Thermo Products OL6RA072DV5(B/R), OL6FA072DV5(B/R), OL6RA072D48(B/R), OL6FA072D48(B/R)

Page 33
Manual background

For PSC systems, the ½ hp motor is equipped with 5 speeds. The unit is set for mid-fire temp rise @ 65ºF. See table for proper blower motor set up: OL6*A072D48

ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE

COOLING UNIT

 

 

 

HTG Speed by Input

 

 

 

Recommended CLG Speed

 

Low fire

 

 

Mid Fire

 

High Fire

 

24,000

 

ML

 

 

MED

 

MH

 

Med Low

 

 

 

30,000

 

ML

 

 

MED

 

MH

 

Med

 

 

 

36,000

 

ML

 

 

MED

 

MH

 

Med High

 

 

 

42,000

 

ML

 

 

MED

 

MH

 

High

 

 

 

48,000

 

ML

 

 

MED

 

MH

 

High

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed Tap\ Static

 

Furnace Airflow (CFM) vs. External Static pressure (in. WC.)

 

 

 

Pressure

 

 

0.2

 

 

0.3

 

 

0.4

 

0.5

0.6

 

 

 

Low

 

 

712

 

 

691

 

 

682

 

667

664

 

 

 

ML

 

 

902

 

 

899

 

 

896

 

883

874

 

 

 

MED

 

 

1113

 

 

1113

 

 

1109

 

1091

1073

 

 

 

MH

 

 

1270

 

 

1266

 

 

1250

 

1239

1215

 

 

 

High

 

 

1670

 

 

1637

 

 

1605

 

1566

1527

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Current Draw (Amps/Watts) vs. External Static pressure (in.

 

 

 

 

 

 

 

 

 

 

 

 

 

WC.)

 

 

 

 

 

 

Low

 

 

4.1/408

 

4.0/398

 

 

4.0/395

 

3.9/385

3.8/378

 

 

 

ML

 

 

5.3/540

 

5.3/535

 

 

5.2/527

 

5.1/512

4.9/500

 

 

 

MED

 

 

6.6/665

 

6.4/644

 

 

6.2/634

 

5.9/609

5.6/584

 

 

 

MH

 

 

7.6/772

 

7.2/739

 

 

6.9/713

 

6.6/682

6.4/663

 

 

 

High

 

 

9.6/951

 

84/830

 

 

9.0/887

 

8.8/869

8.4/835

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed Tap\ Static

 

High Fire Temperature Rise vs. External Static pressure (in. WC.)

 

 

Pressure

 

 

0.2

 

 

0.3

 

 

0.4

 

0.5

0.6

 

 

 

Low

 

 

119

 

 

122

 

 

124

 

127

127

 

 

 

ML

 

 

94

 

 

94

 

 

94

 

96

97

 

 

 

MED

 

 

76

 

 

76

 

 

76

 

77

79

 

 

 

MH

 

 

66

 

 

67

 

 

68

 

68

70

 

 

 

 

 

 

 

 

 

 

 

 

 

High

 

 

51

 

 

52

 

 

53

 

54

55

 

 

 

 

 

 

 

 

 

Speed Tap\ Static

 

Mid Fire Temperature Rise vs. External Static pressure (in. WC.)

 

 

Pressure

 

 

0.2

 

 

0.3

 

 

0.4

 

0.5

0.6

 

 

 

Low

 

 

96

 

 

99

 

 

100

 

102

103

 

 

 

ML

 

 

75

 

 

76

 

 

76

 

77

78

 

 

 

MED

 

 

61

 

 

61

 

 

61

 

62

63

 

 

 

MH

 

 

54

 

 

54

 

 

54

 

55

56

 

 

 

High

 

 

41

 

 

42

 

 

42

 

43

45

 

 

 

 

 

 

 

 

 

Speed Tap\ Static

 

Low Fire Temperature Rise vs. External Static pressure (in. WC.)

 

 

Pressure

 

 

0.2

 

 

0.3

 

 

0.4

 

0.5

0.6

 

 

 

Low

 

 

79

 

 

81

 

 

83

 

84

85

 

 

 

ML

 

 

62

 

 

63

 

 

63

 

64

64

 

 

 

MED

 

 

51

 

 

51

 

 

51

 

52

53

 

 

 

MH

 

 

44

 

 

44

 

 

45

 

45

46

 

 

 

High

 

 

34

 

 

34

 

 

35

 

36

37

 

 

Figure 19A: Heating speed by input

30

Image 33
Contents OL6FA072D48B/R OL6RA072D48B/ROL6RA072DV5B/R OL6RX072DV5RCONTENTS Feature ConfigurationModel Number Digit FuelcWARNING AND CAUTIONS I. SAFETY SECTIONcCAUTION DO NOT ATTEMPT TO START THE BURNER WHEN 1.Excess oil has accumulatedPage a. Combustible material A. CODES AND CLEARANCESb. Non-combustiblematerial TYPE OF A. CHIMNEYFROM MODEL NO2. PREVENTION OF CHIMNEY CONDENSING 1. PROPER CHIMNEY SIZE3. PROPER CHIMNEY HEIGHT 4. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION6. TIGHT JOINTS 7. TIGHT CLEAN-OUTDOORS AND CONNECTIONS8. NO INTERCONNECTED CHIMNEY FLUES 9 FLUE PIPE CLEARANCES, SIZING AND TYPEB. VENTING ROTATION OF FRONT FLUE ELBOW C. DRAFT REGULATORSNote Do not use with Direct Vent application Airflow Requirements and Sizing of Duct Work D. DUCT WORK/AIR CONDITIONINGPage The ASHRAE Handbook - Fundamentalsis an excellent source of duct system design principles and pressure drop data. Conversely, for a specified type of fitting, it is also possible to determine the required size or diameter of the component for a specified pressure drop and flow rate 1.1 X TR TEMPERATURE RISE, F = HEATINGCFM 1.HEATING CFM HEAT OUTPUT OF FURNACE BTUHMaximum E. Air Filters Mounted Internal to FurnaceModel Number Filter TypeF. LIMIT POSITION AND LOCATION DO NOT CHANGE POSITION OF THE CHAMBER G. BURNER INSTALLATIONOIL NOZZLE CAPACITY CHART H. BURNER SPECIFICATIONS AND APPLICATIONS+ INSULATOR S = SLEEVE OR N = NONE NOZZLE SIZECAPACITY 2 STAGE FIRING RATESFIRING NOZZLE SIZEI. OIL TANK AND PIPING MOUNTING THE 2-STAGERIELLO BURNER5.A readily accessible, design-certified,manual oil shutoff valve, with a non-displaceablerotor member, shall be installed in the fuel oil supply piping within 6 feet of the appliance K. ELECTRICAL WIRIING J. OIL FILTERAssembly MaximumWire size selections in Table 10 are based upon Table 310-16of the National Electrical Codefor three copper conductors, with insulation rated for 75 degrees Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation temperature ratings and ambient conditions, refer to the National Electrical Codefor the minimum wire sizing requirements Thermostat Anticipator Setting Preferred method of adjustment L. Blower Motor Speed Selection OL6*A072DV5 Heating Speed Set-upsFurnace Motor Current Draw Amps/ / Watts vsHIGH CAPACITY LOW CAPACITY= Recommended heating speed setting Heating Speed Set-ups 2 - Stage OL6*X072DV5Furnace Motor Current Cooling Speed Set-ups OL6**072DV5Draw Amps / Watts vs External Static Pressure in W.CPage TERMINAL DEFINITIONS & FIELD WIRING M. BLOWER CONTROLLER INFORMATION FOR PSC MOTORB. Outputs A. InputsC. Operating Modes Heat Mode DIAGNOSTIC FEATURES PSC TROUBLE SHOOTINGOperating Instructions N. STARTUP PROCEDURESFor Your Safety Read Before Operating i.STOP! Read the safety information aboveTo Turn Off Oil to Appliance 2. Adjustment of Burner CombustionCOMBUSTION HEAD SETTING FOR 2-STAGERIELLO BURNER AIR DAMPER ADJUSTMENT TURN TO THE RIGHT SIGN +TURN TO THE LEFT SIGN 2nd STAGE ADJUSTMENT 1st STAGE ADJUSTMENTNotice Minimum return air temperature is 55F 3. Adjustment Of Heat Input Rate4. Setting Supply Air Temperature Rise 5. Checkout Procedure C. INSPECTION AREAS III. USERS INFORMATION SECTIONcCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF cCAUTION DO NOT ATTEMPT TO START THE BURNER WHEND. STARTING THE BURNER E. FILTER CLEANING AND LOCATIONIV. INSTALLERS INSTRUCTIONS TO USER V. DEALER MAINTENANCE A.GENERAL INSPECTIONSAFETY DURING SERVICING AND INSPECTION B. HEAT EXCHANGER C. HEAT EXCHANGER CLEANING INSTRUCTIONSVacuum Hose Length OL6 8FT Figure 24 Heat Exchanger Clean-OutsD. ELECTRICAL SYSTEM Filter maintenance procedureE. SUPPLY/RETURN AIR BLOWER F. SUPPLY/RETURN AIR FILTERG. EXTENDED APPLIANCE SHUTDOWN Filter replacementON STARTUP 2.Remove the furnace front door Riello Burner Beckett BurnerA. DIAGNOSTICS VII. TROUBLESHOOTINGDiagnostic Features PERSONNEL, AND NOT BY THE FURNACE OWNERB. CAD CELL CHECKOUT PROCEDURE VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page CUSTOMER HEATINGSYSTEM Replacement Parts for OL6F*072D Appendix - A Replacement PartsPage Replacement Parts for OL6R*072D Page OL6*A072D48 PSC Wiring Diagram Appendix - B Wiring DiagramsOL6*A072DV5 ECM Wiring Diagram OL6*X072DV5 ECM 2-StageWiring Diagram