Thermo Products OL6FX072DV5(R), OL6FA072DV5(B/R), OL6RA072D48(B/R) B. Cad Cell Checkout Procedure

Page 59

If it is necessary to troubleshoot the flame sensor independently of the burner primary, the following procedure may be used.

B. CAD CELL CHECKOUT PROCEDURE:

1.Stop burner and shutoff electrical power to the appliance.

2.Open burner junction box (on top of the burner blower) and remove the plug-in portion of the cad cell by pulling it forward from and clear of the receptacle. Connect an ohmmeter across cad cell pins. With the cell exposed to direct room light, the measured resistance should be less than 2500 ohms (in fact, it may be less than 200 ohms).

3.Check the resistance across the cad cell pins with the cell covered (protected from exposure to ambient light). The resistance should be greater than 20,000 ohms.

4.If cell resistances are different from above, replace the plug-in portion of cell, (Honeywell Part No. 130367).

5.Carefully reinsert the plug-in portion of the cad cell into the receptacle. If the cad cell appears to be functioning correctly, troubleshoot the fan control module and the safety and ignition control (primary control) module, according to the Honeywell instructions covering the devices.

The troubleshooting chart beginning on the following page should help identify the type of malfunction or deviation from normal operation. To use this diagram, just follow the instructions in the boxes. If the answer is yes or the condition is true, go down to the next box. If the answer is no or the condition is false, go to the box on the right. Continue checking and answering questions and conditions in each box until a problem and/or repair is found. After any maintenance or repair, the trouble shooting sequence should be repeated until normal system operation is achieved.

56

Image 59
Contents OL6RX072DV5R OL6RA072D48B/ROL6FA072D48B/R OL6RA072DV5B/RCONTENTS Fuel ConfigurationFeature Model Number Digit1.Excess oil has accumulated I. SAFETY SECTIONcWARNING AND CAUTIONS cCAUTION DO NOT ATTEMPT TO START THE BURNER WHENPage a. Combustible material A. CODES AND CLEARANCESb. Non-combustiblematerial MODEL NO A. CHIMNEYTYPE OF FROM2. PREVENTION OF CHIMNEY CONDENSING 1. PROPER CHIMNEY SIZE3. PROPER CHIMNEY HEIGHT 4. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION9 FLUE PIPE CLEARANCES, SIZING AND TYPE 7. TIGHT CLEAN-OUTDOORS AND CONNECTIONS6. TIGHT JOINTS 8. NO INTERCONNECTED CHIMNEY FLUESB. VENTING Note Do not use with Direct Vent application ROTATION OF FRONT FLUE ELBOWC. DRAFT REGULATORS Airflow Requirements and Sizing of Duct Work D. DUCT WORK/AIR CONDITIONINGPage The ASHRAE Handbook - Fundamentalsis an excellent source of duct system design principles and pressure drop data. Conversely, for a specified type of fitting, it is also possible to determine the required size or diameter of the component for a specified pressure drop and flow rate 1.1 X TR TEMPERATURE RISE, F = HEATINGCFM 1.HEATING CFM HEAT OUTPUT OF FURNACE BTUHFilter Type E. Air Filters Mounted Internal to FurnaceMaximum Model NumberF. LIMIT POSITION AND LOCATION DO NOT CHANGE POSITION OF THE CHAMBER G. BURNER INSTALLATIONNOZZLE SIZE H. BURNER SPECIFICATIONS AND APPLICATIONSOIL NOZZLE CAPACITY CHART + INSULATOR S = SLEEVE OR N = NONENOZZLE SIZE 2 STAGE FIRING RATESCAPACITY FIRINGI. OIL TANK AND PIPING MOUNTING THE 2-STAGERIELLO BURNER5.A readily accessible, design-certified,manual oil shutoff valve, with a non-displaceablerotor member, shall be installed in the fuel oil supply piping within 6 feet of the appliance Maximum J. OIL FILTERK. ELECTRICAL WIRIING AssemblyWire size selections in Table 10 are based upon Table 310-16of the National Electrical Codefor three copper conductors, with insulation rated for 75 degrees Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation temperature ratings and ambient conditions, refer to the National Electrical Codefor the minimum wire sizing requirements Thermostat Anticipator Setting Preferred method of adjustment L. Blower Motor Speed Selection Draw Amps/ / Watts vs Heating Speed Set-upsOL6*A072DV5 Furnace Motor CurrentHeating Speed Set-ups 2 - Stage OL6*X072DV5 LOW CAPACITYHIGH CAPACITY = Recommended heating speed settingExternal Static Pressure in W.C Cooling Speed Set-ups OL6**072DV5Furnace Motor Current Draw Amps / Watts vsPage TERMINAL DEFINITIONS & FIELD WIRING M. BLOWER CONTROLLER INFORMATION FOR PSC MOTORB. Outputs A. InputsC. Operating Modes Heat Mode DIAGNOSTIC FEATURES PSC TROUBLE SHOOTINGi.STOP! Read the safety information above N. STARTUP PROCEDURESOperating Instructions For Your Safety Read Before OperatingTo Turn Off Oil to Appliance 2. Adjustment of Burner CombustionCOMBUSTION HEAD SETTING FOR 2-STAGERIELLO BURNER TURN TO THE LEFT SIGN AIR DAMPER ADJUSTMENTTURN TO THE RIGHT SIGN + 2nd STAGE ADJUSTMENT 1st STAGE ADJUSTMENTNotice Minimum return air temperature is 55F 3. Adjustment Of Heat Input Rate4. Setting Supply Air Temperature Rise 5. Checkout Procedure cCAUTION DO NOT ATTEMPT TO START THE BURNER WHEN III. USERS INFORMATION SECTIONC. INSPECTION AREAS cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELFD. STARTING THE BURNER E. FILTER CLEANING AND LOCATIONIV. INSTALLERS INSTRUCTIONS TO USER SAFETY DURING SERVICING AND INSPECTION V. DEALER MAINTENANCEA.GENERAL INSPECTION B. HEAT EXCHANGER C. HEAT EXCHANGER CLEANING INSTRUCTIONSVacuum Hose Length OL6 8FT Figure 24 Heat Exchanger Clean-OutsF. SUPPLY/RETURN AIR FILTER Filter maintenance procedureD. ELECTRICAL SYSTEM E. SUPPLY/RETURN AIR BLOWERG. EXTENDED APPLIANCE SHUTDOWN Filter replacementON STARTUP 2.Remove the furnace front door Riello Burner Beckett BurnerPERSONNEL, AND NOT BY THE FURNACE OWNER VII. TROUBLESHOOTINGA. DIAGNOSTICS Diagnostic FeaturesB. CAD CELL CHECKOUT PROCEDURE VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page SYSTEM CUSTOMERHEATING Replacement Parts for OL6F*072D Appendix - A Replacement PartsPage Replacement Parts for OL6R*072D Page OL6*A072D48 PSC Wiring Diagram Appendix - B Wiring DiagramsOL6*A072DV5 ECM Wiring Diagram OL6*X072DV5 ECM 2-StageWiring Diagram