1PIPING PANEL REMOVAL AND PREPARING LINE

SET

Remove piping panel for easier access to service valves. Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.

CUT AND DEBUR

LINE SET SIZE MATCHES

SERVICE VALVE CONNECTION

SERVICE VALVE

CONNECTION

COPPER TUBE

STUB

REDUCER

LINE SET SIZE IS SMALLER

THAN CONNECTION

REFRIGERANT LINE

DO NOT CRIMP SERVICE VALVE

CONNECTOR WHEN PIPE IS

SMALLER THAN CONNECTION

2CAP AND CORE REMOVAL

Remove service cap and core from both the suction / vapor and liquid line service ports.

SERVICE PORT CAP

SERVICE PORT

CORE

LIQUID LINE SERVICE VALVE

SERVICE PORT

CORE

SERVICE

PORT CAP

SUCTION / VAPOR LINE

SERVICE VALVE

3ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES

AConnect gauge set low pressure side to liquid line service valve (service port).

BConnect gauge set center port to bottle of nitrogen with regulator.

CWith valve core removed from the suction / vapor line service port, nitrogen flow will have an exit point.

SUCTION / VAPOR SERVICE PORT MUST BE OPEN AND SERVICE PORT CORE REMOVED

TO ALLOW EXIT POINT FOR NITROGEN FLOW C

SUCTION / VAPOR

LINE

INDOOR

UNIT

LOW

ATTACH

GAUGES

SUCTION /

VAPOR LINE

SERVICE

VALVE

HIGH

B

OUTDOOR

UNIT

NITROGEN

LIQUID LINE

LIQUID LINE SERVICE

A

VALVE

 

 

Figure 9. Brazing Procedures

Page 14

506586−01 10/10

Image 14
Contents Heat Pumps Table of ContentsGeneral Model Number Identification Unit Dimensions −− Inches mmSide View Access View Base with Elongated LegsTypical Unit Parts Arrangement Control BOXShipping and Packing List Using Manifold Gauge SetOperating Service Valves To Access Service Port Operating Angle Type Service ValveOperating Ball Type Service Valve Reinstall Stem CapRecovering Refrigerant Recovering Refrigerant from Existing System1DISCONNECT Power 2CONNECT Manifold Gauge SETUnit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitRoof Mounting Removing and Installing PanelsStabilizing Unit on Uneven Surfaces Detail C Louvered Panel InstallationLouvered Panel Removal Detail D Detail aNew or Replacement Line Set Refrigerant Line SETRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1PIPING Panel Removal and Preparing Line SET 2CAP and Core RemovalBraze Line SET Wrap Service ValvesFlow Nitrogen 7PREPARATION for Next StepFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilSensing Bulb Installation Installing Indoor Expansion ValveIndoor Expansion Valve Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Leak TestEvacuating Line Set and Indoor Coil S S S SElectrical Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC Transformer4ROUTE High Voltage and Ground Wires 3A. Route Control Wires TingRoute Control Wires Ting Typical XP17 Wiring Heat Pump Control A175 Jumpers and Terminals Heat Pump Control AGEHeat Pump Control A175 Jumper and Terminal Descriptions Field Control Wiring Flat metal jumperFurnace Control Unit Start−Up Connections for Testing and ChargingServicing Units Delivered Void of Charge System RefrigerantAdding or Removing Refrigerant Cooling Mode Indoor Airflow CheckHeating Mode Indoor Airflow Check Airflowindoor CoilUsing HFC−410A Weigh In Method Subcooling Charging MethodAir Handler / Coil Match ups and Targeted Subcooling Values Operating and Temperature Pressures PsigSystem Operations Defrost SystemResistor Location Sensor Temperature / Resistance Range Unit SensorsDefrost Calibration Sequence of Operations YESTest Pin E33 Functions S SLow Pressure S87 Switch Operation Or belowHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 Resetting Fault and Lockout LED Codes System Status, Fault and Lockout LED CodesDS11 and DS14 ATUS, Fault Lockout LED Codes DS15 and DS13 Ault Lockout LED CodesAlert Status Moderate Device225ºF 107ºC Lockout Vice removed or Clears after FAN Motor B4 Test Procedure Field Configuration and TestingTroubleshooting FAN Motor Control A177 OPERATION,Fan Motor Control RPM, LED Code and DC Voltage Output Fan Motor Control Error/Fault LED CodesFan Motor Control Stage LED Indicator Codes Fan Motor Control Flash and Pause DurationsFAN Motor Position Adjustment TOP Grille or FAN Motor Mount Adjustment for FAN ClearanceTOP Grille Adjustment Demand BeginsFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Terminal StripStart FinishMaintenance Snow Guard Top CoverHomeowner SunSource Home Energy System Heating Mode XP17 Start−Up and Performance ChecklistCooling Mode START−UP Checks