For PSC systems, the ½ hp motor is equipped with 5 speeds. The unit is set for
ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE
COOLING UNIT |
|
|
| HTG Speed by Input |
|
|
| Recommended CLG Speed | ||||||||
| Low fire |
|
| Mid Fire |
| High Fire |
| |||||||||
24,000 |
| ML |
|
| MED |
| MH |
| Med Low |
|
|
| ||||
30,000 |
| ML |
|
| MED |
| MH |
| Med |
|
|
| ||||
36,000 |
| ML |
|
| MED |
| MH |
| Med High |
|
|
| ||||
42,000 |
| ML |
|
| MED |
| MH |
| High |
|
|
| ||||
48,000 |
| ML |
|
| MED |
| MH |
| High |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
| Speed Tap\ Static |
| Furnace Airflow (CFM) vs. External Static pressure (in. WC.) |
|
| |||||||||||
| Pressure |
|
| 0.2 |
|
| 0.3 |
|
| 0.4 |
| 0.5 | 0.6 |
|
| |
| Low |
|
| 712 |
|
| 691 |
|
| 682 |
| 667 | 664 |
|
| |
| ML |
|
| 902 |
|
| 899 |
|
| 896 |
| 883 | 874 |
|
| |
| MED |
|
| 1113 |
|
| 1113 |
|
| 1109 |
| 1091 | 1073 |
|
| |
| MH |
|
| 1270 |
|
| 1266 |
|
| 1250 |
| 1239 | 1215 |
|
| |
| High |
|
| 1670 |
|
| 1637 |
|
| 1605 |
| 1566 | 1527 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
| Motor Current Draw (Amps/Watts) vs. External Static pressure (in. |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| WC.) |
|
|
|
|
|
| Low |
|
| 4.1/408 |
| 4.0/398 |
|
| 4.0/395 |
| 3.9/385 | 3.8/378 |
|
| ||
| ML |
|
| 5.3/540 |
| 5.3/535 |
|
| 5.2/527 |
| 5.1/512 | 4.9/500 |
|
| ||
| MED |
|
| 6.6/665 |
| 6.4/644 |
|
| 6.2/634 |
| 5.9/609 | 5.6/584 |
|
| ||
| MH |
|
| 7.6/772 |
| 7.2/739 |
|
| 6.9/713 |
| 6.6/682 | 6.4/663 |
|
| ||
| High |
|
| 9.6/951 |
| 84/830 |
|
| 9.0/887 |
| 8.8/869 | 8.4/835 |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| |||||
| Speed Tap\ Static |
| High Fire Temperature Rise vs. External Static pressure (in. WC.) |
| ||||||||||||
| Pressure |
|
| 0.2 |
|
| 0.3 |
|
| 0.4 |
| 0.5 | 0.6 |
|
| |
| Low |
|
| 119 |
|
| 122 |
|
| 124 |
| 127 | 127 |
|
| |
| ML |
|
| 94 |
|
| 94 |
|
| 94 |
| 96 | 97 |
|
| |
| MED |
|
| 76 |
|
| 76 |
|
| 76 |
| 77 | 79 |
|
| |
| MH |
|
| 66 |
|
| 67 |
|
| 68 |
| 68 | 70 |
|
| |
|
|
|
|
|
|
|
|
|
| |||||||
| High |
|
| 51 |
|
| 52 |
|
| 53 |
| 54 | 55 |
|
| |
|
|
|
|
|
| |||||||||||
| Speed Tap\ Static |
| Mid Fire Temperature Rise vs. External Static pressure (in. WC.) |
| ||||||||||||
| Pressure |
|
| 0.2 |
|
| 0.3 |
|
| 0.4 |
| 0.5 | 0.6 |
|
| |
| Low |
|
| 96 |
|
| 99 |
|
| 100 |
| 102 | 103 |
|
| |
| ML |
|
| 75 |
|
| 76 |
|
| 76 |
| 77 | 78 |
|
| |
| MED |
|
| 61 |
|
| 61 |
|
| 61 |
| 62 | 63 |
|
| |
| MH |
|
| 54 |
|
| 54 |
|
| 54 |
| 55 | 56 |
|
| |
| High |
|
| 41 |
|
| 42 |
|
| 42 |
| 43 | 45 |
|
| |
|
|
|
|
|
| |||||||||||
| Speed Tap\ Static |
| Low Fire Temperature Rise vs. External Static pressure (in. WC.) |
| ||||||||||||
| Pressure |
|
| 0.2 |
|
| 0.3 |
|
| 0.4 |
| 0.5 | 0.6 |
|
| |
| Low |
|
| 79 |
|
| 81 |
|
| 83 |
| 84 | 85 |
|
| |
| ML |
|
| 62 |
|
| 63 |
|
| 63 |
| 64 | 64 |
|
| |
| MED |
|
| 51 |
|
| 51 |
|
| 51 |
| 52 | 53 |
|
| |
| MH |
|
| 44 |
|
| 44 |
|
| 45 |
| 45 | 46 |
|
| |
| High |
|
| 34 |
|
| 34 |
|
| 35 |
| 36 | 37 |
|
|
Figure 19A: Heating speed by input
30