERSYSTEM Appendix - A Replacement Parts Replacement Parts for OL6F*072DPage Replacement Parts for OL6R*072D Page Appendix - B Wiring Diagrams OL6*A072D48 PSC Wiring DiagramOL6*A072DV5 ECM Wiring Diagram OL6*X072DV5 ECM 2-StageWiring Diagram