Thermo Products OL6RA072D48(B/R), OL6FA072DV5(B/R), OL6FA072D48(B/R), OL6RA072DV5(B/R) Heat Mode

Page 37
Heat Mode

Heat Mode

When a call for heat (“W”) is received from the thermostat, if the “Cool” mode is not already active, the “T-T” terminal is energized and the blower on delay is started. The on-off pattern of DIP switch SW2 (positions 1 and 2) select one of four blower on delay values (see Table 11). When the delay time has elapsed, the “HEAT” blower speed is energized. The control remains in steady heat mode until the thermostat is satisfied. When the call for heat signal is removed, the “T-T” terminal is de-energized and the blower off delay is started. The on-off pattern of DIP switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 11). When the delay time has elapsed, the “HEAT” blower speed terminal is de-energized.

DIP SWITCH 2 SECTION STATE

BLOWER DELAY TIMES

 

1

2

3

4

Counter Flow

ON - SEC

 

OFF - MIN

ON - SEC

 

 

 

 

 

 

 

 

OFF

OFF

 

 

15

30

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

24

60

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

36

120

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

48

240

 

 

 

 

 

 

 

 

 

 

 

 

OFF

OFF

 

 

 

2

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

 

4

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

 

6

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

 

8

 

 

 

 

 

 

 

 

Table 11: ON and OFF Blower Delay Time Switch Settings

Motor Blower Speed

Three interconnected blower speed outputs are provided. A “G” call for fan will provide power to the LOW speed tap only. A “W” heat call will provide power to the Heat speed tap only. A “Y” cooling call will provide power to the Cool speed tap only.

In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the input that was first initiated. In the case where the control is in a cooling mode with both “Y” and “W” inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to the control switching into a heating mode. In the case where the control is in a heating mode with both “Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be executed prior to the control switching into a cooling mode. In the case where a call for fan “G” already exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective “W” or a “Y” speed following the blower on delay for that call.

The speed taps are interconnected and interlocked, only one speed may be powered at any one time. When a speed is to be operated, the speed select relays are operated to select the path to the motor tap and then the enable relay is operated to switch the operating power to the selected motor speed tap. If the speed of the running motor is to be changed, first the enable relay removes power from the motor, the new speed is selected and then power is restored to the motor.

Blower On and Off Delays

Four Heat blower on and four blower off delays are selected by two dip switches for each function. Refer to Table 11 for specific delay values.

34

Image 37
Contents OL6FA072D48B/R OL6RA072D48B/ROL6RA072DV5B/R OL6RX072DV5RCONTENTS Feature ConfigurationModel Number Digit FuelcWARNING AND CAUTIONS I. SAFETY SECTIONcCAUTION DO NOT ATTEMPT TO START THE BURNER WHEN 1.Excess oil has accumulatedPage a. Combustible material A. CODES AND CLEARANCESb. Non-combustiblematerial TYPE OF A. CHIMNEYFROM MODEL NO2. PREVENTION OF CHIMNEY CONDENSING 1. PROPER CHIMNEY SIZE3. PROPER CHIMNEY HEIGHT 4. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION6. TIGHT JOINTS 7. TIGHT CLEAN-OUTDOORS AND CONNECTIONS8. NO INTERCONNECTED CHIMNEY FLUES 9 FLUE PIPE CLEARANCES, SIZING AND TYPEB. VENTING C. DRAFT REGULATORS ROTATION OF FRONT FLUE ELBOWNote Do not use with Direct Vent application Airflow Requirements and Sizing of Duct Work D. DUCT WORK/AIR CONDITIONINGPage The ASHRAE Handbook - Fundamentalsis an excellent source of duct system design principles and pressure drop data. Conversely, for a specified type of fitting, it is also possible to determine the required size or diameter of the component for a specified pressure drop and flow rate 1.1 X TR TEMPERATURE RISE, F = HEATINGCFM 1.HEATING CFM HEAT OUTPUT OF FURNACE BTUHMaximum E. Air Filters Mounted Internal to FurnaceModel Number Filter TypeF. LIMIT POSITION AND LOCATION DO NOT CHANGE POSITION OF THE CHAMBER G. BURNER INSTALLATIONOIL NOZZLE CAPACITY CHART H. BURNER SPECIFICATIONS AND APPLICATIONS+ INSULATOR S = SLEEVE OR N = NONE NOZZLE SIZECAPACITY 2 STAGE FIRING RATESFIRING NOZZLE SIZEI. OIL TANK AND PIPING MOUNTING THE 2-STAGERIELLO BURNER5.A readily accessible, design-certified,manual oil shutoff valve, with a non-displaceablerotor member, shall be installed in the fuel oil supply piping within 6 feet of the appliance K. ELECTRICAL WIRIING J. OIL FILTERAssembly MaximumWire size selections in Table 10 are based upon Table 310-16of the National Electrical Codefor three copper conductors, with insulation rated for 75 degrees Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation temperature ratings and ambient conditions, refer to the National Electrical Codefor the minimum wire sizing requirements Thermostat Anticipator Setting Preferred method of adjustment L. Blower Motor Speed Selection OL6*A072DV5 Heating Speed Set-upsFurnace Motor Current Draw Amps/ / Watts vsHIGH CAPACITY LOW CAPACITY= Recommended heating speed setting Heating Speed Set-ups 2 - Stage OL6*X072DV5Furnace Motor Current Cooling Speed Set-ups OL6**072DV5Draw Amps / Watts vs External Static Pressure in W.CPage TERMINAL DEFINITIONS & FIELD WIRING M. BLOWER CONTROLLER INFORMATION FOR PSC MOTORB. Outputs A. InputsC. Operating Modes Heat Mode DIAGNOSTIC FEATURES PSC TROUBLE SHOOTINGOperating Instructions N. STARTUP PROCEDURESFor Your Safety Read Before Operating i.STOP! Read the safety information aboveTo Turn Off Oil to Appliance 2. Adjustment of Burner CombustionCOMBUSTION HEAD SETTING FOR 2-STAGERIELLO BURNER TURN TO THE RIGHT SIGN + AIR DAMPER ADJUSTMENTTURN TO THE LEFT SIGN 2nd STAGE ADJUSTMENT 1st STAGE ADJUSTMENTNotice Minimum return air temperature is 55F 3. Adjustment Of Heat Input Rate4. Setting Supply Air Temperature Rise 5. Checkout Procedure C. INSPECTION AREAS III. USERS INFORMATION SECTIONcCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF cCAUTION DO NOT ATTEMPT TO START THE BURNER WHEND. STARTING THE BURNER E. FILTER CLEANING AND LOCATIONIV. INSTALLERS INSTRUCTIONS TO USER A.GENERAL INSPECTION V. DEALER MAINTENANCESAFETY DURING SERVICING AND INSPECTION B. HEAT EXCHANGER C. HEAT EXCHANGER CLEANING INSTRUCTIONSVacuum Hose Length OL6 8FT Figure 24 Heat Exchanger Clean-OutsD. ELECTRICAL SYSTEM Filter maintenance procedureE. SUPPLY/RETURN AIR BLOWER F. SUPPLY/RETURN AIR FILTERG. EXTENDED APPLIANCE SHUTDOWN Filter replacementON STARTUP 2.Remove the furnace front door Riello Burner Beckett BurnerA. DIAGNOSTICS VII. TROUBLESHOOTINGDiagnostic Features PERSONNEL, AND NOT BY THE FURNACE OWNERB. CAD CELL CHECKOUT PROCEDURE VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page HEATING CUSTOMERSYSTEM Replacement Parts for OL6F*072D Appendix - A Replacement PartsPage Replacement Parts for OL6R*072D Page OL6*A072D48 PSC Wiring Diagram Appendix - B Wiring DiagramsOL6*A072DV5 ECM Wiring Diagram OL6*X072DV5 ECM 2-StageWiring Diagram