Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS, 506586-01

Page 11

New or Replacement Line Set

REFRIGERANT LINE SET

This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 13.

IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in Table 2, use the procedure outlined under Flushing the System on page 13.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 8 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.

IMPORTANT

Refrigerant lines must not contact structure.

Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing the System on page 16).

Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.

Table 2. Refrigerant Line Set

 

 

Liquid

Vapor

L15

Model

 

Line Sets

 

Line

Line

 

 

Feet (Meters)

 

 

 

 

 

 

 

 

 

−024 and

 

3/8" (10)

3/4" (19)

L15 line set sizes are depen-

−030

 

 

 

 

dent on unit match up. See

 

 

 

 

 

 

 

 

XP17 Engineering Handbook to

 

 

 

 

−036, −042

 

 

 

determine correct line set sizes.

 

3/8" (10)

7/8" (22)

 

and −048

 

 

 

 

 

 

 

 

 

 

 

−060

 

3/8" (10)

1−1/8"

Field Fabricated

 

(29)

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

1−1/8" adapter

 

 

 

 

 

 

 

 

NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. :

To obtain the correct information from Lennox, be sure to communicate the following information:

SModel (XP17) and size of unit (e.g. −036).

SLine set diameters for the unit being installed as listed in table 2 and total length of installation.

SNumber of elbows vertical rise or drop in the piping.

The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.

Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.

WARNING

Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.

IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol ester oil.

Page 11

XP17 SERIES

Image 11
Contents Heat Pumps Table of ContentsGeneral Base with Elongated Legs Unit Dimensions −− Inches mmSide View Access View Model Number IdentificationControl BOX Typical Unit Parts ArrangementShipping and Packing List Using Manifold Gauge SetOperating Service Valves Reinstall Stem Cap Operating Angle Type Service ValveOperating Ball Type Service Valve To Access Service Port2CONNECT Manifold Gauge SET Recovering Refrigerant from Existing System1DISCONNECT Power Recovering RefrigerantUnit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementRoof Mounting Removing and Installing PanelsStabilizing Unit on Uneven Surfaces Detail D Detail a Louvered Panel InstallationLouvered Panel Removal Detail CRefrigerant Line SET New or Replacement Line SetRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 2CAP and Core Removal 1PIPING Panel Removal and Preparing Line SET7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen Braze Line SETFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilEqualizer Line Installation Installing Indoor Expansion ValveIndoor Expansion Valve Installation Sensing Bulb InstallationLeak Test Leak Test Line Set and Indoor CoilS S S S Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat Electrical4ROUTE High Voltage and Ground Wires 3A. Route Control Wires TingRoute Control Wires Ting Typical XP17 Wiring Heat Pump Control AGE Heat Pump Control A175 Jumpers and TerminalsHeat Pump Control A175 Jumper and Terminal Descriptions Flat metal jumper Field Control WiringFurnace Control System Refrigerant Connections for Testing and ChargingServicing Units Delivered Void of Charge Unit Start−UpAirflowindoor Coil Cooling Mode Indoor Airflow CheckHeating Mode Indoor Airflow Check Adding or Removing RefrigerantSubcooling Charging Method Using HFC−410A Weigh In MethodAir Handler / Coil Match ups and Targeted Subcooling Values Psig Operating and Temperature PressuresDefrost System System OperationsUnit Sensors Resistor Location Sensor Temperature / Resistance RangeYES Defrost Calibration Sequence of OperationsS S Test Pin E33 FunctionsOr below Low Pressure S87 Switch OperationHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 DS15 and DS13 Ault Lockout LED Codes System Status, Fault and Lockout LED CodesDS11 and DS14 ATUS, Fault Lockout LED Codes Resetting Fault and Lockout LED CodesModerate Device Alert Status225ºF 107ºC Lockout Vice removed or Clears after FAN Motor Control A177 OPERATION, Field Configuration and TestingTroubleshooting FAN Motor B4 Test ProcedureFan Motor Control Flash and Pause Durations Fan Motor Control Error/Fault LED CodesFan Motor Control Stage LED Indicator Codes Fan Motor Control RPM, LED Code and DC Voltage OutputDemand Begins TOP Grille or FAN Motor Mount Adjustment for FAN ClearanceTOP Grille Adjustment FAN Motor Position AdjustmentFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Finish StripStart TerminalSnow Guard Top Cover MaintenanceHomeowner SunSource Home Energy System START−UP Checks XP17 Start−Up and Performance ChecklistCooling Mode Heating Mode